Approved Document B: Fire Safety, Volume 2: Buildings other than dwellings
Fire safety requirements for buildings other than dwellings: means of warning and escape, internal fire spread, external fire spread, and access and facilities for the fire service.
Title page
The Building Regulations 2010
Fire safety
APPROVED DOCUMENT B
Volume 2: Buildings other than dwellings
Also includes: 2029 amendments
2019 edition incorporating 2020, 2022, 2025
and 2026 amendments and forthcoming
2029 changes – for use in England
Main changes made by the 2020 amendments
The changes focus on the following fire safety provisions in blocks of flats (Volume 1):
In addition a typographical error is corrected in both volumes. Purpose group number 2 is now included in reference to ‘residential’ buildings in the guidance on boundaries.
The changes are set out in the May 2020 AD B amendments.
Main changes made by the 2022 amendments
The changes focus on the following fire safety provisions:
Updated provisions in Section 12 for residential buildings (purpose groups 1 and 2) with a storey 11m or more in height.
The changes are set out in the June 2022 AD B amendment booklet and the November 2022 correction notice.
Main changes made by the 2025 amendments
The changes focus on the following fire safety provisions:
The changes are set out in the March 2025 AD B amendments.
Main changes made by the 2026 amendments
The changes focus on the following fire safety provisions:
The changes are set out in the September 2026 AD B amendments.
Changes made by the 2029 amendments
This document also includes the 2029 amendments to Approved Document B Volume 2, as laid out in the respective amendment booklet.
2029 amendments
The 2029 amendments take effect on 2 September 2029 for use in England. The 2019 edition incorporating the 2020, 2022, 2025 and 2026 amendments will continue to apply where a building notice or an initial notice has been given to, or a building control approval application with full plans made to, the relevant authority before 2 September 2029 and either the building work to which it relates:
a. has started and is sufficiently progressed before that day; or
b. is started and is sufficiently progressed within the period of six months beginning on that day.
The changes focus on the fire safety provisions regarding the removal of national classes for fire resistance.
Please note that ‘building notice’, ‘initial notice’ and ‘building control approval application with full plans’ have the meanings given in the Building Regulations 2010. For the purpose of these transitional arrangements, building work is to be regarded as ‘sufficiently progressed’:
Introduction
What is an approved document?
Approved documents are approved by the Secretary of State and give practical guidance on common building situations about how to meet the requirements of the Building Regulations 2010 for England. Different approved documents give guidance on each of the technical parts of the regulations. These are all listed in the back of the approved documents. In addition to guidance, some approved documents include provisions that must be followed exactly, as required by regulations or where methods of test or calculation are approved by the Secretary of State.
Each approved document covers the requirements of the Building Regulations 2010 relating to a different aspect of building work. Building work must also comply with all other applicable requirements of the Building Regulations 2010 and all other applicable legislation.
How is construction regulated in England?
Most building work being carried out in England must comply with the Building Regulations 2010. The Building Regulations are made under powers in the Building Act 1984.
Building Regulations protect the health and safety of people in and around buildings, they also provide for energy and water conservation and access to and use of buildings.
The Manual to the Building Regulations (references to this in the introduction are taken from the first edition) gives an overview of the building regulatory system in England. You can access the most recent version of the manual at: www.gov.uk/guidance/building-regulationsand-approved-documents-index.
How do you comply with the Building Regulations?
Building work must meet all relevant requirements of the Building Regulations. To comply with the Building Regulations, it is necessary both to follow the correct procedures and meet technical performance requirements.
The approved documents set out what, in ordinary circumstances, may be accepted as one way to comply with the Building Regulations. Note, however, that:
Those responsible for building work include agents, designers, builders, installers and the building owner. For further information, see Chapter 7 in Volume 1 and paragraphs A26, B2 and F2 in Volume 2 of the Manual to the Building Regulations.
The Building Regulations can be contravened by not following the correct procedures or not meeting the technical performance requirements. If the building owner or those responsible for the works contravene the Building Regulations, the local authority may prosecute them in the magistrates’ court. For further information on enforcement and sanctions in the existing system, see Chapter B in Volume 2 of the Manual to the Building Regulations.
What do the Building Regulations cover?
‘Building work’ is a legal term for work covered by the Building Regulations. Where a building is not exempt, the Building Regulations apply to all types of building work as defined in regulation 3 of the Building Regulations. For further information, what constitutes building work is covered in Chapter A, Volume 2 of the Manual to the Building Regulations.
The Building Regulations contain sections dealing with definitions, procedures and the expected technical performance of building work. For example, the Building Regulations:
When must a building control body be notified?
It is often necessary to notify a building control body of planned building work. To help ensure that work complies with the Building Regulations, those responsible for building work may need to use one of the two types of building control body listed below:
If building work consists only of installing certain types of services or fittings (e.g. fuel-burning appliances or replacement windows) and the building owner employs an installer that is registered with a relevant competent person scheme designated in the regulations, a building control body does not need to be notified.
How to use this approved document
Each approved document contains:
They may not provide appropriate guidance if the case is unusual in terms of its design, setting, use, scale or technology. Non-standard conditions may include any of the following:
Anyone using the approved documents should have sufficient knowledge and skills to understand the guidance and correctly apply it to the building work. This is important because simply following the guidance does not guarantee that your building work will comply with the legal requirements of the Building Regulations. Each approved document contains legal requirements (which you must follow) and guidance (which you may or may not choose to follow). The text in a box with a green background at the beginning of each section of an approved document is taken from the Building Regulations. This text sets out the legal requirements.
The explanation which follows the legal requirements is guidance (see Diagram i below). The guidance then explains one or more ways to demonstrate how building work can be shown to comply with the legal requirements in common circumstances. The terms in green lettering in an approved document are key terms, listed and explained in the appendix to that approved document. Guidance in the approved documents addresses most, but not all, situations that building owners will face. Situations may arise that are not covered. You or your advisers will need to carefully consider whether following the guidance will mean that the requirements of the Building Regulations will be met.
For further information about the use of technical guidance, see Chapter 7 in Volume 1 and Chapter F in Volume 2 of the Manual to the Building Regulations.
Diagram i The relationship between regulations and guidance in the approved documents

Where to get further help
If you are unsure whether you have the knowledge and skills to apply the guidance correctly, or if you do not understand the technical guidance or other information in this approved document or the additional detailed technical references to which it directs you, you should seek further help. Some sources of help are listed below.
Section 0: Approved Document B: Fire safety – buildings other than dwellings
Summary
0.1
This approved document has been published in two volumes. Volume 1 deals solely with dwellings, including blocks of flats, while Volume 2 deals with all other types of building covered by the Building Regulations.
Arrangement of sections
0.2
Requirements B1–B5 of Schedule 1 to the Building Regulations are dealt with separately in one or more sections. Each requirement is shown at the start of the relevant sections.
0.3
The provisions in this document have the following aims:
Requirement B1: When there is a fire, ensure both:
Requirement B2: Inhibit the spread of fire over internal linings of buildings.
Requirement B3: The building must be built such that all of the following are achieved in the event of a fire:
Requirement B4: Restrict both:
Requirement B5: Ensure both:
Regulation 38: Provide fire safety information to building owners.
0.4
Guidance is given on each aspect separately, though many are closely interlinked. The document should be considered as a whole. The relationship between different requirements and their interdependency should be recognised. Particular attention should be given to the situation where one part of the guidance is not fully followed as this could have a negative effect on other provisions.
Appendices: Information common to more than one requirement of Part B
0.5
Guidance on matters that refer to more than one section of this document can be found in the following appendices.
Appendix A: Key terms
Appendix B: Performance of materials, products and structures
Appendix C: Fire doorsets
Appendix D: Methods of measurement
Appendix E: Sprinklers
Appendix F: Standards referred to
Appendix G: Documents referred to
Management of premises
0.6
The Building Regulations do not impose any requirements on the management of a building, but do assume that it will be properly managed. This includes, for example, keeping protected escape routes virtually ‘fire sterile’.
Appropriate fire safety design considers the way in which a building will be managed. Any reliance on an unrealistic or unsustainable management regime cannot be considered to have met the requirements of the regulations.
Once the building is in use, the management regime should be maintained and a suitable risk assessment undertaken for any variation in that regime. Failure to take proper management responsibility may result in the prosecution of an employer, building owner or occupier under legislation such as the Regulatory Reform (Fire Safety) Order 2005.
Property protection
0.7
The Building Regulations are intended to ensure a reasonable standard of life safety in a fire. The protection of property, including the building itself, often requires additional measures. Insurers usually set higher standards before accepting the insurance risk.
Many insurers use the RISCAuthority Design Guide for the Fire Protection of Buildings by the Fire Protection Association (FPA) as a basis for providing guidance to the building designer on what they require.
Further information on the protection of property can be obtained from the FPA website: www.thefpa.co.uk.
Inclusive design
0.8
The fire safety aspects of the Building Regulations aim to achieve reasonable standards of health and safety for people in and around buildings.
People, regardless of ability, age or gender, should be able to access buildings and use their facilities. The fire safety measures incorporated into a building should take account of the needs of everyone who may access the building, both as visitors and as people who live or work in it. It is not appropriate, except in exceptional circumstances, to assume that certain groups of people will be excluded from a building because of its use.
The provisions in this approved document are considered to be of a reasonable standard for most buildings. However, some people’s specific needs might not be addressed. In some situations, additional measures may be needed to accommodate these needs. This should be done on a case-by-case basis.
Alternative approaches
0.9
The fire safety requirements of the Building Regulations will probably be satisfied by following the relevant guidance in this approved document. However, approved documents provide guidance for some common building situations and there may be alternative methods of complying with the Building Regulations’ requirements.
If alternative methods are adopted, the overall level of safety should not be lower than the approved document provides. It is the responsibility of those undertaking the work to demonstrate compliance.
If other standards or guidance documents are adopted, the relevant fire safety recommendations in those publications should be followed in their entirety. However, in some circumstances it may be necessary to use one publication to supplement another. Care must be taken when using supplementary guidance to ensure that an integrated approach is used in any one building.
Guidance documents intended specifically for assessing fire safety in existing buildings often include less onerous provisions than those for new buildings and are therefore unlikely to be appropriate for building work that is controlled by the Building Regulations.
Buildings for industrial and commercial activities that present a special fire hazard, e.g. those that sell fuels, may require additional fire precautions to those in this approved document.
Health care premises
0.10
Health care premises and the patients who use them are diverse. Patients using the premises require different types of care to suit their specific needs. The choice of fire safety strategy depends on both of the following.
The Department of Health (DoH) guidance documents on fire precautions in health care buildings, Firecode, take account of the particular characteristics of these buildings and should be followed.
Firecode contains managerial and other fire safety provisions that are outside the scope of the Building Regulations.
Unsupervised group homes
0.11
An unsupervised group home for not more than six mental health service users should be regarded as having a purpose group of either of the following.
Shopping complexes
0.12
Although the guidance in this document may be readily applied to individual shops, shopping complexes present different escape problems. The design of units within a shopping complex should be compatible with the fire strategy for the complex as a whole. A suitable approach is given in Annex E of BS 9999.
Assembly buildings
0.13
Assembly buildings where a large number of people are present require additional considerations for means of escape; for example, fixed seating may limit the ability of people to escape.
Guidance on fixed seating and other aspects of means of escape in assembly buildings is given in Annex D of BS 9999.
For buildings to which the Safety of Sports Grounds Act 1975 applies, the Sports Grounds Safety Authority’s Guide to Safety at Sports Grounds should also be followed.
Schools
0.14
The design of fire safety in schools is covered by Building Bulletin 100, which should be used. Building Bulletin 100 contains fire safety provisions that are outside the scope of the Building Regulations.
Prisons provided under section 33 of the Prisons Act 1952
0.15
Prisons are exempted from the functional requirements of Parts B1 to B5 of the Building Regulations under section 33 of the Prisons Act 1952. It is usual that prisons should comply with the fire safety requirements of the Building Regulations, except where the requirements are incompatible with safe custody, good order or security.
HM Prison and Probation Service (HMPPS) provides guidance documents on fire precautions in prisons, which take account of the public safety need to secure doors and exits while maintaining life safety objectives.
The HMPPS Custodial Premises Fire Safety Design Guide (FSDG) is the design standard for fire safety in prisons, providing structured guidance for those involved in the planning, designing or approval of new or altered buildings.
Further guidance documents on fire safety in prisons are provided by HMPPS. These documents may also be used for other places of lawful detention.
Buildings containing one or more atria
0.16
A building with an atrium that passes through compartment floors may need special fire safety measures. Guidance is given in Annexes B and C of BS 9999.
Buildings of special architectural or historic interest
0.17
Where Part B applies to existing buildings, particularly buildings of special architectural or historic interest for which the guidance in this document might prove too restrictive, some variation of the provisions in this document may be appropriate. In such cases, it is appropriate to assess the hazard and risk in the particular case and consider a range of fire safety features in that context.
Fire safety engineering
0.18
Fire safety engineering might provide an alternative approach to fire safety. Fire safety engineering may be the only practical way to achieve a satisfactory standard of fire safety in some complex buildings and in buildings that contain different uses.
Fire safety engineering may also be suitable for solving a specific problem with a design that otherwise follows the provisions in this document.
0.19
BS 7974 and supporting published documents (PDs) provide a framework for and guidance on the application of fire safety engineering principles to the design of buildings.
Purpose groups
0.20
Building uses are classified within different purpose groups, which represent different levels of hazard (see Table 0.1). A purpose group can apply to a whole building or to a compartment within the building, and should relate to the main use of the building or compartment.
0.21
Where a building or compartment has more than one use, it is appropriate to assign each different use to its own purpose group in the following situations.
0.22
Where there are multiple main uses that are not ancillary to one another (for example, shops with independent offices above), each use should be assigned to a purpose group in its own right. Where there is doubt as to which purpose group is appropriate, the more onerous guidance should be applied.
Table 0.1 Classification of purpose groups
| Volume 1 purpose groups | ||
|---|---|---|
| Title | Group | Purpose for which the building or compartment of a building is intended to be used |
| Residential (dwellings) | 1(a)(1) | Flat. |
| 1(b)(2) | Dwellinghouse that contains a habitable storey with a floor level a minimum of 4.5m above ground level up to a maximum of 18m.(3) | |
| 1(c)(2)(4) | Dwellinghouse that does not contain a habitable storey with a floor level a minimum of 4.5m above ground level. | |
| Volume 2 purpose groups | ||
| Residential (institutional) | 2(a) | Hospital, home, school or other similar establishment, where people sleep on the premises. The building may be either of the following: • Living accommodation for, or accommodation for the treatment, care or maintenance of, either: - disabled people with a range of impairments including physical, sensory and cognitive impairments, or mental health conditions - people under the age of 5 years. • A place of lawful detention. |
| Residential (other) | 2(b) | Hotel, boarding house, residential college, hall of residence, hostel or any other residential purpose not described above. |
| Office | 3 | Offices or premises used for any of the following and their control: • administration • clerical work (including writing, bookkeeping, sorting papers, filing, typing, duplicating, machine calculating, drawing and the editorial preparation of matter for publication, police and fire and rescue service work) • handling money (including banking and building society work) • communications (including postal, telegraph and radio communications) • radio, television, film, audio or video recording • performance (premises not open to the public). |
| Shop and commercial | 4 | Shops or premises used for either of the following. • A retail trade or business (including selling food or drink to the public for immediate consumption, retail by auction, self-selection and over-the-counter wholesale trading, the business of lending books or periodicals for gain, the business of a barber or hairdresser, and the rental of storage space to the public). • Premises to which the public are invited either: – to deliver or collect goods in connection with their hire, repair or other treatment – (except in the case of repair of motor vehicles) where the public themselves may carry out such repairs or other treatments. |
| Assembly and recreation | 5 | Place of assembly, entertainment or recreation, including any of the following: • bingo halls, broadcasting, recording and film studios open to the public, casinos, dance halls • entertainment, conference, exhibition and leisure centres • funfairs and amusement arcades • museums and art galleries, non-residential clubs, theatres, cinemas, concert halls • educational establishments, dancing schools, gymnasia, swimming pool buildings, riding schools, skating rinks, sports pavilions, sports stadia • law courts • churches and other buildings of worship, crematoria • libraries open to the public, non-residential day centres, clinics, health centres and surgeries • passenger stations and termini for air, rail, road or sea travel • public toilets • zoos and menageries. |
| Industrial | 6 | Factories and other premises used for any of the following: • manufacturing, altering, repairing, cleaning, washing, breaking up, adapting or processing any article • generating power • slaughtering livestock. |
| Storage and other nonresidential(4) | 7(a) | Either of the following: • place (other than described under 7(b)) for the storage or deposit of goods or materials • any building not within purpose groups 1 to 6. |
| 7(b) | Car parks designed to admit and accommodate only cars, motorcycles and passenger or light goods vehicles that weigh a maximum of 2500kg gross. | |
NOTES:
This table only applies to Part B.
See Approved Document B Volume 1 for guidance on dwellings (purpose group 1).
Mixed use buildings
0.23
This approved document includes reference to selected guidance for dwellings. For the design of mixed use buildings which include dwellings, Approved Document B Volume 1 should be consulted in addition to the guidance contained in this approved document.
0.24
Where a complex mix of uses exists, the effect that one use may have on another in terms of risk should be considered. It could be necessary to use guidance from both volumes, apply other guidance (such as from HTM 05-02 or Building Bulletin 100), and/or apply special measures to reduce the risk.
Requirement B1: Means of warning and escape
These sections deal with the following requirement from Part B of Schedule 1 to the Building Regulations 2010.
Requirement
| Requirement | Limits on application |
|---|---|
Means of warning and escape B1. The building shall be designed and constructed so that there are appropriate provisions for the early warning of fire, and appropriate means of escape in case of fire from the building to a place of safety outside the building capable of being safely and effectively used at all material times. | Requirement B1 does not apply to any prison provided under section 33 of the Prison Act 1952(a) (power to provide prisons, etc.). (a) 1952 c. 52; section 33 was amended by section 100 of the Criminal Justice and Public Order Act 1994 (c. 33) and by S.I. 1963/597. |
Intention
In the Secretary of State’s view, requirement B1 is met by achieving all of the following.
The extent to which any of these measures are necessary is dependent on the use of the building, its size and its height.
Building work and material changes of use subject to requirement B1 include both new and existing buildings.
Section 1: Fire detection and alarm systems
General provisions
1.1
All buildings should have arrangements for detecting fire and raising the alarm. In most buildings, fires are detected by people, either by sight or smell, and therefore often nothing more is needed.
1.2
In some small buildings/premises, the means of raising the alarm may be simple (for example, a shouted warning). In assessing appropriate solutions, warnings need to be heard and understood throughout the premises.
Fire detection and alarm systems
1.3
Other than for some small buildings/premises, an electrically operated fire alarm system should be provided. In some situations, the alarm should be operated by a fire detection system. The detailed specification should be compatible with the fire strategy for the building.
NOTE: The term ‘fire alarm system’ describes the combination of components for giving an audible and/or other perceptible warning of fire.
NOTE: In this document, the term ‘fire detection system’ describes any type of automatic sensor network and associated control and indicating equipment. Sensors may be sensitive to smoke, heat, gaseous combustion products or radiation. Automatic sprinkler systems can also be used to operate a fire alarm system.
1.4
In ‘residential (institutional)’ and ‘residential (other)’ occupancies (purpose groups 2(a) and 2(b)), automatic fire detection and alarms should be provided.
1.5
Automatic fire detection and alarm systems should be provided in non-residential occupancies where a fire could break out in an unoccupied part of the premises (e.g. a storage area or a part of the building that is not visited on a regular basis) and prejudice the means of escape from occupied part(s) of the premises.
1.6
Automatic fire detection will also be necessary where fire protection systems, such as pressure differential systems or door releases, need to operate automatically.
1.7
Every building design should be assessed individually. General guidance on the category of fire detection system that may need to be provided within a building can be found in Table A1 of BS 5839-1.
1.8
Where an electrically operated fire detection and alarm system is provided, it should comply with BS 5839-1.
1.9
BS 5839-1 specifies three categories of system.
Category L systems are divided into the following.
L1 – systems installed throughout the protected building.
L2 – systems installed only in defined parts of the protected building (a category L2 system will normally include the coverage required of a category L3 system).
L3 – systems designed to warn of fire at an early enough stage to enable all occupants, other than possibly those in the room where the fire started, to escape safely before the escape routes become impassable because of fire, smoke or toxic gases.
L4 – systems installed within those parts of the escape routes that comprise circulation areas and circulation spaces, such as corridors and stairs.
L5 – systems in which the protected area(s) and/or the location of detectors are designed to satisfy a specific fire safety objective (other than that of a category L1, L2, L3 or L4 system).
Type P systems are divided into the following.
P1 – systems installed throughout the protected building.
P2 – systems installed only in defined parts of the protected building.
1.10
Electrical alarm system call points should comply with either of the following.
Call points should be installed in accordance with BS 5839-1.
Type B (indirect operation) call points of BS EN 54-11 should only be used with the approval of the building control body.
1.11
A voice alarm system complying with BS 5839-8, and giving a fire warning different from other signals in general use, may be considered if either of the following applies.
1.12
In premises where lots of members of the public are present, an initial general alarm may be undesirable. Any fire alarm system that first alerts staff should comply with BS 5839-1.
1.13
Where the escape strategy is based on simultaneous evacuation, actuation of the fire alarm system should give warning from all fire alarm sounders. Where phased evacuation is planned, a staged alarm system is appropriate. See paragraph 3.21.
1.14
BS 9999 provides guidance for fire detection and alarm systems in buildings containing atria.
Warnings for people with impaired hearing
1.15
Clause 18 of BS 5839-1 gives detailed guidance on the design and selection of fire alarm warnings for people with impaired hearing. In buildings or part of a building where people may be in relative isolation, a visual and audible fire alarm may be the most appropriate solution. In buildings where the population is managed, a vibrating personal paging system may be more appropriate.
Design and installation of systems
1.16
Fire detection and alarm systems must be properly designed, installed and maintained. A design, installation and commissioning certificate should be provided for fire detection and alarm systems. Third party certification schemes for fire protection products and related services are an effective means of providing assurances of quality, reliability and safety.
Interface between fire detection and alarm systems and other systems
1.17
Fire detection and alarm systems sometimes trigger other systems. The interface between systems must be reliable. Particular care should be taken if the interface is facilitated via another system. Where any part of BS 7273 applies to the triggering of other systems, the recommendations of that part of BS 7273 should be followed.
Student accommodation
1.18
In student residences that are designed and occupied as a block of flats, separate automatic detection should be provided in each self-contained flat where all of the following apply.
Where a total evacuation strategy is adopted, the alarm system should follow the guidance elsewhere in this section.
Section 2: Design for horizontal escape
Introduction
2.1
Means of escape should be provided from any point on a storey to the storey exit, for all types of building. The general principle is that any person confronted by a fire within a building can turn away from it and escape safely.
2.2
For small shop, office, industrial, storage and other similar premises, the guidance on small premises (see section 4) may be followed instead of the provisions in this section, if they meet both of the following conditions.
Escape route design
Number of escape routes and exits
2.3
The number of escape routes and exits that should be provided depends on both of the following.
2.4
In multi-storey buildings, if more than one stair is needed for vertical escape, every part of each storey should have access to more than one stair. An area may be in a dead end provided the alternative stair is accessible.
2.5
In mixed use buildings, separate means of escape should be provided from any storeys or parts of storeys used for the ‘residential’ or ‘assembly and recreation’ purpose groups (purpose groups 1, 2 and 5).
Single escape routes and exits
2.6
A single escape route is acceptable for either of the following.
2.7
In many cases, the beginning of a route will not have an alternative escape route (for example, a single exit from a room into a corridor where escape is possible in two directions). This is acceptable if both of the following apply.
Diagram 2.1 shows how to measure travel distances from a dead end in an open storey layout.
Diagram 2.1 Travel distance in dead-end condition

