Fire detection and alarm systems 1.10
1.10
Electrical alarm system call points should comply with either of the following.
a. BS 5839-2.
b. BS EN 54-11 Type A (direct operation).
Call points should be installed in accordance with BS 5839-1.
Type B (indirect operation) call points of BS EN 54-11 should only be used with the approval of the building control body.