Table 2.1 Limitations on travel distance
| Maximum travel distance(1) where travel is possible in: | ||||
|---|---|---|---|---|
| Purpose group | Use of the premises or part of the premises | One direction only (m) | More than one direction (m) | |
| 2(a) | Residential (institutional) | 9 | 18 | |
| 2(b) | Residential (other): | |||
a. in bedrooms(2) | 9 | 18 | ||
b. in bedroom corridors | 9 | 35 | ||
c. elsewhere | 18 | 35 | ||
| 3 | Office | 18 | 45 | |
| 4 | Shop and commercial | 18 | 45 | |
| 5 | Assembly and recreation: | |||
a. buildings primarily for disabled people | 9 | 18 | ||
b. areas with seating in rows | 15 | 32 | ||
c. elsewhere | 18 | 45 | ||
| 6 | Industrial(3) | Normal hazard | 25 | 45 |
| Higher hazard | 12 | 25 | ||
| 7 | Storage and other non-residential(3) | Normal hazard | 25 | 45 |
| Higher hazard | 12 | 25 | ||
| 2–7 | Place of special fire hazard(4) | 9(5) | 18(5) | |
| 2–7 | Plant room or roof-top plant: | |||
a. distance within the room | 9 | 35 | ||
b. escape route not in open air (overall travel distance) | 18 | 45 | ||
c. escape route in open air (overall travel distance) | 60 | 100 | ||
NOTES:
Access control measures
2.8
Measures to restrict access to the building (or parts of it) should not adversely affect fire safety provisions. It may be reasonable to close some escape routes outside normal business hours, but measures should remain to safely evacuate people left inside the building (see paragraph 5.6).
Number of occupants and exits
2.9
The building design should be based on the number of occupants. If the number is not known, use the appropriate floor space factors (Appendix D).
Table 2.2 gives the minimum number of escape routes and exits from a room or storey for different numbers of occupants. This number is likely to be increased by the need to observe travel distances and other practical considerations.
The width of escape routes and exits is given in paragraph 2.18.
Table 2.2 Minimum number of escape routes and exits from a room, tier or storey
| Maximum number of people | Minimum number of escape routes/exits |
|---|---|
| 60 | 1 |
| 600 | 2 |
| More than 600 | 3 |
Alternative escape routes
2.10
Alternative escape route should satisfy one of the following criteria.
Diagram 2.2 Alternative escape routes

Inner rooms
2.11
An inner room is at risk if a fire starts in the access room (Diagram 2.3). Such an arrangement should only be accepted if all of the following conditions are satisfied.
Diagram 2.3 Inner room and access room

Planning of exits in a central core
2.12
Where a central core has more than one exit, storey exits should be remote from one another and no two exits should be approached from the same lift hall, common lobby or undivided corridor (Diagram 2.4).
Open spatial planning
2.13
Escape routes should not be within 4.5m of openings between floors, such as for an escalator, unless either of the following applies.
Diagram 2.4 Exits in a central core

Diagram 2.5 Open connections

Access to storey exits
2.14
Where a storey has more than one escape stair, it should be planned so that it is not necessary to pass through one stair to reach another. However, it would be acceptable to pass through one stair’s protected lobby to reach another stair.
Separation of circulation routes from protected stairways
2.15
Where they serve protected stairways that are part of primary circulation routes, self-closing fire doors should be fitted with an automatic release mechanism, to avoid them being rendered ineffective by misuse. Otherwise, the stair (and any associated exit passageway) should not form part of the primary circulation route between different parts of the building at the same level.
Storeys divided into different uses
2.16
If a storey contains areas for consuming food and/or drink, and where that is not the main use of the building, then both of the following apply.
Storeys divided into different occupancies
2.17
Where a storey is divided into areas of occupancy under separate ownership or tenancy, then both of the following apply.
Width of escape routes and exits
2.18
The width of escape routes and exits should meet the provisions in Table 2.3, as well as the guidance in Approved Document M.
2.19
If the maximum number of people likely to use the escape route and exit is not known, it should be calculated using the occupant number guidance in Appendix D.
2.20
Guidance on the spacing of fixed seating for auditoria is given in Annex D of BS 9999.
Table 2.3 Widths of escape routes and exits
| Maximum number of people | Minimum width (mm)(1)(2)(3) |
|---|---|
| 60 | 750(4) |
| 110 | 850 |
| 220 | 1050 |
| More than 220 | 5 per person(5) |
NOTES:
Calculating exit capacity
2.21
Where multiple storey exits are available, fire might prevent one from being used. Remaining exits need to be wide enough for all occupants, so when using Table 2.3, the largest exit should be discounted.
Stairs should be at least as wide as any storey exit leading onto them. While some stairs are not subject to discounting (paragraphs 3.14 and 3.15), because the stairs will be available for other floors, the storey exits onto them are.
2.22
To calculate how many people two or more available exits (after discounting) can accommodate, add together the maximum numbers of people that each exit width can accommodate.
For example, three exits each 850mm wide accommodate 3×110 = 330 people.
2.23
If a ground floor storey exit and a stair share a final exit (via a ground floor lobby), then the final exit should be wide enough to evacuate people at a maximum flow rate equal to or greater than from the storey exit and stair combined (Diagram 2.6).
This can be calculated using the following formula:
W = ((N/2.5) + (60S))/80
where:
W is the width of final exit in metres
N is the number of people served by ground floor storey exit
S is the stair width in metres.
If the number of people (N) entering the lobby from the ground storey is more than 60, then the distance from the foot of the stair or the storey exit to the final exit should be a minimum of 2m (see Diagram 2.6).
If that minimum distance cannot be achieved, the width of the final exit (W) should be at least the width of the stair plus the width of the storey exit.
Diagram 2.6 Merging flows at final exit

Worked example
A ground floor storey exit serving 250 people shares a common final exit with a 1.2m wide stair.
Required final exit width = ((250/2.5) + (1.2×60))/80 = 2.150m
Protected corridors
2.24
A corridor serving as part of the means of escape in any of the following circumstances should be a protected corridor.
Diagram 2.7 Recesses off corridors

Diagram 2.8 Extension of corridor beyond a protected stairway

Enclosure of corridors that are not protected corridors
2.25
If a corridor is used for a means of escape but is not a protected corridor, even though the enclosing partitions may have no fire resistance, both of the following should be met to inhibit the spread of smoke.
Open planning will not inhibit the spread of smoke, but occupants can become aware of a fire quickly.
Division of corridors
2.26
A corridor providing access to alternative escape route should be divided by fire doorsets fitted with a self-closing device (and associated screens) where both of the following apply.
The fire doorsets (including any screens) should be approximately mid-way between the two storey exits. They should safeguard the route from smoke, while considering the layout of the corridor and any adjacent fire risks.
2.27
For buildings other than dwellings (purpose groups 2 to 7): if a cavity exists above the enclosures to a corridor as described above (because the enclosures are not carried to full storey height or the underside of the roof covering at the top storey), the potential for smoke to bypass the enclosure should be restricted by one of the following methods.
Any door that could provide a path for smoke to bypass the division should be fitted with a selfclosing device (but need not necessarily be fire resisting).
Diagram 2.9 Division of corridors

2.28
Where dead ends of corridors exceeding 4.5m long provide access to a point from which alternative escape route are available, they should be separated by self-closing fire doorsets (together with any associated screens) from any part of the corridor that either:
Alternatively, the stairs and corridors may be protected by a pressurisation system complying with BS EN 12101-6.
Diagram 2.10 Dead-end corridors exceeding 4.5m long

Cavity barriers
2.29
Additional measures to safeguard means of escape from smoke are given in Section 10.
External escape routes
2.30
Where an external escape route is beside an external wall of the building, the external wall should be of fire resisting construction in both of the following zones.
This does not apply to external escape stairs (see paragraph 3.32).
Escape over flat roofs
2.31
Where a storey or part of a building has multiple escape routes available, one may be over a flat roof if it does not serve a ‘residential (institutional)’ (purpose group 2(a)) building, or part of a building intended for use by members of the public.
2.32
Where an escape route over a flat roof is provided, the roof should comply with all of the following.
Residential care homes
General provisions
2.33
The choice of fire safety strategy depends on the way a building is designed, furnished, staffed and managed, and on the level of dependency of the residents.
2.34
In care homes for the elderly, some or all residents are likely to need help to evacuate. Buildings should generally be designed for progressive horizontal evacuation (PHE) in accordance with paragraphs 2.35 to 2.46.
For other care home types, the most appropriate of either a PHE or simultaneous evacuation strategy should be identified. The approach adopted in the design of a building must be recorded and communicated to the building management team, who can adopt procedures compatible with the building design.
Planning for progressive horizontal evacuation
2.35
The guidance below on PHE is for care homes where the provisions of the Firecode documents do not apply (see paragraph 0.10).
PHE requires areas used for the care of residents to be divided into protected areas by compartment walls and compartment floors. Protected areas provide a place of relative safety, from which further evacuation can be made if necessary.
2.36
Each storey used for the care of residents should be divided by compartment walls into at least three protected areas. All floors should be compartment floors.
2.37
Every protected area should have a minimum of two exits to adjoining protected areas. Maximum travel distances within a protected area should be both of the following.
2.38
A fire in one protected area should not prevent occupants of other areas from reaching a final exit (Diagram 2.11). Escape routes should not pass through ancillary accommodation listed in paragraph 2.44.
2.39
The number of residents’ beds in protected areas should be based on an assessment of both of the following.
The maximum number of residents’ beds in one protected area should not exceed 10, but may need to be lower depending on the assessment.
2.40
A protected area used for horizontal evacuation from an adjoining protected area should have a floor area able to accommodate its own occupants plus those from the largest adjoining protected area.
Diagram 2.11 Progressive horizontal evacuation in care homes

Fire detection and alarm
2.41
A fire detection and alarm system should be provided to L1 standard in accordance with BS 5839-1.
Bedrooms
2.42
Each bedroom in a care home should be enclosed in fire resisting construction (minimum REI 30) with fire resisting doors (minimum E 30). Every corridor serving bedrooms should be a protected corridor (see paragraph 2.24).
2.43
Bedrooms should not contain more than one single or double bed.
NOTE: It is not the intention to separate couples who happen to live in a care home by recommending that they sleep in separate bedrooms or beds.
Ancillary accommodation
2.44
Ancillary accommodation such as all of the following should be enclosed by fire resisting construction (minimum REI 30).
Door closing devices
2.45
If doors fitted with a self-closing device could present an obstacle to residents, the following hardware in accordance with BS EN 1155 is appropriate.
Sprinkler systems
2.46
Care homes should be fitted with a sprinkler system throughout the building in accordance with Appendix E.
Section 3: Design for vertical escape
Introduction
3.1
The limits on horizontal travel escape distances mean most people should be able to independently reach a protected escape route or final exit. The following guidance also includes measures for people who are unable to use stairs without help.
In larger buildings, some escape stairs may need to serve as firefighting stairs, and Section 17 will also apply.
Number of escape stairs
Mixed use buildings
3.2
If a building contains storeys, or parts of storeys, in different purpose groups, it is necessary to consider providing either of the following.
Single escape stairs
3.3
A single escape stair may serve a building (or part of a building) in the following situations.
Provision of refuges
3.4
Refuges form part of the management plan and offer relatively safe areas for people to wait for a short period only. Refuges should meet the following conditions.
3.5
The following are both examples of satisfactory refuges.
3.6
Refuges should be a minimum of 900mm × 1400mm in size and accessible by someone in a wheelchair. Where sited in a protected stairway, protected lobby or protected corridor, they should not reduce the width of the escape route or obstruct the flow of people escaping.
3.7
Refuges should be provided with an emergency voice communication (EVC) system complying with BS 5839-9. It should consist of Type B outstations communicating with a master station in the building control room (if one exists) or next to the fire detection and alarm panel. In some buildings, wireless technology may be more appropriate.
3.8
Refuges and evacuation lifts should be clearly identified. In protected lobbies and protected stairways there should be a blue mandatory sign worded ‘Refuge – keep clear’ in addition to fire safety signs.
3.9
Paragraph 5.32 gives guidance on using lifts, including evacuation lifts, during a fire.
Diagram 3.1 Refuge formed by compartmentation

Diagram 3.2 Refuge formed in a protected stairway

Width of escape stairs
3.10
The width of escape stairs should meet all of the following conditions.
3.11
Approved Document K requires stairs more than 2000mm wide in public buildings to have a central handrail.
3.12
If an exit route from a stair is also the escape route from the ground storey and/or basement storey, the width of the exit route may need to be increased (see paragraph 2.23).
Table 3.1 Minimum widths of escape stairs
| Situation of stair | Maximum number of people served(1) | Minimum stair width (mm) |
|---|---|---|
1a. In a ‘residential (institutional)’ building (unless the stair will only be used by staff) | 150 | 1000(2) |
1b. In an ‘assembly and recreation’ building and serving an area used for assembly purposes (unless the area is less than 100m²) | 220 | 1100 |
1c. In any other building and serving an area with an occupancy of more than 50 | Over 220 | See note 3 |
2. Any stair not described above | 50 | 800(4) |
NOTES:
Calculation of minimum stair width
3.13
The width depends on the number of stairs provided and the escape strategy (simultaneous or phased evacuation). If the maximum number of people needing to use escape stairs is unknown, calculate it using the floor space factors in Appendix D.
Discounting of stairs
3.14
Regardless of escape strategy, where two or more stairs are provided, it should be assumed that one might not be available during a fire. Each stair should be discounted in turn to ensure the capacity of the remaining stairs is adequate. This applies to buildings with or without a sprinkler system.
3.15
Paragraph 3.14 does not apply if either of the following applies.
Despite these exceptions, at least one storey exit still needs to be discounted (paragraph 2.21).
Paragraph 3.34 identifies cases where stairs need lobby protection.
Simultaneous evacuation
3.16
The width of escape stairs should take account of the number of people using them while evacuating all storeys at the same time. The following stairs should be designed to allow simultaneous evacuation.
Annexes B and C of BS 9999 include designs based on simultaneous evacuation.
3.17
The capacity of stairs of widths from 1000mm to 1800mm is given in Table 3.2.
Table 3.2 Capacity of stairs for basements and for simultaneous evacuation of the building
| No. of floors served | Maximum number of people served by a stair of width: | ||||||||
|---|---|---|---|---|---|---|---|---|---|
| 1000mm | 1100mm | 1200mm | 1300mm | 1400mm | 1500mm | 1600mm | 1700mm | 1800mm | |
| 1 | 150 | 220 | 240 | 260 | 280 | 300 | 320 | 340 | 360 |
| 2 | 190 | 260 | 285 | 310 | 335 | 360 | 385 | 410 | 435 |
| 3 | 230 | 300 | 330 | 360 | 390 | 420 | 450 | 480 | 510 |
| 4 | 270 | 340 | 375 | 410 | 445 | 480 | 515 | 550 | 585 |
| 5 | 310 | 380 | 420 | 460 | 500 | 540 | 580 | 620 | 660 |
| 6 | 350 | 420 | 465 | 510 | 555 | 600 | 645 | 690 | 735 |
| 7 | 390 | 460 | 510 | 560 | 610 | 660 | 710 | 760 | 810 |
| 8 | 430 | 500 | 555 | 610 | 665 | 720 | 775 | 830 | 885 |
| 9 | 470 | 540 | 600 | 660 | 720 | 780 | 840 | 900 | 960 |
| 10 | 510 | 580 | 645 | 710 | 775 | 840 | 905 | 970 | 1035 |
NOTES:
3.18
As an alternative to Table 3.2, the capacity of stairs 1100mm wide or wider can be found using either of the following formulas:
where:
P is the number of people that can be served
W is the width of the stair, in metres
N is the number of storeys served.
Separate calculations should be made for stairs serving basement storeys and stairs serving upper storeys.
The population, P, should be divided by the number of available stairs.
The formula is useful to determine the width of stairs where people are not distributed evenly – either within a storey or between storeys.
In the formula, 200W represents the number of people estimated to have left the stair after 2.5 minutes of evacuation, and 50 (W – 0.3)(N – 1) represents the number of people estimated to be on the stair after 2.5 minutes of evacuation.
Worked examples
Phased evacuation
3.19
Phased evacuation cannot be used in every type of building, but can be advantageous for escape stairs in high buildings. It requires supporting facilities, such as fire detection and alarm systems, to be provided and maintained.
In a phased evacuation, the first people to be evacuated are those with reduced mobility and those on the storey most immediately affected by the fire. If needed, subsequent evacuation is done two floors at a time, reducing disruption in large buildings.
Phased evacuation enables stairs to be narrower than with simultaneous evacuation, and may be used for any building provided it is not identified in paragraph 3.16.
3.20
Phased evacuation in buildings with a storey over 30m in height introduces the potential for escaping people to impede firefighters entering and operating within the building. This can be addressed by consulting with the fire and rescue service about special management procedures.
In very tall buildings, typically with a storey over 45m in height, physical measures may need to be incorporated, such as by discounting a stair.
3.21
A building (or part of a building) designed for phased evacuation should satisfy all of the following criteria.
3.22
The minimum width of stairs needed for phased evacuation is given in Table 3.3.
Table 3.3 Minimum width of stairs designed for phased evacuation
| Maximum number of people in any storey | Stair width (mm) |
|---|---|
| 100 | 1000 |
| 120 | 1100 |
| 130 | 1200 |
| 140 | 1300 |
| 150 | 1400 |
| 160 | 1500 |
| 170 | 1600 |
| 180 | 1700 |
| 190 | 1800 |
NOTES:
Worked example using Table 3.3
What is the minimum width needed for the stairs serving a 15 storey office building (ground + 14 office floors), assuming a total population of 2500 people (excluding the ground floor population, which does not use the stairs)? To satisfy the travel distance limitations, three stairs are required.
The building is over 45m in height and designed for phased evacuation. It has been decided to discount one stair to take account of fire and rescue service operations as described in paragraph 3.20. Therefore:
Each remaining stair must be able to accommodate half the population of one storey (i.e. 90 people).
Thus each stair should be 1000mm wide (maximum capacity 100 people).
This width will also be adequate when one storey exit is discounted as described in paragraph 2.21. It also complies with paragraph 3.10a (i.e. the stair widths are not less than the minimum width needed for 90 people in Table 2.3).
Additional worked example using Table 3.3
What is the minimum width needed for the stairs serving a 9 storey office building (ground + 8 office floors), assuming a total population of 1920 people (excluding the ground floor population, which does not use the stairs)? To satisfy the travel distance limitations, two stairs are required.
As both stairs need to be entered at each level through a protected lobby (see paragraph 3.21), both stairs can be assumed to be available (see paragraph 3.15). Therefore:
Design and protection of escape stairs
Enclosure of escape stairs
3.23
Every internal escape stair should be a protected stairway (within a fire resisting enclosure). If it is also a protected shaft (i.e. it passes from one compartment to another) or firefighting shaft, additional guidance in Sections 8 and 17 applies.
There is one exception: an unprotected stair (e.g. an accommodation stair) may form part of an internal route to a storey exit or final exit, provided that the distance of travel and the number of people involved are very limited. For example, small premises (Section 4) and raised storage areas (see paragraphs 7.6 and 7.7).
Construction of escape stairs
3.24
The flights and landings of escape stairs should be constructed of materials achieving class A2-s3, d2 or better in all of the following situations.
Materials achieving class B-s3, d2 or worse may be added to the top horizontal surface, except on firefighting stairs.
3.25
Further guidance on firefighting stairs is given in Section 17. Dimensional constraints on the design of stairs are given in Approved Document K.
Single steps
3.26
Single steps on escape routes should be prominently marked. A single step on the line of a doorway is acceptable, subject to paragraph 5.22.
Helical stairs and spiral stairs
3.27
Helical stairs and spiral stairs may form part of an escape route provided they are designed in accordance with BS 5395-2. If they are intended to serve members of the public, stairs should be type E (public) stairs.
Fixed ladders
3.28
Fixed ladders should not be provided as a means of escape for members of the public. They should only be provided where a conventional stair is impractical, such as for access to plant rooms which are not normally occupied.
External walls adjacent to protected stairways
3.29
With some configurations of external wall, a fire in one part of a building could subject the external wall of a protected stairway to heat (for example, where the two are adjacent at an internal angle in the façade, as shown in Diagram 3.3).
3.30
If a protected stairway projects beyond, is recessed from or is in an internal angle of the adjoining external wall of the building, then the minimum distance between an unprotected area of the building enclosure and an unprotected area of the stair enclosure should be 1800mm.
Diagram 3.3 External protection to protected stairways

External escape stairs
3.31
Where a storey or part of the building has more than one escape route available, some of the escape routes may be via an external escape stair, provided the following conditions are met.
3.32
Any external escape stair should meet all of the following conditions (Diagram 3.4).
3.33
Access to an external escape stair may be via a flat roof, provided the flat roof meets the requirements of paragraphs 2.31 and 2.32.
Diagram 3.4 Fire resistance of areas near to external stairs

Access lobbies and corridors
3.34
In the following situations, protected lobbies or protected corridors should be provided at all storeys above ground, except the top storey.
As an alternative to (a) to (c), a smoke control system as described in paragraph 3.15a may be used.
3.35
A protected lobby should be provided between an escape stair and a place of special fire hazard to protect from the ingress of smoke. The lobby should have a minimum 0.4m2 of permanent ventilation, or be protected by a mechanical smoke control system.
Exits from protected stairways
3.36
Every protected stairway should lead to a final exit, either directly or via an exit passageway. Any protected exit corridor or stair should have the same standard of fire resistance and lobby protection as the stair it serves. The exit from a protected stairway should comply with paragraphs 5.20 to 5.24.
Separation of adjoining protected stairways
3.37
The construction separating two adjacent protected stairways (or exit passageways) leading to different final exits should be imperforate.
Use of space within protected stairways
3.38
A protected stairway may only include any of the following.
Gas service and installation pipes in protected stairways
3.39
Gas service and installation pipes and meters should not be within a protected stairway, unless installed in accordance with the Pipelines Safety Regulations 1996 and the Gas Safety (Installation and Use) Regulations 1998.
Basement stairs
3.40
An escape stair forming part of the only escape route from an upper storey should not continue down to serve a basement storey. The basement storey should be served by a separate escape stair.
3.41
Where multiple escape stairs serve the upper storeys, only one needs to end at ground level. Other stairs may connect with the basement storeys if there is a protected lobby or a protected corridor between the stairs and accommodation at each basement level.
Section 4: Small premises
4.1
A ‘small premises’ is generally limited both in its size and in its number of occupants. When undivided, all of its parts are likely to be clearly visible to occupants. Occupants of small premises will be able to reach an exit quickly in an emergency and therefore a reduction in the number of exits and stairs is acceptable.
This guidance is not applicable to small premises where highly flammable materials are sold, stored or used.
4.2
Small premises should meet all of the following general conditions.
4.3
The following paragraphs only apply in place of those provisions elsewhere in this Approved Document which relate to the following.
For provisions other than those listed above, the guidance elsewhere in this Approved Document should be followed.
Construction
4.4
Except in kitchens, ancillary offices and stores, floor areas should be undivided so exits are clearly visible from all parts.
4.5
Store rooms should be enclosed with fire resisting construction (minimum REI 30).
Travel distance and number of escape routes
4.6
Escape routes should be sited so that the travel distance from any point of a storey to the nearest storey exit does not exceed the distance given in Table 4.1 (see Diagrams 4.1, 4.2 and 4.3). The siting of two or more exits or stairs should give effective alternative directions of travel from any point in a storey.
Table 4.1 Maximum travel distances in small premises
| Storey | Maximum travel distance (m) |
|---|---|
| Ground storey with a single exit | 27 |
| Basement or first storey with a single stair | 18 |
| Storey with more than one exit/stair | 45 |
NOTES:
If the internal layout of partitions, fittings, etc. is not known, direct distances, rather than travel distances, should be assessed. The direct distance should be assumed to be two-thirds of the travel distance.
The travel distance in small premises with an open stair is measured as follows.
Diagram 4.1 Maximum travel distances in a small two or three storey premises with a single protected stairway to each storey

Diagram 4.2 Maximum travel distances in a small three storey premises with a single open stair

Diagram 4.3 Maximum travel distances in a small three storey premises with a single stair to each storey

Escape stairs in small premises
4.7
A single escape stair may be used in small premises.
4.8
An open stair may be used as a means of escape if all of the following apply.
4.9
Where the premises contains three storeys and a single open stair serves a top or bottom storey, the stair serving the other storey should be enclosed with fire resisting construction at the ground storey level and discharge to a final exit independent of the ground storey (see Diagram 4.3).
Section 5: General provisions
Introduction
5.1
This section applies to all buildings and deals with the design, construction and protection of escape routes and service installations.
Protection of escape routes
Fire resistance of enclosures
5.2
Fire resistance test criteria are set out in Appendix B. Standards of performance are summarised in Table B1 and Table B2. Apart from specific situations described in Sections 1 and 2, and requirements B3 and B5, a minimum performance of REI 30 is sufficient to protect means of escape.
Fire resistance of doors
5.3
Fire resistance test criteria are set out in Appendix C. Standards of performance are summarised in Table C1.
Fire resistance of glazed elements
5.4
If glazed elements in fire resisting enclosures and doors can only meet the required integrity performance, their use is limited. These limitations depend on whether the enclosure forms part of a protected shaft (see Section 8) and the provisions set out in Appendix B, Table B3. If both integrity and insulation performance can be met, there is no restriction in this document on the use or amount of glass.
5.5
Glazed elements should also comply with the following, where necessary.
Doors on escape routes
5.6
Doors should be readily openable to avoid undue delay to people escaping. Doors on escape routes (both within and from the building) should comply with paragraphs 5.7 to 5.15. Guidance on door closing and ‘hold open’ devices for fire doorsets is set out in Appendix C.
Door fastenings
5.7
In general, doors on escape routes (whether or not the doors are fire doorsets) should be either of the following.
Doors may be fitted with hardware to allow them to be locked when rooms are empty.
In places such as hotel bedrooms, locks may be fitted that are key operated from the outside and manually opened from the inside.
If a secure door is operated by code or combination keypad, swipe or proximity card, biometric data, etc., a security mechanism override should be possible from the side approached by people escaping.
5.8
Electrically powered locks should return to the unlocked position in all of the following situations.
Security mechanism overrides for electrically powered locks should be a Type A call point as described in BS 7273-4. The call point should be positioned on the side approached by people escaping. If the door provides escape in either direction, a call point should be installed on both sides of the door.
5.9
In places of assembly and shop and commercial buildings (purpose groups 4 and 5), doors on escape routes from rooms with more than 60 people should be either of the following.
In non-residential buildings (purpose groups 3 to 7), some final exit doors feature security locks that are used only when the building is empty. Such locks may be appropriate, but management procedures must emphasise their safe use.
5.10
Guidance on door closing and ‘hold open’ devices for fire doorsets is set out in Appendix C.
Direction of opening
5.11
The door of any doorway or exit should be hung to open in the direction of escape whenever reasonably practicable. It should always be hung to open in the direction of escape if either of the following conditions applies.
Amount of opening and effect on associated escape routes
5.12
All doors on escape routes should be hung to meet both of the following conditions.
5.13
Any door opening towards a corridor or a stair should be recessed to prevent its swing encroaching on the effective width.
Vision panels in doors
5.14
Doors should contain vision panels in both of the following situations.
Approved Document M contains guidance about vision panels in doors across accessible corridors and Approved Document K contains guidance about the safety of glazing.
Revolving and automatic doors
5.15
Where revolving doors, automatic doors and turnstiles are placed across escape routes they should comply with one of the following.
General provisions
Headroom in escape routes
5.16
Escape routes should have a minimum clear headroom of 2m. The only projections allowed below this height are door frames.
Flooring of escape routes
5.17
Escape route floor finishes should minimise their slipperiness when wet. Finishes include the treads of steps and surfaces of ramps and landings.
Ramps and sloping floors
5.18
A ramp forming part of an escape route should meet the provisions in Approved Document M. Any sloping floor or tier should have a pitch of not more than 35 degrees to the horizontal.
5.19
Guidance for where there is fixed seating is given in both of the following.
Final exits
5.20
The width of a final exit should be at least the same as the minimum required width of the escape route it serves.
5.21
People should be able to rapidly leave the area around the building. Direct access to a street, passageway, walkway or open space should be available. The route away from the building should comply with the following.
5.22
Final exits should not present a barrier for disabled people. Where the route to a final exit does not include stairs, a level threshold and, where necessary, a ramp should be provided.
5.23
Final exit locations should be clearly visible and recognisable.
5.24
Final exits should avoid outlets of basement smoke vents and openings to transformer chambers, refuse chambers, boiler rooms and similar risks.
Table 5.1 Provisions for escape lighting
| Use of the building or part of the building | Areas requiring escape lighting |
|---|---|
| Residential | All common escape routes(1), except in two storey blocks of flats |
| Office, industrial, storage and other nonresidential | a. Underground or windowless accommodation b. Stairs either: • in a central core • that serve storey(s) more than 18m above ground level c. Internal corridors more than 30m long d. Open-plan areas of more than 60m2 |
| Shop and commercial, and car parks | a. Underground or windowless accommodation b. Stairs either: • in a central core • that serve storey(s) more than 18m above ground level c. Internal corridors more than 30m long d. Open-plan areas of more than 60m2 e. All escape routes (other than the following exception) to which the public are admitted.(1) The exception is shops that meet all of the following: • have a maximum of three storeys • have no sales floor of more than 280m2 • are not a restaurant or bar |
| Assembly and recreation | a. All escape routes(1) b. Accommodation except for that which is open on one side to view sport or entertainment during normal daylight hours |
| Any purpose group | a. All toilet accommodation with a minimum floor area of 8m2 b. Electricity and generator rooms c. Switch room/battery room for emergency lighting system d. Emergency control rooms |
NOTE:
Lighting of escape routes
5.25
All escape routes should have adequate artificial lighting. If the mains electricity power supply fails, escape lighting should illuminate the routes listed in Table 5.1.
5.26
Escape stair lighting should be on a separate circuit from the electricity supply to any other part of the escape route.
5.27
Escape lighting should conform to BS 5266-1.
Exit signs
5.28
Every doorway or other exit providing access to a means of escape, other than exits in ordinary use (e.g. main entrances), should be distinctively and conspicuously marked by an exit sign in accordance with BS ISO 3864-1 and BS 5499-4.
Advice on fire safety signs, including emergency escape signs, is given in the HSE publication Safety Signs and Signals: Guidance on Regulations.
Some buildings may require additional signs to comply with other legislation.
Protected power circuits
5.29
To limit potential damage to cables in protected circuits, all of the following should apply.
5.30
A protected circuit to operate equipment during a fire should achieve all of the following.
5.31
Guidance on cables for large and complex buildings is given in BS 5839-1, BS 5266-1 and BS 8519.
Lifts
Evacuation lifts
5.32
Generally, lifts should not be used when there is a fire in the building, unless their use forms part of a management plan for evacuating people and the following conditions are met.
Guidance on the design and use of evacuation lifts is given in Annex G to BS 9999.
5.33
Where a firefighting lift is provided, it can be used to evacuate disabled people. Management plans should describe how this would be managed, and what will happen when the fire and rescue service arrives.
Fire protection of lift installations
5.34
Lift wells should comply with one of the following conditions.
5.35
A lift well connecting different compartments should form a protected shaft (see Section 8).
5.36
Lifts that rise within a large volume such as a mall or atrium and do not have a conventional well, such as wall-climber or feature lifts, may be at risk if they run through a smoke reservoir. Care should be taken to maintain the integrity of the smoke reservoir and protect people in the lift.
5.37
In buildings designed for phased evacuation or progressive horizontal evacuation, if the lift well is not within the enclosures of a protected stairway, its entrance should be separated at every storey by a protected lobby (minimum REI 30).
5.38
In basements and enclosed car parks, the lift should be within the enclosure of a protected stairway. Otherwise, the lift should be approached only via a protected lobby or protected corridor (minimum REI 30).
5.39
If a lift delivers into a protected corridor or protected lobby serving sleeping accommodation and also serves a storey containing a high fire risk (such as a kitchen, communal areas, stores, etc.) then the lift should be separated from the high fire risk area(s) by a protected lobby or protected corridor (minimum REI 30).
5.40
A lift shaft serving storeys above ground level should not serve any basement if either of the following applies.
5.41
Lift machine rooms should be sited over the lift well where possible. Where buildings or part of a building with only one stairway make this arrangement impractical, the lift machine room should be sited outside the protected stairway.
Refuse chutes and storage
5.42
Refuse storage chambers, refuse chutes and refuse hoppers should be sited and constructed in accordance with BS 5906.
5.43
Refuse chutes and rooms for storing refuse should meet both of the following conditions.
5.44
The approach to rooms containing refuse chutes or for storing refuse should comply with one of the following conditions.
5.45
Access openings to refuse storage chambers should not be sited next to escape routes or final exits.
Shop store rooms
5.46
Fully enclosed walk-in store rooms should be separated from retail areas with fire resisting construction (minimum REI 30) if they negatively affect the means of escape. The fire resisting construction is not necessary if the walk-in store room complies with either of the following.
Requirement B2: Internal fire spread (linings)
This section deals with the following requirement from Part B of Schedule 1 to the Building Regulations 2010.
Requirement
| Requirement | Limits on application |
|---|---|
Internal fire spread (linings) B2. (1) To inhibit the spread of fire within the building, the internal linings shall— (a) adequately resist the spread of flame over their surfaces; and (b) have, if ignited, either a rate of heat release or a rate of fire growth, which is reasonable in the circumstances. (2) In this paragraph “internal linings” means the materials or products used in lining any partition, wall, ceiling or other internal structure. |
Intention
In the Secretary of State’s view, requirement B2 is met by achieving a restricted spread of flame over internal linings. The building fabric should make a limited contribution to fire growth, including a low rate of heat release.
It is particularly important in circulation spaces, where linings may offer the main means by which fire spreads and where rapid spread is most likely to prevent occupants from escaping.
Requirement B2 does not include guidance on the following.
Section 6: Wall and ceiling linings
Classification of linings
6.1
The surface linings of walls and ceilings should meet the classifications in Table 6.1.
Table 6.1 Classification of linings
| Location | Classification |
|---|---|
Small rooms of maximum internal floor area: a. 4m2 in residential accommodation b. 30m2 in non-residential accommodation | D-s3, d2 |
| Other rooms (including garages) | C-s3, d2 |
| Other circulation spaces | B-s3, d2(1) |
NOTE:
Walls
6.2
For the purposes of this requirement, a wall includes both of the following.
6.3
For the purposes of this requirement, a wall does not include any of the following.
6.4
Parts of walls in rooms may be of lower performance than stated in Table 6.1, but no worse than class D-s3, d2. In any one room, the total area of lower performance wall lining should be less than an area equivalent to half of the room’s floor area, up to a maximum of:
Ceilings
6.5
For the purposes of this requirement, a ceiling includes all of the following.
6.6
For the purposes of this requirement, a ceiling does not include any of the following.
Fire resisting ceilings
6.7
The need for cavity barriers in concealed floor or roof spaces can be reduced by installing a fire resisting ceiling (minimum EI 30) below the cavity, complying with Diagram 9.3.
Rooflights
6.8
Rooflights should meet the following classifications, according to material. No guidance for European fire test performance is currently available, because there is no generally accepted test and classification procedure.
Special applications
6.9
Any flexible membrane covering a structure, other than an air-supported structure, should comply with Appendix A of BS 7157.
6.10
Guidance on the use of PTFE-based materials for tension-membrane roofs and structures is given in BRE report BR 274.
Fire behaviour of insulating core panels used internally
6.11
Insulating core panels consist of an inner core of insulation sandwiched between, and bonded to, a membrane, such as galvanised steel or aluminium.
Where they are used internally they can present particular problems with regard to fire spread, and should meet all of the following conditions.
Other controls on internal surface properties
6.12
Guidance on the control of flame spread is given in the following sections.
Thermoplastic materials
General provisions
6.13
Thermoplastic materials that do not meet the classifications in Table 6.1 can be used as described in paragraphs 6.14 to 6.18. No guidance for European fire test performance is currently available, because there is no generally accepted test and classification procedure.
Thermoplastic materials are defined in Appendix B, paragraph B11. Classifications used here are explained in paragraph B13.
Windows
6.14
Thermoplastic material classified as a TP(a) rigid product may be used to glaze external windows to rooms, but not external windows to circulation spaces. Approved Document K includes guidance on the safety of glazing.
Rooflights
6.15
In rooms and circulation spaces other than protected stairways, rooflights may be constructed of thermoplastic material if they comply with both of the following.
Lighting diffusers
6.16
The following paragraphs apply to lighting diffusers forming part of a ceiling. Diffusers may be part of a luminaire or used below sources of light. The following paragraphs do not apply to diffusers of light fittings attached to the soffit of a ceiling or suspended beneath a ceiling (Diagram 6.1).
Diagram 6.1 Lighting diffuser in relation to ceiling

6.17
Diffusers constructed of thermoplastic material may be incorporated in ceilings to rooms and circulation spaces, but not to protected stairways, if both of the following conditions are met.
Suspended or stretched-skin ceilings
6.18
A ceiling constructed from TP(a) flexible panels should meet the following conditions.
Diagram 6.2 Layout restrictions on class D-s3, d2 plastic rooflights, TP(b) rooflights and TP(b) lighting diffusers

Table 6.2 Limitations applied to thermoplastic rooflights and lighting diffusers in suspended ceilings and class D-s3, d2 plastic rooflights(1)
| Minimum classification of lower surface | Use of space below the diffusers or rooflight | Maximum area of each diffuser or rooflight(2) (m2) | Maximum total area of diffusers and rooflights as a percentage of floor area of the space in which the ceiling is located (%) | Minimum separation distance between diffusers or rooflights(2) (m) |
|---|---|---|---|---|
| TP(a) | Any except protected stairway | No limit(3) | No limit | No limit |
| D-s3, d2(4) or TP(b) | Rooms | 1 | 50(5)(6) | A distance equal to the largest plan dimension of the largest diffuser or rooflight (see Diagram 6.3) |
| 5 | 50(5)(6) | 3(6) | ||
| Circulation spaces except protected stairways | 5 | 15(5) | 3 |
NOTES:
Diagram 6.3 Layout restrictions on small class D-s3, d2 plastic rooflights, TP(b) rooflights and TP(b) lighting diffusers

Requirement B3: Internal fire spread (structure)
These sections deal with the following requirement from Part B of Schedule 1 to the Building Regulations 2010.
Requirement
| Requirement | Limits on application |
|---|---|
Internal fire spread (structure) B3. (1) The building shall be designed and constructed so that, in the event of fire, its stability will be maintained for a reasonable period (2) A wall common to two or more buildings shall be designed and constructed so that it adequately resists the spread of fire between those buildings. For the purposes of this sub-paragraph a house in a terrace and a semi-detached house are each to be treated as a separate building. (3) Where reasonably necessary to inhibit the spread of fire within the building, measures shall be taken, to an extent appropriate to the size and intended use of the building, comprising either or both of the following— (a) sub-division of the building with fire-resisting construction; (b) installation of suitable automatic fire suppression systems. (4) The building shall be designed and constructed so that the unseen spread of fire and smoke within concealed spaces in its structure and fabric is inhibited. | Requirement B3(3) does not apply to material alterations to any prison provided under section 33 of the Prison Act 1952. |
Intention
In the Secretary of State’s view, requirement B3 is met by achieving all of the following.
The extent to which any of these measures are necessary is dependent on the use of the building and, in some cases, its size, and on the location of the elements of construction.
Section 7: Loadbearing elements of structure
Fire resistance standard
7.1
Elements of structure such as structural frames, beams, columns, loadbearing walls (internal and external), floor structures and gallery structures should have, as a minimum, the fire resistance given in Appendix B, Table B1.
7.2
Appendix B includes guidance on all of the following.
Exclusions from the provisions for elements of structure
7.3
The following are excluded from the definition of ‘element of structure’.
NOTE: In some cases, structural members within a roof may be essential for the structural stability system of the building. In these cases, the structural members in the roof do not just support a roof and must demonstrate the relevant fire resistance for the building as required by paragraph 7.2a above.
Additional guidance
7.4
If a loadbearing wall is any of the following, guidance in other sections may also apply.
7.5
If a floor is also a compartment floor, see Section 8.
Raised storage areas
7.6
The normal provisions for fire resistance may be too onerous to apply to raised, free-standing floors (sometimes supported by racking) in single storey buildings used for industrial and storage purposes. The introduction of raised storage areas can alter the effective number of storeys in the building (see the definition of ‘storey’ in Appendix A).
7.7
A structure that does not have the minimum fire resistance specified in Appendix B, Table B2, is acceptable if it satisfies all of the following conditions.
Section 8: Compartmentation/sprinklers
Provision of compartmentation
All purpose groups
8.1
All of the following should be provided as compartment walls and compartment floors and should have, as a minimum, the fire resistance given in Appendix B, Table B1.
8.2
A wall common to two or more buildings should be a compartment wall.
8.3
Parts of a building occupied mainly for different purposes should be separated from one another by compartment walls and/or compartment floors. Compartmentation is not needed if one of the different purposes is ancillary to the other. See paragraphs 0.23 and 0.24.
8.4
Effective compartmentation relies on both of the following.
8.5
The lowest floor in a building does not need to be a compartment floor.
Protected shafts
8.6
Stairs and service shafts connecting compartments should be protected to restrict the spread of fire between the compartments. These are called protected shafts. Walls or floors surrounding a protected shaft are considered to be compartment walls or compartment floors.
Places of special fire hazard
8.7
Fire resisting construction enclosing these places should achieve minimum REI 30. These walls and floors are not compartment walls and compartment floors.
‘Residential (institutional)’ buildings including health care
8.8
All floors should be constructed as compartment floors.
8.9
Paragraphs 2.35 and 2.36 give guidance on the provisions for compartment walls in care homes that use progressive horizontal evacuation.
‘Residential (other)’ buildings
8.10
In ‘residential (other)’ (purpose group (2(b)) buildings, all floors should be compartment floors.
Non-residential buildings
8.11
In buildings in a non-residential purpose group (purpose groups 3 to 7), the following should be compartment walls and compartment floors.
8.12
In two storey ‘shop and commercial’ or ‘industrial’ buildings (purpose groups 4 or 6), where the use of the upper storey is ancillary to the use of the ground storey, the ground storey may be treated as a single storey building for fire compartmentation purposes where all of the following apply.
Every place of special fire hazard (see Appendix E) should be enclosed with fire resisting construction.
Buildings containing one or more atria
8.13
Detailed advice on atria in buildings is given in Annexes B and C of BS 9999. For the purposes of this document, BS 9999 applies only where the atrium breaches a compartment.
Diagram 8.1 Compartment floors: illustration of guidance in paragraph 8.11

Table 8.1 Maximum dimensions of building or compartment (non-residential buildings)
| Purpose group of building or part | Height of floor of top storey above ground level (m) | Maximum floor area of any one storey in the building or any one storey in a compartment (m2) | ||
|---|---|---|---|---|
| Single storey buildings | Multi-storey buildings | |||
| Office | No limit(1) | No limit | No limit | |
| Assembly and recreation, shop and commercial: | ||||
a. Shops – without sprinkler system | No limit(1) | 2000 | 2000 | |
| Shops – with sprinkler system(2) | No limit | No limit | 4000 | |
b. Elsewhere – without sprinkler system | No limit(1) | No limit | 2000 | |
| Elsewhere – with sprinkler system(2) | No limit | No limit | 4000 | |
| Industrial(3) | ||||
| Without sprinkler system(1) | Not more than 18 | No limit | 7000 | |
| More than 18 | N/A | 2000(4) | ||
| With sprinkler system(2) | Not more than 18 | No limit | 14,000 | |
| More than 18 | N/A | 4000(4) | ||
| Height of floor of top storey above ground level (m) | Maximum floor area (m2) | Maximum height (m)(5) | Maximum compartment volume (m3) | |
| Single storey buildings | Multi-storey buildings | |||
| Storage(3) and other non-residential: | ||||
a. Car park for light vehicles | No limit | No limit | No limit | No limit |
b. Any other building or part: | ||||
| Without sprinkler system(1) | Not more than 18 | 20,000 | 18 | 20,000 |
| More than 18 | N/A | N/A | 4000(4) | |
| With sprinkler system(2) | Not more than 18 | No limit | No limit | 40,000 |
| More than 18 | 8000(4) | |||
NOTES:
This table recommends that where the maximum size limitations placed on a building without a sprinkler system are exceeded, a sprinkler system in accordance with Appendix E should be provided.
Sprinklers
8.14
Buildings within the ‘office’, ‘shop and commercial’, ‘assembly and recreation’, ‘industrial’ and ‘storage and other non-residential’ (except car parks for light vehicles) purpose groups (purpose groups 3 to 7(a)) require sprinklers where there is a top storey above 30m. The sprinkler system should be provided in accordance with Appendix E.
Construction of compartment walls and compartment floors
General provisions
8.15
All compartment walls and compartment floors should achieve both of the following.
8.16
Timber beams, joists, purlins and rafters may be built into or carried through a masonry or concrete compartment wall if the openings for them are both of the following.
If trussed rafters bridge the wall, failure of the truss due to a fire in one compartment should not cause failure of the truss in another compartment.
8.17
Where services could provide a source of ignition, the risk of fire developing and spreading into adjacent compartments should be controlled.
Compartment walls between buildings
8.18
Adjoining buildings should only be separated by walls, not floors. Compartment walls common to two or more buildings should comply with both of the following.
Separated parts of buildings
8.19
Compartment walls forming a separated part of a building should run the full height of the building in a continuous vertical plane.
Separated parts can be assessed independently to determine the appropriate standard of fire resistance in each. The two separated parts can have different standards of fire resistance.
Other compartment walls
8.20
Compartment walls not described in paragraphs 8.18 and 8.19 should run the full height of the storey in which they are situated.
8.21
Compartment walls in a top storey beneath a roof should be continued through the roof space.
Junction of compartment wall or compartment floor with other walls
8.22
At the junction with another compartment wall or an external wall, the fire resistance of the compartmentation should be maintained. Fire-stopping that meets the provisions in paragraphs 10.24 to 10.29 should be provided.
8.23
At the junction of a compartment floor and an external wall with no fire resistance, the external wall should be restrained at floor level. The restraint should reduce movement of the wall away from the floor if exposed to fire.
8.24
Compartment walls should be able to accommodate deflection of the floor, when exposed to fire, by either of the following means.
Where compartment walls are located within the middle half of a floor between vertical supports, the deflection may be assumed to be 40mm unless a smaller value can be justified by assessment. Outside this area, the limit can be reduced linearly to zero at the supports.
For steel beams that do not have the required fire resistance, reference should be made to SCI Publication P288.
Junction of compartment wall with roof
8.25
A compartment wall should achieve both of the following.
8.26
To reduce the risk of fire spreading over the roof from one compartment to another, a 1500mm wide zone of the roof, either side of the wall, should have a covering classified as BROOF(t4), on a substrate or deck of a material rated class A2-s3, d2 or better, as set out in Diagram 8.2a.
Thermoplastic rooflights that, because of paragraph 14.7, are regarded as having a BROOF(t4) classification are not suitable for use in that zone.
8.27
Materials achieving class B-s3, d2 or worse used as a substrate to the roof covering and any timber tiling battens, fully bedded in mortar or other suitable material for the width of the wall (Diagram 8.2b), may extend over the compartment wall in buildings that are both of the following.
8.28
Double-skinned insulated roof sheeting should incorporate a band of material rated class A2-s3, d2 or better, a minimum of 300mm in width, centred over the wall.
8.29
As an alternative to the provisions of paragraph 8.26 or 8.27, the compartment wall may extend through the roof for a minimum of either of the following (see Diagram 8.2c).
Diagram 8.2 Junction of compartment wall with roof

Openings in compartmentation
Openings in compartment walls separating buildings or occupancies
8.30
Openings in a compartment wall common to two or more buildings, or between different occupancies in the same building, should be limited to those for either of the following.
Openings in other compartment walls or in compartment floors
8.31
Openings should be limited to those for any of the following.
Protected shafts
8.32
Any stair or other shaft passing directly from one compartment to another should be enclosed in a protected shaft. Protected shafts should be used for the following only, but may also include sanitary accommodation and washrooms.
Construction of protected shafts
8.33
The construction enclosing a protected shaft (Diagram 8.3) should do all of the following.
Diagram 8.3 Construction of protected shafts

Uninsulated glazed screens to protected shafts
8.34
An uninsulated glazed screen may be incorporated in the enclosure to a protected shaft between a stair and a lobby or corridor entered from the stair. The enclosure must conform to Diagram 8.4 and meet all of the following conditions.
8.35
Where the measures in Diagram 8.4 are not provided, then both of the following apply.
Diagram 8.4 Uninsulated glazed screen separating protected shaft from lobby or corridor

Pipes for oil or gas and ventilation ducts in protected shafts
8.36
A protected shaft containing a protected stairway and/or a lift should not also contain either of the following.
A pipe that is completely separated from a protected shaft by fire resisting construction is not considered to be contained within that shaft.
8.37
In a protected shaft, any pipe carrying natural gas or LPG should be both of the following.
Ventilation of protected shafts conveying gas
8.38
A protected shaft conveying piped flammable gas should be ventilated direct to the outside air, by ventilation openings at high and low level in the shaft.
Any extension of the storey floor into the protected shaft should not compromise the free movement of air throughout the entire length of the shaft.
Guidance on shafts conveying piped flammable gas, including the size of ventilation openings, is given in BS 8313.
Openings into protected shafts
8.39
The external wall of a protected shaft does not normally need to have fire resistance. Situations where there are provisions are given in paragraph 3.29 (external walls of protected stairways, which may also be protected shafts) and paragraph 17.2 (firefighting shafts).
Openings in other parts of the enclosure to a protected shaft should be limited to the following.
Section 9: Cavities
9.1
Cavities in the construction of a building provide a ready route for the spread of smoke and flame, which can present a greater danger as any spread is concealed. For the purpose of this document, a cavity is considered to be any concealed space.
Diagram 9.1 Provisions for cavity barriers

Provision of cavity barriers
9.2
To reduce the potential for fire spread, cavity barriers should be provided for both of the following.
See Diagram 9.1. Cavity barriers should not be confused with fire-stopping details (Section 10).
Pathways around fire-separating elements
Junctions and edges of cavities
9.3
Cavity barriers should be provided at all of the following locations.
This does not apply where a wall meets the conditions of Diagram 9.2.
9.4
It is not appropriate to complete a line of compartment walls by fitting cavity barriers above them. The compartment wall should extend to the underside of the floor or roof above.
Protected escape routes
9.5
If the fire resisting construction of a protected escape route is either of the following.
Then the cavity above or below the fire resisting construction should be either of the following.
Cavities affecting alternative escape routes
9.6
In divided corridors, cavity barriers may be needed to prevent alternative escape routes being affected by fire and/or smoke (see paragraph 2.27 and Diagram 2.9).
Separation of bedrooms in ‘residential (institutional)’ and ‘residential (other)’ buildings
9.7
Where a cavity exists above or below a partition between bedrooms because the enclosure is not carried to full storey height or to the underside of the roof covering, the guidance in paragraph 9.5 should be followed.
Double-skinned corrugated or profiled roof sheeting
9.8
Cavity barriers are not required between double-skinned corrugated or profiled insulated roof sheeting if the sheeting complies with all of the following.
Diagram 9.2 Cavity walls excluded from provisions for cavity barriers

Diagram 9.3 Fire resisting ceiling below cavity

Diagram 9.4 Provisions for cavity barriers in double-skinned insulated roof sheeting

Extensive cavities
Maximum dimensions of cavities
9.9
Cavity barriers should be used to divide any cavity (including roof spaces). Table 9.1 sets out maximum dimensions for undivided cavities.
Table 9.1 Maximum dimensions of cavities in buildings other than dwellings (purpose groups 2 to 7)
| Location of cavity | Class of surface/product exposed in cavity (excluding the surface of any pipe, cable or conduit, or any insulation to any pipe) | Maximum dimension in any direction (m) |
|---|---|---|
| Between roof and a ceiling | Any | 20 |
| Any other cavity | Class C-s3, d2 or better | 20 |
| Worse than Class C-s3, d2 | 10 |
9.10
Table 9.1 does not apply to any of the following cavities.
9.11
If a single room with a ceiling cavity or underfloor cavity exceeds the dimensions in Table 9.1, cavity barriers need only be provided on the line of the enclosing walls/partitions of that room, if both of the following apply.
9.12
If the cavity is over an undivided area that exceeds 40m in any direction, there is no limit to its size if all of the following conditions are met.
Construction and fixings for cavity barriers
9.13
Cavity barriers, tested from each side separately, should provide a minimum of both of the following:
They may be formed by a construction provided for another purpose if it achieves the same performance.
9.14
Cavity barriers in a stud wall or partition, or provided around openings, may be formed of any of the following.
These do not necessarily achieve the performance specified in paragraph 9.13.
NOTE: Cavity barriers provided around openings may be formed by the window or door frame if the frame is constructed of steel or timber of the minimum thickness in (a) or (b), as appropriate.
9.15
Cavity barriers should be tightly fitted to a rigid construction and mechanically fixed in position. If this is not possible (e.g. where a cavity barrier joins to slates, tiles, corrugated sheeting or similar materials) the junction should be fire-stopped.
9.16
Cavity barriers should be fixed so their performance is unlikely to be made ineffective by any of the following.
Openings in cavity barriers
9.17
Openings should be limited to the following.
9.18
If a cavity barrier is provided above or below a partition between bedrooms in ‘residential (institutional)’ and ‘residential (other)’ (purpose groups 2(a) and 2(b)) buildings, and the partition is not a fire resisting partition, then paragraph 9.17 does not apply. However, both of the following apply.
NOTE: For further guidance on openings in cavity barriers see Section 10.
Section 10: Protection of openings and fire-stopping
Introduction
10.1
Every joint, imperfect fit and opening for services through a fire-separating element should be sealed with fire-stopping to ensure the fire resistance of the element is not impaired. Fire-stopping delays the spread of fire and, generally, the spread of smoke as well.
Openings for pipes
10.2
Pipes passing through a fire-separating element, unless in a protected shaft, should comply with one of the alternatives A, B or C below.
Alternative A: Proprietary seals (any pipe diameter)
10.3
Provide a proprietary, tested sealing system that will maintain the fire resistance of the wall, floor or cavity barrier.
Alternative B: Pipes with a restricted diameter
10.4
Where a proprietary sealing system is not used, fire-stop around the pipe, keeping the opening for the pipe as small as possible. The nominal internal diameter of the pipe should not exceed the relevant dimension given in Table 10.1.
Alternative C: Sleeving
10.5
A pipe with a maximum nominal internal diameter of 160mm may be used with a sleeve made out of a high melting point metal, as shown in Diagram 10.1, if the pipe is made of one of the following.
A high melting point metal means any metal (such as cast iron, copper or steel) which, if exposed to a temperature of 800°C, will not soften or fracture to the extent that flame or hot gas will pass through the wall of the pipe.
Diagram 10.1 Pipes penetrating fire-separating elements

Table 10.1 Maximum nominal internal diameter of pipes passing through a fire-separating element
| Situation | Pipe material and maximum nominal internal diameter (mm) | ||
|---|---|---|---|
(a) High melting point metal(1) | (b) Lead, aluminium, aluminium alloy, uPVC(2), fibrecement | (c) Any other material | |
1. Structure (but not a wall separating buildings) enclosing a protected shaft that is not a stairway or a lift shaft | 160 | 110 | 40 |
2. Any other situation | 160 | 40 | 40 |
NOTES:
Mechanical ventilation and air-conditioning systems
General provisions
10.6
Ductwork should not help to transfer fire and smoke through the building. Terminals of exhaust points should be sited away from final exits, cladding or roofing materials achieving class B-s3, d2 or worse and openings into the building.
10.7
Ventilation ducts supplying or extracting air directly to or from a protected stairway should not also serve other areas. A separate ventilation system should be provided for each protected stairway.
10.8
A fire and smoke damper should be provided where ductwork enters or leaves each section of the protected escape route it serves. It should be operated by a smoke detector or suitable fire detection system. Fire and smoke dampers should close when smoke is detected. Alternatively, the methods set out in paragraphs 10.15 and 10.16 and Diagrams 10.2 and 10.3 may be followed.
10.9
In a system that recirculates air, smoke detectors should be fitted in the extract ductwork before both of the following.
When smoke is detected, detectors should do one of the following.
10.10
Non-domestic kitchens, car parks and plant rooms should have separate and independent extraction systems. Extracted air should not be recirculated.
10.11
Under fire conditions, ventilation and air-conditioning systems should be compatible with smoke control systems and need to be considered in their respective design.
Ventilation ducts and flues passing through fire-separating elements
General provisions
10.12
If air handling ducts pass through fire-separating elements, the fire performance of the elements should be maintained using one or more of the following four methods. In most ductwork systems, a combination of the four methods is best.
10.13
Further information on fire resisting ductwork is given in the ASFP Blue Book.
Kitchen extract
10.14
Methods 1 and 4 should not be used for extract ductwork serving kitchens. The likely build-up of grease within the duct can adversely affect dampers.
Ducts passing through protected escape routes
10.15
Method 1 should not be used for extract ductwork passing through the enclosures of protected escape routes (Diagrams 10.2 and 10.3), as large volumes of smoke can pass thermal devices without triggering them.
10.16
An ES classified fire and smoke damper which is activated by a suitable fire detection system (method 4) may also be used for protected escape routes.
Diagram 10.2 Ductwork passing through protected escape routes – method 2 or method 3

Diagram 10.3 Ductwork passing through protected escape routes – method 4

Installation and specification of fire dampers
10.17
Both fire dampers and fire and smoke dampers should be all of the following.
10.18
Access to the fire damper and its actuating mechanism should be provided for inspection, testing and maintenance.
10.19
Fire dampers should meet both of the following conditions.
10.20Fire and smoke dampers should meet both of the following conditions.
10.21
Smoke detectors should be sited so as to prevent the spread of smoke as early as practicable by activating the fire and smoke dampers. Smoke detectors and automatic release mechanisms used to activate fire dampers and/or fire and smoke dampers should conform to BS EN 54-7 and BS 5839-3 respectively.
Further information on fire dampers and/or fire and smoke dampers is given in the ASFP Grey Book.
Sleeping risks
10.22
Where the use of the building involves a sleeping risk, fire dampers or fire and smoke dampers should be actuated by both of the following.
However, in a situation where both of the following are true:
then both of the following exceptions may be made.
Flues, etc.
10.23
The wall of a flue, duct containing flues or appliance ventilation duct(s) should have a fire resistance (REI) that is at least half of any compartment wall or compartment floor it passes through or is built into (Diagram 10.4).
Diagram 10.4 Flues penetrating compartment walls or floors

Fire-stopping
10.24In addition to any other provisions in this section, both of the following conditions should be met.
NOTE: The fire-stopping around fire dampers, fire resisting ducts, fire and smoke dampers and smoke control ducts should be in accordance with the manufacturer or supplier’s installation instructions.
10.25
Materials used for fire-stopping should be reinforced with (or supported by) materials rated class A2-s3, d2 or better to prevent displacement in both of the following cases.
10.26Proprietary, tested fire-stopping and sealing systems are available and may be used. Different materials suit different situations and not all are suitable in every situation.
10.27
Other fire-stopping materials include the following.
These may be used in situations appropriate to the particular material. Not all materials will be suitable in every situation.
10.28Guidance on the design, installation and maintenance of measures to contain fires or slow their spread is given in Ensuring Best Practice for Passive Fire Protection in Buildings produced by the Association for Specialist Fire Protection (ASFP).
10.29Further information on generic systems, their suitability for different applications and guidance on test methods is given in the ASFP Red Book.
Section 11: Special provisions for car parks
11.1
Car parks call for different measures to restrict fire spread within buildings for the following reasons.
Open-sided car parks
Natural ventilation
11.2
For the purposes of assessing fire resistance, a building, compartment or separated part containing a car park may be regarded as open-sided when it complies with all of the following.
Car parks that are not open-sided
11.3
For car parks that do not have the ventilation set out in paragraph 11.2, the required fire resistance is given in Appendix B, Table B2. Ventilation should be either natural or mechanical. See Approved Document F for additional guidance on ventilation of car parks.
Natural ventilation
11.4
Each storey should be ventilated by permanent openings at each car parking level. The openings can be at ceiling level. The aggregate free vent area should be a minimum of 1/40 of that level’s floor area, at least half of which should be provided equally by two opposite walls (1/160 on each side). The remaining free area can be distributed wherever possible.
Mechanical ventilation
11.5
If the minimum standard of natural ventilation is not possible, a system of mechanical ventilation should be provided that complies with all of the following.
For further information on equipment for removing hot smoke, refer to BS EN 12101-3. An alternative method of providing smoke ventilation from enclosed car parks is given in BS 7346-7.
Requirement B4: External fire spread
These sections deal with the following requirement from Part B of Schedule 1 to the Building Regulations 2010. Section 12 also refers to regulation 7(2) of the Building Regulations 2010. Guidance on regulation 7(1) can be found in Approved Document 7.
Requirement
| Requirement | Limits on application |
|---|---|
External fire spread B4. (1) The external walls of the building shall adequately resist the spread of fire over the walls and from one building to another having regard to the height, use and position of the building. (2) The roof of the building shall adequately resist the spread of fire over the roof and from one building to another, having regard to the use and position of the building. |
Regulation
Regulation 7 – Materials and workmanship
(1) Building work shall be carried out—
(1A) Building work shall be carried out so that relevant metal composite material does not become part of an external wall, or specified attachment, of any building.
(2) Subject to paragraph (3), building work shall be carried out so that materials which become part of an external wall, or specified attachment, of a relevant building are of European Classification A2-s1, d0 or A1 (classified in accordance with the reaction to fire classification).
(3) Paragraph (2) does not apply to—
(4) In this regulation—
Intention
Resisting fire spread over external walls
The external envelope of a building should not contribute to undue fire spread from one part of a building to another part. This intention can be met by constructing external walls so that both of the following are satisfied.
The extent to which this is necessary depends on the height and use of the building.
Resisting fire spread from one building to another
The external envelope of a building should not provide a medium for undue fire spread to adjacent buildings or be readily ignited by fires in adjacent buildings. This intention can be met by constructing external walls so that all of the following are satisfied.
The extent to which this is necessary depends on the use of the building and its position in relation to adjacent buildings and therefore the site boundary.
Section 12: Resisting fire spread over external walls
Introduction
12.1
The external wall of a building should not provide a medium for fire spread if that is likely to be a risk to health and safety. Combustible materials and cavities in external walls and attachments to them can present such a risk, particularly in tall buildings. The guidance in this section is designed to reduce the risk of fire spread as well as the risk of ignition from flames coming from adjacent buildings.
Fire resistance
12.2
This section provides guidance on resisting fire spread over external walls; however, it does not deal with fire resistance of external walls. An external wall may need fire resistance to meet the provisions of Section 2 (Design for horizontal escape), Section 3 (Design for vertical escape), Section 7 (Loadbearing elements of structure), Section 13 (Resisting fire spread from one building to another) or Section 17 (Access to buildings for firefighting personnel).
Combustibility of external walls
12.3
The external walls of buildings other than those described in regulation 7(4) of the Building Regulations should achieve either of the following.
12.4
In relation to buildings of any height or use, consideration should be given to the choice of materials (including their extent and arrangement) used for the external wall, or attachments to the wall (e.g. balconies, etc.), to reduce the risk of fire spread over the wall.
External surfaces
12.5
The external surfaces (i.e. outermost external material) of external walls should comply with the provisions in Table 12.1. The provisions in Table 12.1 apply to each wall individually in relation to its proximity to the relevant boundary.
Table 12.1 Reaction to fire performance of external surface of walls
| Building type | Building height | Less than 1000mm from the relevant boundary | 1000mm or more from the relevant boundary |
|---|---|---|---|
| ‘Relevant buildings’ as defined in regulation 7(4) (see paragraph 12.15) | Class A2-s1, d0(1) or better | Class A2-s1, d0(1) or better | |
| All ‘residential’ purpose groups (purpose groups 1 and 2) | More than 11m | Class A2-s1, d0(2) or better | Class A2-s1, d0(2) or better |
| 11m or less | Class B-s3, d2(2) or better | No provisions | |
| Assembly and recreation | More than 18m | Class B-s3, d2(2) or better | From ground level to 18m: class C-s3, d2(3) or better From 18m in height and above: class B-s3, d2(2) or better |
| 18m or less | Class B-s3, d2(2) or better | Up to 10m above ground level: class C-s3, d2(3) or better Up to 10m above a roof or any part of the building to which the public have access: class C-s3, d2(3) or better(4) From 10m in height and above: no minimum performance | |
| Any other building | More than 18m | Class B-s3, d2(2) or better | From ground level to 18m: class C-s3, d2(3) or better From 18m in height and above: class B-s3, d2(2) or better |
| 18m or less | Class B-s3, d2(2) or better | No provisions | |
NOTES:
In all cases all the following provisions apply.
In addition to the provisions within this table, buildings with a storey 18m or more above ground level should also meet the provisions of paragraph 12.6.
In addition to the provisions within this table, buildings with a storey 11m or more above ground level should also meet the provisions of paragraph 12.7.
Materials and products
12.6
In a building with a storey 18m or more in height (see Diagram D6 in Appendix D) any insulation product, filler material (such as the core materials of metal composite panels, sandwich panels and window spandrel panels but not including gaskets, sealants and similar) etc. used in the construction of an external wall should be class A2-s3, d2 or better (see Appendix B). This restriction does not apply to masonry cavity wall construction which complies with Diagram 9.2 in Section 9. Where regulation 7(2) applies, that regulation prevails over all the provisions in this paragraph.
12.7
In buildings that include a ‘residential’ purpose (purpose groups 1 and 2) with a storey 11m or more in height (see Diagram D6 in Appendix D) any insulation product, filler material (such as the core materials of metal composite panels, sandwich panels and window spandrel panels but not including gaskets, sealants and similar) etc. used in the construction of an external wall should be class A2-s1, d0 or better (see Appendix B). This restriction does not apply to masonry cavity wall construction which complies with Diagram 9.2 in Section 9. Where regulation 7(2) applies, that regulation prevails over all the provisions in this paragraph.
12.8
Best practice guidance for green walls (also called living walls) can be found in Fire Performance of Green Roofs and Walls, published by the Department for Communities and Local Government. Where regulation 7(2) applies, that regulation prevails over all the provisions in this paragraph.
Cavities and cavity barriers
12.9
Cavity barriers should be provided in accordance with Section 9.
12.10
In the case of an external wall construction of a building which, by virtue of paragraph 9.10d (external cladding system with a masonry or concrete inner leaf), is not subject to the provisions of Table 9.1, the surfaces which face into cavities should also meet the provisions of Table 12.1 and provisions in Section 9, but where regulation 7(2) applies, that regulation prevails over the guidance provided in Table 12.1 and Section 9.
Balconies
12.11
In buildings that include a ‘residential’ purpose (purpose groups 1 and 2) with a storey 11m or more in height (see Diagram D6 in Appendix D) balconies should meet either of the following conditions.
Where regulation 7(2) applies, that regulation prevails over all the provisions in this paragraph.
Metal composite materials
12.12
Regulation 7(1A) prohibits the use of relevant metal composite materials in the external walls, and specified attachments, of all buildings of any height.
12.13
Relevant metal composite materials are defined (in regulation 2(6)(c)) as any panel or sheet, having a thickness of no more than 10mm which is composed of a number of layers two or more of which are made of metal, alloy or metal compound and one or more of which is a substantial layer made of a material having a gross calorific value of more than 35MJ/kg when tested in accordance with BS EN ISO 1716. A substantial layer is defined as a layer which is at least 1mm thick or has a mass per unit area of at least 1kg/m².
Regulation 7(2) and requirement B4
Materials
12.14
Regulation 7(1)(a) requires that materials used in building work are appropriate for the circumstances in which they are used. Regulation 7(2) sets requirements in respect of external walls and specified attachments in relevant buildings.
NOTE: Further guidance on regulation 7(1) can be found in HM Government’s Manual to the Building Regulations.
12.15
Regulation 7(2) applies to any building with a storey at least 18m above ground level (as measured in accordance with Diagram D6 in Appendix D) and which contains one or more dwellings; an institution; or a room for residential purposes. It requires that all materials which become part of an external wall or specified attachment achieve class A2-s1, d0 or class A1 in accordance with BS EN 13501-1, other than those exempted by regulation 7(3).
NOTE: The above includes student accommodation, care homes, sheltered housing, hospitals, dormitories in boarding schools, hotels, hostels and boarding houses. See regulation 7(4) for the definition of relevant buildings.
12.16
External walls and specified attachments are defined in regulation 2(6) and these definitions include any parts of the external wall as well as balconies, solar panels and solar shading.
12.17
Regulation 7(3) provides an exemption for certain components found in external walls and specified attachments.
Material change of use
12.18
Regulations 5(k) and 6(3) provide that, where the use of a building is changed such that the building becomes a building described in regulation 7(4), the construction of the external walls, and specified attachments, must be investigated and, where necessary, work must be carried out to ensure they only contain materials achieving class A2-s1, d0 or class A1, other than those exempted by regulation 7(3).
Solar shading devices
12.19
Regulation 7(2) requires that the curtain and or slats of solar shading devices in a relevant building (as defined in regulation 7(4)) achieve class A1 or A2-s1, d0. The curtain of solar shading devices cannot be classified as a membrane in accordance with regulation 7(3).
12.20Solar shading devices installed up to 4.5m above ground level are not required to meet the requirements of regulation 7(2).
Additional considerations
12.21
The provisions of regulation 7 apply in addition to requirement B4. Therefore, for buildings described in regulation 7(4), the potential impact of any products incorporated into or onto the external walls and specified attachments should be carefully considered with regard to their number, size, orientation and position.
12.22
Particular attention is drawn to the following points.
Section 13: Resisting fire spread from one building to another
Introduction
13.1
The following assumptions enable a reasonable standard of resistance to the spread of fire to be specified.
13.2
Where regulation 7(2) applies, that regulation prevails over the provisions within this section.
13.3
If a reduced separation distance between buildings, or increased amount of unprotected area, is required, smaller compartments should be considered.
Boundaries
13.4
The fire resistance of a wall depends on its distance from the relevant boundary (see Diagram 13.1). Separation distances are measured to boundaries to ensure that the location and design of buildings on adjoining sites have no influence on the building under consideration.
13.5
The boundary that a wall faces is the relevant boundary (Diagram 13.2). It may be one of the following.
Diagram 13.1 Principles of space separation

Diagram 13.2 Relevant boundary

Diagram 13.3 Notional boundary

Unprotected areas and fire resistance
13.6
Parts of an external wall with less fire resistance than the appropriate amount given in Appendix B, Table B2, are called unprotected areas.
13.7
Where a fire resisting external wall has an external surface material that is worse than class B-s3, d2 and is more than 1mm thick, that part of the wall should be classified as an unprotected area equating to half its area (Diagram 13.4).
External walls on, and within 1000mm of, the relevant boundary
13.8
Unprotected areas should meet the conditions in Diagram 13.5 and the rest of the wall should be fire resisting from both sides.
External surface materials facing the boundary should be class B-s3, d2 or better.
External walls 1000mm or more from the relevant boundary
13.9
Unprotected area should not exceed the result given by one of the methods in paragraph 13.17, and the rest of the wall (if any) should be fire resisting but only from the inside of the building.
External walls of protected stairways
13.10
Exclude external walls of stairways in a protected shaft when assessing unprotected areas (see Diagram 3.3)
Diagram 13.4 Status of materials achieving class B-s3, d2 or worse as unprotected area

Small unprotected areas
13.11
In an otherwise protected wall, small unprotected areas may be ignored where they meet the conditions in Diagram 13.5.
Diagram 13.5 Small unprotected areas that may be disregarded in assessing the separation distance from the boundary

Large uncompartmented buildings
13.12
For the purposes of assessing unprotected area, parts of walls of uncompartmented buildings that are more than 30m above mean ground level may be ignored.
Canopies
13.13
Where both of the following apply, separation distances may be determined from the wall rather than from the edge of the canopy (Diagram 13.6).
Canopies that fall within class 6 or class 7 of Schedule 2 to the regulations (Exempt Buildings and Work) are exempt from the Building Regulations.
13.14
Space separation may be disregarded if a canopy is all of the following.
Diagram 13.6 The effect of a canopy on separation distance

Roofs
13.15
Roofs with a pitch of more than 70 degrees to the horizontal should be assessed in accordance with this section. Vertical parts of a pitched roof, such as dormer windows, should be included, only if the slope of the roof exceeds 70 degrees.
It is a matter of judgement whether a continuous run of dormer windows that occupies most of a steeply pitched roof should be treated as a wall rather than a roof.
Portal frames
13.16
Portal frames are often used in single storey industrial and commercial buildings where there may be no need for fire resistance of the structure (requirement B3). However, where a portal framed building is near a relevant boundary, the external wall near the boundary may need fire resistance to restrict the spread of fire between buildings. It is generally accepted that a portal frame acts as a single structural element because of the moment-resisting connections used, especially at the column/rafter joints. Thus, in cases where the external wall of the building cannot be wholly unprotected, the rafter members of the frame, as well as the column members, may need to be fire protected. The design method for this is set out in SCI Publication P313.
NOTE: The recommendations in the SCI publication for designing the foundation to resist overturning do not need to be followed if the building is fitted with a sprinkler system in accordance with Appendix E.
NOTE: Normally, portal frames of reinforced concrete can support external walls requiring a similar degree of fire resistance without specific provision at the base to resist overturning.
NOTE: Existing buildings may have been designed to comply with all of the following guidance, which is also acceptable.
Methods for calculating acceptable unprotected area
13.17
Two simple methods are given for calculating the acceptable amount of unprotected area in an external wall that is a minimum of 1000mm from any point on the relevant boundary. More precise methods are described in BRE report BR 187 and may be used instead. When using BR 187 the following radiation intensity at each unprotected area should be assumed.
Method 1
13.18
This method applies to small buildings intended to be used for ‘residential (other)’ purposes.
13.19
The building should not exceed three storeys in height (excluding basements) or 24m in length. Each side of the building should meet the limits stated in Diagram 13.7. Any small unprotected areas falling within the limits shown in Diagram 13.5 can be ignored.
Diagram 13.7 Permitted unprotected areas in small residential buildings

Method 2
13.20
This method may be used for buildings or compartments intended for any use and for which method 1 is not appropriate.
13.21
Except for an open-sided car park in purpose group 7(b) (see paragraph 11.2), the building should not exceed 10m in height. Each side of the building should meet the limits in Table 13.1. Areas falling within the limits in Diagram 13.5 can be ignored.
Table 13.1 Permitted unprotected areas in small buildings or compartments
| Minimum distance between side of building and relevant boundary (m) | Maximum total percentage of unprotected area (%) (3) | |
|---|---|---|
| Purpose groups | ||
Residential, office, assembly and recreation (1) | Shop and commercial, industrial, storage and other non-residential (2) | |
| Not applicable | 1 | 4 |
| 1 | 2 | 8 |
| 2.5 | 5 | 20 |
| 5 | 10 | 40 |
| 7.5 | 15 | 60 |
| 10 | 20 | 80 |
| 12.5 | 25 | 100 |
NOTES:
Sprinkler systems
13.22
If a building is fitted throughout with a sprinkler system in accordance with Appendix E, either of the following is permitted.
Atrium buildings
13.23
If a building contains one or more atria, the recommendations in clause B8 of BS 9999 should be followed.
Section 14: Resisting fire spread over roof coverings
Introduction
14.1
‘Roof covering’ describes one or more layers of material, but not the roof structure as a whole.
14.2
Provisions for the fire properties of roofs are given in other parts of this document.
Separation distances
14.3
Separation distance is the minimum distance from the roof, or part of the roof, to the relevant boundary (paragraph 13.5). Table 14.1 sets out separation distances by the type of roof covering and the size and use of the building.
In addition, roof covering products (and/or materials) defined in Commission Decision 2000/553/ EC of 6 September 2000, implementing Council Directive 89/106/EEC, can be considered to fulfil all of the requirements for the performance characteristic ‘external fire performance’ without the need for testing, provided that any national provisions on the design and execution of works are fulfilled, and can be used without restriction.
14.4
The performance of rooflights is specified in a similar way to the performance of roof coverings. Plastic rooflights may also be used.
Plastic rooflights
14.5
Table 14.2 and Diagram 14.1 set the limitations for using plastic rooflights whose lower surface has a minimum rating of class D-s3, d2.
14.6
Table 14.3 sets the limitations for using thermoplastic materials with a TP(a) rigid or TP(b) (see also Diagram 14.1) classification. The method of classifying thermoplastic materials is given in Appendix B.
14.7
Other than for the purposes of Diagram 8.2, polycarbonate or uPVC rooflights achieving a minimum rating of class C-s3, d2 can be regarded as having a BROOF(t4) classification.
Unwired glass in rooflights
14.8
When used in rooflights, unwired glass a minimum of 4mm thick can be regarded as having a BROOF(t4) classification.
Thatch and wood shingles
14.9
If the performance of thatch or wood shingles cannot be established, they should be regarded as having an EROOF(t4) classification in Table 14.1.
Diagram 14.1 Limitations on spacing and size of plastic rooflights that have a class D-s3, d2 or TP(b) lower surface

Table 14.1 Limitations on roof coverings
| Designation(1) of covering of roof or part of roof | Distance from any point on relevant boundary | |||
|---|---|---|---|---|
| Less than 6m | At least 6m | At least 12m | At least 20m | |
| BROOF(t4) | ● | ● | ● | ● |
| CROOF(t4) | ○ | ● | ● | ● |
| DROOF(t4) | ○ | ●(2)(3) | ●(2) | ● |
| EROOF(t4) | ○ | ●(2)(3) | ●(2) | ●(2) |
| FROOF(t4) | ○ | ○ | ○ | ●(2)(3) |
| ● Acceptable. ○ Not acceptable. | ||||
NOTES:
Separation distances do not apply to enclosed/covered walkways. However, see Diagram 8.2 if the roof passes over the top of a compartment wall.
Polycarbonate and uPVC rooflights that achieve a class C-s3, d2 rating by test may be regarded as having a BROOF(t4) classification.
Table 14.2 Class D-s3, d2 plastic rooflights: limitations on use and boundary distance
| Minimum classification on lower surface(1) | Space that rooflight can serve | Minimum distance from any point on relevant boundary to rooflight with an external designation(2) of: | |
|---|---|---|---|
| EROOF(t4) or DROOF(t4) | FROOF(t4) | ||
| Class D-s3, d2 | a. Balcony, verandah, carport, covered way or loading bay that has at least one longer side wholly or permanently open b. Detached swimming pool c. Conservatory, garage or outbuilding, with a maximum floor area of 40m2 | 6m | 20m |
d. Circulation space(3) (except a protected stairway) e. Room(3) | 6m(4) | 20m(4) | |
NOTES:
None of the above designations are suitable for protected stairways. Polycarbonate and uPVC rooflights that achieve a class C-s3, d2 rating by test (see paragraph 14.7) may be regarded as having a BROOF(t4) classification. Where Diagram 8.2a or 8.2b applies, rooflights should be a minimum of 1500m from the compartment wall. If double-skinned or laminate products have upper and lower surfaces of different materials, the greater distance applies.
Table 14.3 TP(a) and TP(b) thermoplastic rooflights: limitations on use and boundary distance
| Minimum classification on lower surface(1) | Space that rooflight can serve | Minimum distance from any point on relevant boundary to rooflight with an external surface classification(1) of: | |
|---|---|---|---|
| TP(a) | TP(b) | ||
1. TP(a) rigid | Any space except a protected stairway | 6m(2) | Not applicable |
2. TP(b) | a. Balcony, verandah, carport, covered way or loading bay, which has at least one longer side wholly or permanently open b. Detached swimming pool c. Conservatory, garage or outbuilding, with a maximum floor area of 40m2 | Not applicable | 6m |
d. Circulation space(3) (except a protected stairway) e. Room(3) | Not applicable | 6m(4) | |
NOTES:
None of the above designations are suitable for protected stairways. Polycarbonate and uPVC rooflights that achieve a class C-s3, d2 rating by test may be regarded as having a BROOF(t4) designation. Where Diagram 8.2a or 8.2b applies, rooflights should be at least 1500mm from the compartment wall. If double-skinned or laminate products have upper and lower surfaces of different materials, the greater distance applies.
Requirement B5: Access and facilities for the fire service
These sections deal with the following requirement from Part B of Schedule 1 to the Building Regulations 2010.
Requirement
| Requirement | Limits on application |
|---|---|
Access and facilities for the fire service B5. (1) The building shall be designed and constructed so as to provide reasonable facilities to assist fire fighters in the protection of life. (2) Reasonable provision shall be made within the site of the building to enable fire appliances to gain access to the building. |
Intention
Provisions covering access and facilities for the fire service are to safeguard the health and safety of people in and around the building. Their extent depends on the size and use of the building. Most firefighting is carried out within the building. In the Secretary of State’s view, requirement B5 is met by achieving all of the following.
If an alternative approach is taken to providing the means of escape, outside the scope of this approved document, additional provisions for firefighting access may be required. Where deviating from the general guidance, it is advisable to seek advice from the fire and rescue service as early as possible (even if there is no statutory duty to consult).
Section 15: Vehicle access
Buildings not fitted with fire mains
15.1
For small buildings (up to 2000m2, with a top storey that is a maximum of 11m above ground level), vehicle access for a pump appliance should be provided to whichever is the less onerous of the following.
15.2
For all other buildings, provide vehicle access in accordance with Table 15.1.
15.3
Every elevation to which vehicle access is provided should have a door, a minimum of 750mm wide, to give access into the building. The maximum distance between doors, or between a door and the end of the elevation, is 60m (e.g. a 150m elevation would need a minimum of two doors).
Table 15.1 Fire and rescue service vehicle access to buildings not fitted with fire mains
| Total floor area(1) of building (m²) | Height of floor of top storey above ground (m)(2) | Provide vehicle access to: | Type of appliance |
|---|---|---|---|
| Up to 2000 | Up to 11 | See paragraph 15.1 | Pump |
| Over 11 | 15% of perimeter | High reach | |
| 2000–8000 | Up to 11 | 15% of perimeter | Pump |
| Over 11 | 50% of perimeter | High reach | |
| 8000–16,000 | Up to 11 | 50% of perimeter | Pump |
| Over 11 | 50% of perimeter | High reach | |
| 16,000–24,000 | Up to 11 | 75% of perimeter | Pump |
| Over 11 | 75% of perimeter | High reach | |
| Over 24,000 | Up to 11 | 100% of perimeter | Pump |
| Over 11 | 100% of perimeter | High reach |
NOTES:
Diagram 15.1 Example of building footprint and perimeter

Buildings fitted with fire mains
15.4
For buildings fitted with dry fire mains, both of the following apply.
15.5
For buildings fitted with wet fire mains, access for a pumping appliance should comply with both of the following.
15.6
Where fire mains are provided in buildings for which Sections 16 and 17 make no provision, vehicle access may be as described in paragraphs 15.4 and 15.5, rather than Table 15.1.
Design of access routes and hardstandings
15.7
Access routes and hardstandings should comply with the guidance in Table 15.2. Requirements can only apply to the site of the works.
It may not be reasonable to upgrade the route across a site to a small building. The building control body, in consultation with the fire and rescue service, should consider options from doing no work to upgrading certain features, such as sharp bends.
15.8
Where access to an elevation is provided in accordance with Table 15.1, the following requirements should be met, depending on the building height.
15.9
Where access is provided for high reach appliances in accordance with Table 15.1, overhead obstructions (such as cables and branches) should be avoided in the zone shown in Diagram 15.2.
15.10
Dead-end access routes longer than 20m require turning facilities, as in Diagram 15.3. Turning facilities should comply with the guidance in Table 15.2.
Table 15.2 Typical fire and rescue service vehicle access route specification
| Appliance type | Minimum width of road between kerbs (m) | Minimum width of gateways (m) | Minimum turning circle between kerbs (m) | Minimum turning circle between walls (m) | Minimum clearance height (m) | Minimum carrying capacity (tonnes) |
|---|---|---|---|---|---|---|
| Pump | 3.7 | 3.1 | 16.8 | 19.2 | 3.7 | 12.5 |
| High reach | 3.7 | 3.1 | 26.0 | 29.0 | 4.0 | 17.0 |
NOTES:
Diagram 15.2 Relationship between building and hardstanding/access roads for high reach fire appliances

Diagram 15.3 Turning facilities

Section 16: Fire mains and hydrants
Introduction
16.1
Fire mains are installed for the fire and rescue service to connect hoses for water. They may be either of the following.
There should be a facility to replenish a wet system from a pumping appliance in an emergency.
Provision of fire mains
16.2
Buildings with firefighting shafts should have fire mains in both of the following.
The criteria for providing firefighting shafts and fire mains are given in Section 17.
16.3
Buildings without firefighting shafts should be provided with fire mains where fire service vehicle access is not provided in accordance with Table 15.1. In these cases, outlets from fire mains should be located as described in paragraph 16.4, with a maximum hose distance of 45m from the fire main outlet to the furthest point, measured on a route suitable for laying a hose. Stairs do not need to be designed as firefighting shafts.
Design and construction of fire mains
16.4
If a firefighting shaft is provided, outlets from fire mains should be within the protected stairway or protected lobby (see Diagram 17.1).
16.5
Guidance on the design and construction of fire mains is given in BS 9990.
16.6
Buildings with a storey more than 50m above fire service vehicle access level should be provided with wet fire mains. In all other buildings where fire mains are provided, either wet or dry fire mains are suitable.
16.7
Fire service vehicle access to fire mains should be provided as described in paragraphs 15.4 and 15.5.
Provision of private hydrants
16.8
A building requires additional fire hydrants if both of the following apply.
16.9
If additional hydrants are required, these should be provided in accordance with the following.
16.10
Each fire hydrant should be clearly indicated by a plate, fixed nearby in a conspicuous position, in accordance with BS 3251.
16.11
Guidance on aspects of provision and siting of private fire hydrants is given in BS 9990.
Alternative supply of water
16.12
An alternative source of water supply should be provided where any of the following apply.
16.13
The alternative source of water supply should be one of the following, subject to consultation with the local fire and rescue service.
Section 17: Access to buildings for firefighting personnel
Introduction
17.1
Facilities for fire and rescue, such as firefighting lifts, firefighting stairs and firefighting lobbies, are combined in protected firefighting shafts (Diagram 17.1). Section 8 gives guidance on the design and construction of protected shafts.
Diagram 17.1 Components of a firefighting shaft

Provision of firefighting shafts
17.2
A building with a storey more than 18m above the fire and rescue service vehicle access level should have one or more firefighting shafts containing a firefighting lift. The number and location of firefighting shafts should comply with paragraphs 17.4 to 17.7. Firefighting shafts are not required to serve a basement that is not large or deep enough to need one (see paragraph 17.3 and Diagram 17.2).
17.3
A building with basement storeys should have firefighting shafts in accordance with the following.
The building’s height and size determine whether firefighting shafts also serve upper storeys.
17.4
Firefighting shafts should serve all storeys through which they pass.
17.5
A minimum of two firefighting shafts should be provided to buildings with a storey that has both of the following.
17.6
At least two firefighting shafts, which do not need to include firefighting lifts, should be provided if buildings meet all of the following.
Diagram 17.2 Provision of firefighting shafts

Location of firefighting shafts
17.7
Firefighting shafts and protected stairways should be positioned such that every part of each storey more than 18m above the fire and rescue service vehicle access level complies with the maximum distances given in paragraph 17.8. Distances should be measured from the fire main outlet on a route suitable for laying a hose.
NOTE: If the internal layout is not known, the distance should be measured at two-thirds of the direct distance.
17.8
In any building, the hose laying distance should meet all of the following conditions.
Diagram 17.3 Location of firefighting shafts: hose laying distances

Design and construction of firefighting shafts
17.9
Every firefighting stair and firefighting lift should be approached from the accommodation through a firefighting lobby. Both the stair and lobby of the firefighting shaft should be provided with a means of venting smoke and heat (see clause 27.1 of BS 9999).
Only services associated with the firefighting shaft, such as ventilation systems and lighting for the firefighting shaft, should pass through or be contained within the firefighting shaft.
17.10
All firefighting shafts should have fire mains with outlet connections and valves at every storey.
17.11
A firefighting lift installation includes all of the following.
The lift shaft should be constructed in accordance with Section 6 of BS 9999.
Firefighting lift installations should conform to BS EN 81-72 and BS EN 81-20.
Rolling shutters in compartment walls
17.12
The fire and rescue service should be able to manually open and close rolling shutters without the use of a ladder.
Section 18: Venting of heat and smoke from basements
Provision of smoke outlets
18.1
Heat and smoke from basement fires vented via stairs can inhibit access for firefighting personnel. This may be reduced by providing smoke outlets, or smoke vents, which allow heat and smoke to escape from the basement levels to the open air. They can also be used by the fire and rescue service to let cooler air into the basements (Diagram 18.1).
18.2
Each basement space should have one or more smoke outlets.
Where this is not practicable (for example, the plan area is deep and the amount of external wall is restricted by adjoining buildings), the perimeter basement spaces may be vented, with other spaces vented indirectly by opening connecting doors. This does not apply for place of special fire hazard (see paragraph 18.7).
If a basement is compartmented, each compartment should have one or more smoke outlets, rather than indirect venting.
A basement storey or compartment containing rooms with doors or windows does not need smoke outlets.
18.3
Smoke outlets connecting directly to the open air should be provided from every basement storey, except for any basement storey that has both of the following.
18.4
Strong rooms do not need to be provided with smoke outlets.
Natural smoke outlets
18.5
Smoke outlets should be both of the following.
18.6
The combined clear cross-sectional area of all smoke outlets should be a minimum of 1/40 of the area of the floor of the storey they serve.
18.7
Separate outlets should be provided from places of special fire hazard.
18.8
If the smoke outlet terminates at a point that is not readily accessible, it should be kept unobstructed and covered only with a class A1 grille or louvre.
18.9
If the smoke outlet terminates in a readily accessible position, it may be covered by a panel, stallboard or pavement light that can be broken out or opened. The position of covered smoke outlets should be suitably indicated.
18.10
Outlets should not be placed where they prevent the use of escape routes from the building.
Mechanical smoke extract
18.11
If basement storeys are fitted with a sprinkler system in accordance with Appendix E, a mechanical smoke extraction system may be provided as an alternative to natural venting. Sprinklers do not need to be installed on the other storeys unless needed for other reasons.
Car parks are not normally expected to be fitted with sprinklers (see Section 11 for guidance on car parks).
18.12
The air extraction system should comply with all of the following.
Further information on equipment for removing hot smoke is given in BS EN 12101-3.
Diagram 18.1 Fire resisting construction for smoke outlet shafts

Construction of outlet ducts or shafts
18.13
Outlet ducts or shafts, including any bulkheads over them (see Diagram 18.1), should be enclosed in construction of class A1 rating and fire resistance at least equal to that of the element through which they pass.
18.14
Natural smoke outlet shafts should be separated from each other using construction of class A1 rating and fire resistance at least equal to that of the storeys they serve, where the shafts are either of the following.
Basement car parks
18.15
The provisions for ventilation of basement car parks in Section 11 satisfy the requirements for venting smoke from any basement used as a car park.
Regulation 38: Fire safety information
This section deals with the following regulation of the Building Regulations 2010.
Fire safety information
Intention
The aim of this regulation is to ensure that the person responsible for the building has sufficient information relating to fire safety to enable them to manage the building effectively. The aim of regulation 38 will be achieved when the person responsible for the building has all the information to enable them to do all of the following.
Section 19: Fire safety information
19.1
For building work involving the erection or extension or a change of use of a relevant building (i.e. a building to which the Regulatory Reform (Fire Safety) Order 2005 or the Building Safety Act 2022 applies, or will apply), fire safety information should be given to the relevant dutyholder (responsible person or accountable person) at one of the following times, whichever is the earlier.
19.2
This section is a guide to the information that should be provided and is not exhaustive. Guidance is in terms of essential information and additional information for complex buildings; however, the level of detail required should be considered on a case-by-case basis.
Essential information
19.3
The essential information provided should be sufficient to enable the relevant dutyholder to understand, operate and maintain the building (including the fire safety systems in it). It should make it clear how the fire safety arrangements of the building are intended to operate together. In cases where a fire safety strategy has been prepared (e.g. as part of the design and construction process for a building or building work), then this should be made available to the relevant dutyholder.
19.4
Information on the location of fire protection measures may be sufficient. An as-built plan of the building should be provided showing all of the following.
19.5
Details should be provided of all of the following.
Additional information for complex buildings
19.6
A detailed record should be provided of both of the following.
19.7
The records should include details of the following.
Appendix A: Key terms
NOTE: Except for the items marked * (which are from the Building Regulations 2010), these definitions apply only to Approved Document B.
NOTE: The terms defined below are key terms used in this document only. Refer to BS 4422 for further guidance on the definitions of common terms used in the fire safety industry which are not listed below.
Access room A room that the only escape route from an inner room passes through.
Alternative escape routes Escape routes that are sufficiently separated by direction and space or by fire resisting construction to ensure that one is still available if the other is affected by fire.
NOTE: A second stair, balcony or flat roof which enables a person to reach a place free from danger from fire is considered an alternative escape route for the purposes of a dwellinghouse.
Alternative exit One of two or more exits, each of which is separate from the other.
Appliance ventilation duct A duct to deliver combustion air to a gas appliance.
Atrium (plural atria) A continuous space that passes through one or more structural floors within a building, not necessarily vertically.
NOTE: Enclosed lift wells, enclosed escalator wells, building services ducts and stairs are not classified as atria.
Automatic release mechanism A device that normally holds a door open, but closes it automatically if any one of the following occurs.
Basement storey A storey with a floor that, at some point, is more than 1200mm below the highest level of ground beside the outside walls. (However, see Appendix B, paragraph B26c, for situations where the storey is considered to be a basement only because of a sloping site.)
Boundary The boundary of the land that belongs to a building, or, where the land abuts a road, railway, canal or river, the centre line of that road, railway, canal or river.
*Building Any permanent or temporary building but not any other kind of structure or erection. A reference to a building includes a reference to part of a building.
Building control body A term that includes both local authority building control and approved inspectors.
Cavity A space enclosed by elements of a building (including a suspended ceiling) or contained within an element, but that is not a room, cupboard, circulation space, protected shaft, or space within a flue, chute, duct, pipe or conduit.
Cavity barrier A construction within a cavity, other than a smoke curtain, to perform either of the following functions.
Ceiling Part of a building that encloses a room, protected shaft or circulation space and is exposed overhead.
NOTE: The soffit of a rooflight, but not the frame, is included as part of the surface of the ceiling. An upstand below a rooflight is considered as a wall.
Circulation space A space (including a protected stairway) mainly used as a means of access between a room and an exit from the building or compartment.
Common balcony A walkway, open to the air on one or more sides, that forms part of the escape route from more than one flat.
Common stair An escape stair that serves more than one flat.
Compartment (fire) A building or part of a building, comprising one or more rooms, spaces or storeys, that is constructed to prevent the spread of fire to or from another part of the same building or an adjoining building.
NOTE: A roof space above the top storey of a compartment is included in that compartment. (See also ‘Separated part’.)
Compartment wall or floor A fire resisting wall or floor to separate one fire compartment from another.
NOTE: Provisions relating to construction are given in Section 8.
Corridor access A design of a building containing flats, in which each flat is approached via a common horizontal internal access or circulation space, which may include a common entrance hall.
Curtain Part of a solar shading device which is set in motion by the operating system and fulfils the purpose of a blind, awning or shutter.
Dead end An area from which escape is possible in one direction only.
Direct distance The shortest distance from any point within the floor area to the nearest storey exit, measured within the external enclosures of the building, and ignoring walls, partitions and fittings other than the enclosing walls and partitions to protected stairways.
*Dwelling Includes a dwellinghouse and a flat.
NOTE: A dwelling is a unit where one or more people live (whether or not as a sole or main residence) in either of the following situations.
*Dwellinghouse Does not include a flat or a building containing a flat.
Element of structure Any of the following.
NOTE: However, see the guidance to requirement B3, paragraph 7.3, for a list of structures that are not considered to be elements of structure.
Emergency lighting Lighting for use when the power supply to the normal lighting fails.
Escape lighting The part of the emergency lighting that is provided to ensure that the escape route is illuminated at all material times.
Escape route The route along which people can escape from any point in a building to a final exit.
Evacuation lift A lift that may be used to evacuate people in a fire.
Evacuation lift lobby An area protected from fire and smoke ingress by fire resisting construction and smoke control measures, providing direct access to an evacuation lift, where a person can wait for a lift service in relative safety while an evacuation is underway.
Evacuation shaft A protected shaft containing a protected stairway, an evacuation lift (together with its machine room) and evacuation lift lobbies.
Exit passageway A protected passageway that connects a protected stairway to a final exit.
NOTE: Exit passageways should be protected to the same standard as the stairway they serve.
*External wall The external wall of a building includes all of the following.
Final exit The end of an escape route from a building that gives direct access to a street, passageway, walkway or open space, and is sited to ensure that people rapidly disperse away from the building so that they are no longer in danger from fire and/or smoke.
NOTE: Windows are not acceptable as final exits.
Fire alarm system Combination of components for giving an audible and/or other perceptible warning of fire.
Fire damper A mechanical or intumescent device within a duct or ventilation opening that operates automatically and is designed to resist the spread of fire.
Fire and smoke damper A fire damper which, in addition to the performance of the fire damper, resists the spread of smoke.
Fire doorset A door or shutter which, together with its frame and furniture as installed in a building, is intended (when closed) to resist the spread of fire and/or gaseous products of combustion and meets specified performance criteria to those ends.
NOTE: A fire doorset may have one or more leaves. The term includes a cover or other form of protection to an opening in a fire resisting wall or floor, or in a structure that surrounds a protected shaft. A fire doorset is a complete door assembly, assembled on site or delivered as a completed assembly, consisting of the door frame, leaf or
leaves, essential hardware, edge seals and glazing, and any integral side panels or fanlight panels in an associated door screen.
Firefighting lift A lift with additional protection and with controls that enable it to be used by the fire and rescue service when fighting a fire. (See Section 17.)
Firefighting lobby A protected lobby that provides access from a firefighting stair to the accommodation area and to any associated firefighting lift.
Firefighting shaft A protected enclosure that contains a firefighting stair, firefighting lobbies and, if provided, a firefighting lift together with its machine room.
Firefighting stair A protected stairway that connects to the accommodation area through only a firefighting lobby.
Fire resisting (Fire resistance) The ability of a component or a building to satisfy, for a stated period of time, some or all of the appropriate criteria given in the relevant standard.
Fire-separating element A compartment wall, compartment floor, cavity barrier and construction that encloses a protected escape route and/or a place of special fire hazard.
Fire-stop (Fire-stopping) A seal provided to close an imperfection of fit or design tolerance between elements or components, to restrict the spread of fire and smoke.
*Flat A flat is a separate and self-contained premises constructed or adapted for use for residential purposes and forming part of a building from some other part of which it is divided horizontally.
Gallery A floor or balcony that does not extend across the full extent of a building’s footprint and is open to the floor below.
Habitable room A room used, or intended to be used, for people to live in (including, for the purposes of Approved Document B Volumes 1 and 2, a kitchen, but not a bathroom).
Height (of a building or storey for the purposes of Approved Document B Volumes 1 and 2)
Inner room Room from which escape is possible only by passing through another room (the access room).
Interlocked stair Two interlocking protected stairways providing two separate paths of egress within one protected shaft or separated protected shafts. These are also sometimes referred to as scissor stairs or stacked stairs.
Live/work unit A flat that is a workplace for people who live there, its occupants, and for people who do not live on the premises.
Means of escape Structural means that provide one or more safe routes for people to go, during a fire, from any point in the building to a place of safety.
Measurement
Notional boundary A boundary presumed to exist between two buildings on the same site.
Open spatial planning The internal arrangement of a building in which more than one storey or level is contained in one undivided volume, e.g. split-level floors. For the purposes of this document there is a distinction between open spatial planning and an atrium space.
Perimeter (of a building) The maximum aggregate plan perimeter, found by vertical projection onto a horizontal plane. (See Section 15.)
Pipe Includes pipe fittings and accessories. The definition of ‘pipe’ excludes a flue pipe and a pipe used for ventilating purposes, other than a ventilating pipe for an above-ground drainage system.
Place of special fire hazard A room such as any of the following.
Platform floor (also called an access or raised floor) A floor that is supported by a structural floor, but with an intervening cavity to house services.
Protected circuit An electrical circuit that is protected against fire.
Protected corridor/lobby A corridor or lobby that is adequately protected from fire in adjoining areas by fire resisting construction.
Protected entrance hall/landing A circulation area, consisting of a hall or space in a flat, that is enclosed with fire resisting construction other than an external wall of a building.
Protected shaft A shaft that enables people, air or objects to pass from one compartment to another, and which is enclosed with fire resisting construction.
Protected stairway A stair that leads to a final exit to a place of safety and that is adequately enclosed with fire resisting construction. Included in the definition is any exit passageway between the foot of the stair and the final exit.
Purpose group A classification of a building according to the purpose to which it is intended to be put. (See Table 0.1.)
Relevant boundary The boundary or notional boundary that one side of the building faces and/ or coincides with, and that is parallel or at an angle of a maximum of 80 degrees to that side of the building.
Rooflight A dome light, lantern light, skylight, ridge light, glazed barrel vault or other element to admit daylight through a roof.
Room An enclosed space within a building that is not used solely as a circulation space. The term includes not only conventional rooms, but also cupboards that are not fittings and large spaces such as warehouses and auditoria. The term does not include cavities such as ducts, ceiling cavities and roof spaces.
School A place of education for children between 2 and 19 years old. The term includes nursery schools, primary schools and secondary schools as defined in the Education Act 1996.
Self-closing device A device that closes a door, when open at any angle, against a door frame.
NOTE: If the door is in a cavity barrier, rising butt hinges (which are different from the self-closing device mentioned above) are acceptable.
Separated part (of a building) Part of a building that is separated from another part of the same building by a compartment wall. The wall runs the full height of the part and is in one vertical plane. (See Appendix D, Diagram D5.)
Sheltered housing Includes two or more dwellings in the same building or on adjacent sites, designed and constructed as residential accommodation for vulnerable or elderly people who receive, or will receive, a support service.
Single storey building A building that consists of a ground storey only. Basements are not counted as storeys in a building (see Appendix D). A separated part that consists of a ground storey only, with a roof to which access is only provided for repair or maintenance, may be treated as a single storey building.
Site (of a building) The land occupied by the building, up to the boundaries with land in other ownership.
*Solar shading device A device attached to the external surface of an external wall for reducing heat gain within a building by shading or deflecting sunlight.
*Specified attachment Includes any of the following.
Storey Includes any of the following.
NOTE: The building is regarded as a multi-storey building if both of the following apply.
Storey exit A final exit, or a doorway that gives direct access into a protected stairway, evacuation lift lobby within an evacuation shaft, firefighting lobby or external escape route.
NOTE: If an institutional building is planned to enable progressive horizontal evacuation, a door in a compartment wall is considered a storey exit for the purposes of requirement B1.
Suspended ceiling (fire-protecting) A ceiling suspended below a floor that adds to the fire resistance of the floor.
Thermoplastic material Any synthetic polymeric material that has a softening point below 200°C if tested to BS EN ISO 306 Method A120. Specimens for this test may be fabricated from the original polymer where the thickness of material of the end product is less than 2.5mm.
Travel distance (unless otherwise specified, e.g. as in the case of flats) The distance that a person would travel from any point within the floor area to the nearest storey exit, determined by the layout of walls, partitions and fittings.
Unprotected area (in relation to a side or external wall of a building) All of the following are classed as unprotected areas.
NOTE: Recessed car parking areas as shown in Diagram A1 should not be regarded as unprotected areas.
Diagram A1 Recessed car parking areas

Appendix B: Performance of materials, products and structures
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: Appendix B: Performance of materials, products and structures (2029 amendment).
Introduction
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: Introduction (2029 amendment).
B1
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: B1 (2029 amendment).
Much of the guidance in this document is given in terms of performance classifications in relation to British or European Standards. In such cases, it will be necessary to demonstrate that a system or product can meet the relevant performance classification. This will be achieved if the system or product complies with one of the following.
NOTE: Some products are subject to Classification Without Further Testing (CWFT). For the purposes of this approved document, such products can be considered to have been shown to be capable of meeting a performance specification as per paragraph B1a.
B2
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: B2 (2029 amendment).
Any test evidence used to demonstrate the fire performance classification of a product or system should be carefully checked to ensure that it is applicable to the intended use. Small differences in detail, such as fixing method, joints, dimensions, the introduction of insulation materials and air gaps (ventilated or not), might significantly affect the performance and should be tested or assessed in accordance with paragraph B1.
B3
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: B3 (2029 amendment).
Assessments should not be regarded as a way to avoid a test where one is necessary. Assessments should only be carried out where sufficient relevant test evidence is available. Relevant test evidence is unlikely to be provided by test standards which have different classification criteria.
B4
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: B4 (2029 amendment).
Where it is proposed to assess the classification of a product or system in lieu of carrying out a specific test (as in paragraph B1c), this should be done in accordance with the relevant standard for extended application for the test in question and should include details of the test evidence that has been used to support the assessment.
For performance classifications where there is no specific standard for extended application, assessment reports should be produced in accordance with the principles of BS EN 15725 and should include details of the test evidence that has been used to support the assessment. In cases where the end use application is not covered by the extended application standard and an assessment is the only other suitable approach, then further information on best practice is provided in the Passive Fire Protection Forum’s Guide to Undertaking Technical Assessments of the Fire Performance of Construction Products Based on Fire Test Evidence. The same principle should be followed for assessments as described in paragraph B2.
NOTE: Regulation 7(2) limits components used in or on the external walls of certain buildings to materials achieving class A2-s1, d0 or class A1 (see Section 12). Assessments cannot be used to demonstrate compliance with this requirement.
B5
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: B5 (2029 amendment).
Tests and assessments should be carried out by organisations with the necessary expertise. For example, organisations listed as ‘notified bodies’ in accordance with the European Construction Products Regulation or laboratories accredited by the United Kingdom Accreditation Service (UKAS) for the relevant test standard can be assumed to have the necessary expertise.
NOTE: Standard fire tests do not directly measure fire hazard. They measure or assess the response of a material or system to exposure to one or more aspects of fire conditions. Performance in fire tests is only one of a number of factors that should be taken into account.
Reaction to fire
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: Reaction to fire (2029 amendment).
B6
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: B6 (2029 amendment).
Reaction to fire relates to the degree to which a product will contribute, by its own decomposition, to a fire under specified conditions. Products, other than floorings, are classified as A1, A2, B, C, D, E or F (with class A1 being the highest performance and F being the lowest) in accordance with BS EN 13501-1. Class F is assigned when a product fails to attain class E. Untested products cannot be classified in accordance with BS EN 13501-1.
Materials covered by the Classification Without Further Testing (CWFT) process can be found by accessing the European Commission’s website https://eur-lex.europa.eu/.
B7
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: B7 (2029 amendment).
The classes of reaction to fire performance of A2, B, C, D and E are accompanied by additional classifications related to the production of smoke (s1, s2, s3), with s1 indicating the lowest production, and/or flaming droplets/particles (d0, d1, d2), with d0 indicating the lowest production.
NOTE: When a classification includes s3, d2 this means that there is no limit set for smoke production and/or flaming droplets/particles.
B8
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: B8 (2029 amendment).
To reduce the testing burden on manufacturers, BS EN 13238 defines a number of standard substrates that produce test results representative of different end use applications. The classification for reaction to fire achieved during testing is only valid when the product is used within this direct field of application, i.e. when the product is fixed to a substrate of that class in its end use. The standard substrate selected for testing should take account of the intended end use applications (field of application) of the product and represent end use substrates that have a density of a minimum of 75% of the standard substrate’s nominal density.
B9
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: B9 (2029 amendment).
Standard substrates include gypsum plasterboard (BS EN 520) with a density of 700+/-100kg/m3, calcium silicate board (BS EN 14306) 870+/-50kg/m3 and fibre-cement board 1800+/-200kg/m3.
NOTE: Standard calcium silicate board is not representative of gypsum plasterboard end use (due to the paper layer), but would be representative of most gypsum plasters (with densities of more than 650kg/m3).
NOTE: Classifications based on tests using a plasterboard substrate would also be acceptable for products bonded to a gypsum plaster end use substrate.
Thermoplastic materials
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: Thermoplastic materials (2029 amendment).
B10
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: B10 (2029 amendment).
Thermoplastic material is any synthetic polymeric material that has a softening point below 200°C if tested to BS EN ISO 306 Method A120. Products formed from these materials cannot always be classified in the normal way. In those circumstances the following approach can be followed.
B11
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: B11 (2029 amendment).
Thermoplastic materials used for window glazing, rooflights and lighting diffusers within suspended ceilings do not need to meet the criteria within paragraph B18 onwards, if the guidance to requirements B2 and B4 is followed.
B12
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: B12 (2029 amendment).
For the purposes of requirements B2 and B4, thermoplastic materials should be classified as TP(a) rigid, TP(a) flexible or TP(b), as follows:
B13
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: B13 (2029 amendment).
A thermoplastic material alone when used as a lining to a wall or ceiling cannot be assumed to protect a substrate. The surface rating of both thermoplastic material and substrate must therefore meet the required classification.
If, however, the thermoplastic material is fully bonded to a non-thermoplastic substrate, then only the surface rating of the composite needs to meet the required classification.
Roofs
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: Roofs (2029 amendment).
B14
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: B14 (2029 amendment).
Performance of the resistance of roofs to external fire exposure is measured in terms of penetration through the roof construction and the spread of flame over its surface.
B15
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: B15 (2029 amendment).
Roof constructions are classified within the European system as BROOF(t4), CROOF(t4), DROOF(t4), EROOF(t4) or FROOF(t4) in accordance with BS EN 13501-5. BROOF(t4) indicates the highest performance and FROOF(t4) the lowest.
B16
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: B16 (2029 amendment).
BS EN 13501-5 refers to four separate roof tests. The suffix (t4) used in paragraph B15 indicates that Test 4 is to be used for the purposes of this approved document.
B17
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: B17 (2029 amendment).
This document uses the European classification system for roof covering set out in BS EN 13501-5; however, there may be some products or systems whose performance will need to be assessed based on the recommendations of paragraphs B1 to B5 as being capable of meeting that performance classification.
Fire resistance
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: Fire resistance (2029 amendment).
B18
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: B18 (2029 amendment).
Common to all of the provisions of Part B of the Building Regulations is the property of fire resistance. Fire resistance is a measure of one or more of the following.
B19
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: B19 (2029 amendment).
The standards of fire resistance necessary for a particular building are based on assumptions about the severity of fires and the consequences should an element fail. Fire severity is estimated in very broad terms from the use of the building (its purpose group), on the assumption that the building contents (which constitute the fire load) are similar for buildings with the same use.
B20
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: B20 (2029 amendment).
Because the use of buildings may change, a precise estimate of fire severity based on the fire load due to a particular use may be misleading. Therefore if a fire engineering approach of this kind is adopted, the likelihood that the fire load may change in the future needs to be considered.
B21
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: B21 (2029 amendment).
Performance in terms of the fire resistance to be achieved by elements of structure, doors and other forms of construction is classified in accordance with one of the following.
B22
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: B22 (2029 amendment).
Fire resistance is measured in minutes. This relates to time elapsed in a standard test and should not be confused with real time.
B23
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: B23 (2029 amendment).
The fire resistance necessary for different circumstances is set out in the following tables.
B24
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: B24 (2029 amendment).
This document uses the European classification system for fire resistance set out in BS EN 13501-2 to 4; however, there may be some products lawfully on the market using the classification system set out in previous editions. In those situations the alternative classifications given in Table B1 can be used.
Table B1 Specific provisions of the test for fire resistance of elements of structure, etc.
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: Table B1 Specific provisions of the test for fire resistance of elements of structure, etc. (2029 amendment).
| Part of building | Minimum provisions when tested to the relevant European standard (minutes)(1) | Alternative minimum provisions when tested to the relevant part of BS 476(2) (minutes) | Type of exposure | ||
|---|---|---|---|---|---|
| Loadbearing capacity(3) | Integrity | Insulation | |||
1. Structural frame, beam or column. | R see Table B2 | See Table B2 | Not applicable | Not applicable | Exposed faces |
2. Loadbearing wall (for a wall which is also described in any of the following items, the more onerous guidance should be applied). | R see Table B2 | See Table B2 | Not applicable | Not applicable | Each side separately |
3. Floors(4) | |||||
a. between a shop and flat above | REI 60 or see Table B2 (whichever is greater) | 60 min or see Table B2 (whichever is greater) | 60 min or see Table B2 (whichever is greater) | 60 min or see Table B2 (whichever is greater) | From underside(5) |
b. in upper storey of two storey dwellinghouse (but not over garage or basement) | R 30 and EI 15 | 30 min | 15 min | 15 min | From underside(5) |
c. any other floor – including compartment floors. | REI see Table B2 | See Table B2 | See Table B2 | See Table B2 | From underside(5) |
4. Roofs | |||||
a. any part forming an escape route | REI 30 | 30 min | 30 min | 30 min | From underside(5) |
b. any roof that performs the function of a floor. | REI see Table B2 | See Table B2 | See Table B2 | See Table B2 | From underside(5) |
5. External walls | |||||
a. any part a maximum of 1000mm from any point on the relevant boundary(6) | REI see Table B2 | See Table B2 | See Table B2 | See Table B2 | Each side separately |
b. any part a minimum of 1000mm from the relevant boundary(6) | RE see Table B2 and I 15 | See Table B2 | See Table B2 | 15 min | From inside the building |
c. any part beside an external escape route (Section 2 Diagram 2.7 of Approved Document B Volume 1 and Section 3, Diagram 3.4). | RE 30 | 30 min | 30 min | No provision(7) (8) | From inside the building |
6. Compartment walls Separating either: | |||||
a. a flat from any other part of the building (see paragraph 7.1 of Approved Document B Volume 1) | REI 60 or see Table B2 (whichever is less) | 60 min or see Table B2 (whichever is less) | 60 min or see Table B2 (whichever is less) | 60 min or see Table B2 (whichever is less) | Each side separately |
b. occupancies. | REI 60 or see Table B2 (whichever is less) | 60 min or see Table B2 (whichever is less) | 60 min or see Table B2 (whichever is less) | 60 min or see Table B2 (whichever is less) | Each side separately |
7. Compartment walls (other than in item 6 or item 10). | REI see Table B2 | See Table B2 | See Table B2 | See Table B2 | Each side separately |
8. Protected shafts Excluding any firefighting shaft: | |||||
a. any glazing described in Section 8 diagram 8.4 | E 30 | Not applicable | 30 min | No provision(8) | Each side separately |
b. any other part between the shaft and a protected lobby/corridor described in Section 8 diagram 8.4 | REI 30 | 30 min | 30 min | 30 min | Each side separately |
c. any part not described in (a) or (b) above. | REI see Table B2 | See Table B2 | See Table B2 | See Table B2 | Each side separately |
9. Enclosure (that does not form part of a compartment wall or a protected shaft) to a: | |||||
a. protected stairway | REI 30(8) | 30 min | 30 min | 30 min(8) | Each side separately |
b. lift shaft. | REI 30 | 30 min | 30 min | 30 min | Each side separately |
10. Wall or floor separating an attached or integral garage from a dwellinghouse | REI 30(8) | 30 min | 30 min | 30 min(8) | From garage side |
11. Fire resisting construction in dwellinghouses not described elsewhere | REI 30(8) | 30 min | 30 min | 30 min(8) | Each side separately |
12. Firefighting shafts | REI 120 | 120 min | 120 min | 120 min | From side remote from shaft |
a. construction that separates firefighting shaft from rest of building | REI 60 | 60 min | 60 min | 60 min | From shaft side |
b. construction that separates firefighting stair, firefighting lift shaft and firefighting lobby. | REI 60 | 60 min | 60 min | 60 min | Each side separately |
13. Enclosure (that is not a compartment wall or described in item 8) to a: | |||||
a. protected lobby | REI 30(8) | 30 min | 30 min | 30 min(8) | Each side separately |
b. protected corridor. | REI 30(8) | 30 min | 30 min | 30 min(8) | Each side separately |
14. Sub-division of a corridor | REI 30(8) | 30 min | 30 min | 30 min(8) | Each side separately |
15. Fire resisting construction | |||||
a. construction that encloses places of special fire hazard | REI 30 | 30 min | 30 min | 30 min | Each side separately |
b. construction between store rooms and sales area in shops | REI 30 | 30 min | 30 min | 30 min | Each side separately |
c. fire resisting sub-division | REI 30 | 30 min | 30 min | 30 min | Each side separately |
d. construction that encloses bedrooms and ancillary accommodation in care homes. | REI 30 | 30 min | 30 min | 30 min | Each side separately |
16. Enclosure in a flat to a protected entrance hall, or to a protected landing. | REI 30(8) | 30 min | 30 min | 30 min(8) | Each side separately |
17. Cavity barrier | E 30 and I 15 | Not applicable | 30 min | 15 min | Each side separately |
18. Ceiling see paragraph 2.5, Diagram 2.3 of Approved Document B Volume 1 and paragraph 9.5 and Diagram 9.3. | EI 30 | Not applicable | 30 min | 30 min | From underside |
19. Duct described in paragraph 9.17e. | E 30 | Not applicable | 30 min | No provision | From outside |
20. Casing around a drainage system described in Diagram 9.1 of Approved Document B Volume 1. | E 30 | Not applicable | 30 min | No provision | From outside |
21. Flue walls described in Diagram 10.4. | EI half the period given in Table B2 for the compartment wall/floor | Not applicable | Half the period given in Table B2 for the compartment wall/floor | Half the period given in Table B2 for the compartment wall/floor | From outside |
22. Construction described in note (a) to paragraph 12.9 of Approved Document B Volume 1. | EI 30 | Not applicable | 30 min | 30 min | From underside |
23. Fire doorsets | See Table C1 | See Table C1 | See Appendix C | ||
NOTES:
Table B2 Minimum periods of fire resistance
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: Table B2 Minimum periods of fire resistance (2029 amendment).
| Purpose group of building | Minimum periods of fire resistance(1) (minutes) in a: | ||||||
|---|---|---|---|---|---|---|---|
| Basement storey* including floor over | Ground or upper storey | ||||||
| Depth (m) of the lowest basement | Height (m) of top floor above ground, in a building or separated part of a building | ||||||
| More than 10 | Up to 10 | Up to 5 | Up to 11 | Up to 18 | Up to 30 | More than 30 | |
1. Residential: a. Block of flats | |||||||
| – without sprinkler system | 90 min | 60 min | 30 min† | 60 min+§ | Not permitted(2) | Not permitted(2) | Not permitted(2) |
| – with sprinkler system(3) | 90 min | 60 min | 30 min† | 60 min+§ | 60 min+§ | 90 min+ | 120 min+ |
b. and c. Dwellinghouse | Not applicable(4) | 30 min*† | 30 min† | 60 min(5) | 60 min(5) | Not applicable(4) | Not applicable(4) |
2. Residential | |||||||
a. Institutional | 90 min | 60 min | 30 min† | 60 min | 60 min | 90 min | 120 min‡ |
b. Other residential | 90 min | 60 min | 30 min† | 60 min | 60 min | 90 min | 120 min‡ |
3. Office: | |||||||
| – without sprinkler system | 90 min | 60 min | 30 min† | 60 min | 60 min | 90 min | Not permitted(6) |
| – with sprinkler system(3) | 60 min | 60 min | 30 min† | 30 min† | 30 min† | 60 min | 120 min‡ |
4. Shop and commercial: | |||||||
| – without sprinkler system | 90 min | 60 min | 60 min | 60 min | 60 min | 90 min | Not permitted(6) |
| – with sprinkler system(3) | 60 min | 60 min | 30 min† | 60 min | 60 min | 60 min | 120 min‡ |
5. Assembly and recreation: | |||||||
| – without sprinkler system | 90 min | 60 min | 60 min | 60 min | 60 min | 90 min | Not permitted(6) |
| – with sprinkler system(3) | 60 min | 60 min | 30 min† | 60 min | 60 min | 60 min | 120 min‡ |
6. Industrial: | |||||||
| – without sprinkler system | 120 min | 90 min | 60 min | 90 min | 90 min | 120 min | Not permitted(6) |
| – with sprinkler system(3) | 90 min | 60 min | 30 min† | 60 min | 60 min | 90 min | 120 min‡ |
7. Storage and other nonresidential: a. any building or part not described elsewhere: | |||||||
| – without sprinkler system | 120 min | 90 min | 60 min | 90 min | 90 min | 120 min | Not permitted(6) |
| – with sprinkler system(3) | 90 min | 60 min | 30 min† | 60 min | 60 min | 90 min | 120 min‡ |
b. car park for light vehicles: | |||||||
i. open sided car park(7) | Not applicable | Not applicable | 15 min†# | 15 min†#(8) | 15 min†#(8) | 15 min†#(8) | 60 min |
ii. any other car park | 90 min | 60 min | 30 min† | 60 min | 60 min | 90 min | 120 min‡ |
NOTES:
For single storey buildings, the periods under the heading ‘Up to 5’ apply. If single storey buildings have basements, for the basement storeys the period appropriate to their depth applies.
† For compartment walls that separate buildings, the period is increased to a minimum of 60 minutes.
+ For any floor that does not contribute to the support of the building within a flat of more than one storey, the period is reduced to 30 minutes.
§ For flat conversions, refer to paragraphs 6.5 to 6.7 of Approved Document B Volume 1 regarding the acceptability of 30 minutes.
‡ For elements that do not form part of the structural frame, the period is reduced to 90 minutes.
# For elements that protect the means of escape, the period is increased to 30 minutes.
Application of the fire resistance standards in Table B2
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: Application of the fire resistance standards in Table B2 (2029 amendment).
B25
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: B25 (2029 amendment).
The following guidance should be used when applying the fire resistance standards in Table B2.
B26
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: B26 (2029 amendment).
For the purposes of this paragraph, the ground storey of a building that has one or more basement storeys and no upper storeys may be considered as a single storey building. The fire resistance of the basement storeys should be that specified for basements.
Table B3 Limitations on the use of uninsulated glazed elements on escape routes. These limitations do not apply to glazed elements that satisfy the relevant insulation criterion, see Table B1
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: Table B3 Limitations on the use of uninsulated glazed elements on escape routes. These limitations do not apply to glazed elements that satisfy the relevant insulation criterion, see Table B1 (2029 amendment).
| Position of glazed element | Maximum total glazed area in parts of a building with access to: | |||
|---|---|---|---|---|
| A single stair | More than one stair | |||
| Walls | Door leaf | Walls | Door leaf | |
| Flats | ||||
1. Within the enclosures of a protected entrance hall or protected landing, or within fire resisting separation shown in Section 3, Diagram 3.4, of Approved Document B Volume 1. | Fixed fanlights only | Unlimited above 1100mm from floor | Fixed fanlights only | Unlimited above 1100mm from floor |
| Dwellinghouses | ||||
2. Within either: a. the enclosures of a protected stairway b. fire resisting separation shown in Diagram 2.2 of Approved Document B Volume 1. | Unlimited above 1100mm from floor or pitch of the stair | Unlimited | Unlimited above 1100mm from floor or pitch of the stair | Unlimited |
3. Within fire resisting separation either: a. shown in Diagram 2.4 of Approved Document B Volume 1 b. described in paragraph 2.16b of Approved Document B Volume 1. | Unlimited above 100mm from floor | Unlimited above 100mm from floor | Unlimited above 100mm from floor | Unlimited above 100mm from floor |
4. Existing window between an attached/ integral garage and the dwellinghouse. | Unlimited | Not applicable | Unlimited | Not applicable |
5. Adjacent to an external escape stair (see paragraph 2.17 and Diagram 2.7 of Approved Document B Volume 1) or roof escape route (see paragraph 2.13 of Approved Document B Volume 1). | Unlimited | Unlimited | Unlimited | Unlimited |
| General (except dwellinghouses) | ||||
6. Between residential/sleeping accommodation and a common escape route (corridor, lobby or stair). | Nil | Nil | Nil | Nil |
7. Between a protected stairway(1) and either: a. the accommodation b. a corridor that is not a protected corridor other than in item 6 above. | Nil | 25% of door area | Unlimited above 1100mm(2) | 50% of door area |
8. Between either: a. a protected stairway(1) and a protected lobby or protected corridor b. accommodation and a protected lobby other than in item 6 above. | Unlimited above 1100mm from floor | Unlimited above 100mm from floor | Unlimited above 100mm from floor | Unlimited above 100mm from floor |
9. Between the accommodation and a protected corridor that forms a dead end, other than in item 6 above. | Unlimited above 1100mm from floor | Unlimited above 100mm from floor | Unlimited above 1100mm from floor | Unlimited above 100mm from floor |
10. Between accommodation and any other corridor, or subdividing corridors, other than in item 6 above. | Not applicable | Not applicable | Unlimited above 100mm from floor | Unlimited above 100mm from floor |
11. Beside an external escape route. | Unlimited above 1100mm from floor | Unlimited above 1100mm from floor | Unlimited above 1100mm from floor | Unlimited above 1100mm from floor |
12. Beside an external escape stair (see paragraph 3.32 and Diagram 3.4) or roof escape route (see paragraph 2.32). | Unlimited | Unlimited | Unlimited | Unlimited |
NOTES:
Items 1 and 8 apply also to single storey buildings.
Fire resisting glass should be marked with the name of the manufacturer and the name of the product.
Further guidance can be found in A Guide to Best Practice in the Specification and Use of Fire-resistant Glazed Systems published by the Glass and Glazing Federation.
Appendix B: Performance of materials, products and structures (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: Appendix B: Performance of materials, products and structures.
Introduction (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: Introduction.
B1 (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: B1.
The guidance in this document is given in terms of performance classifications in relation to European Standards. In such cases, it will be necessary to demonstrate that a system or product can meet the relevant performance classification. This will be achieved if the system or product complies with one of the following.
NOTE: Some products are subject to Classification Without Further Testing (CWFT). For the purposes of this approved document, such products can be considered to have been shown to be capable of meeting a performance specification as per paragraph B1a.
B2 (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: B2.
Any test evidence used to demonstrate the fire performance classification of a product or system should be carefully checked to ensure that it is applicable to the intended use. Small differences in detail, such as fixing method, joints, dimensions, the introduction of insulation materials and air gaps (ventilated or not), might significantly affect the performance and should be tested or assessed in accordance with paragraph B1.
B3 (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: B3.
Assessments should not be regarded as a way to avoid a test where one is necessary. Assessments should only be carried out where sufficient relevant test evidence is available. Relevant test evidence is unlikely to be provided by test standards which have different classification criteria.
B4 (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: B4.
Where it is proposed to assess the classification of a product or system in lieu of carrying out a specific test (as in paragraph B1c), this should be done in accordance with the relevant standard for extended application for the test in question and should include details of the test evidence that has been used to support the assessment.
For performance classifications where there is no specific standard for extended application, assessment reports should be produced in accordance with the principles of BS EN 15725 and should include details of the test evidence that has been used to support the assessment. In cases where the end use application is not covered by the extended application standard and an assessment is the only other suitable approach, then further information on best practice is provided in the Passive Fire Protection Forum’s Guide to Undertaking Technical Assessments of the Fire Performance of Construction Products Based on Fire Test Evidence. The same principle should be followed for assessments as described in paragraph B2.
NOTE: Regulation 7(2) limits components used in or on the external walls of certain buildings to materials achieving class A2-s1, d0 or class A1 (see Section 12). Assessments cannot be used to demonstrate compliance with this requirement.
B5 (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: B5.
Tests and assessments should be carried out by organisations with the necessary expertise. For example, organisations listed as ‘notified bodies’ in accordance with the European Construction Products Regulation or laboratories accredited by the United Kingdom Accreditation Service (UKAS) for the relevant test standard can be assumed to have the necessary expertise.
NOTE: Standard fire tests do not directly measure fire hazard. They measure or assess the response of a material or system to exposure to one or more aspects of fire conditions. Performance in fire tests is only one of a number of factors that should be taken into account.
Reaction to fire (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: Reaction to fire.
B6 (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: B6.
Reaction to fire relates to the degree to which a product will contribute, by its own decomposition, to a fire under specified conditions. Products, other than floorings, are classified as A1, A2, B, C, D, E or F (with class A1 being the highest performance and F being the lowest) in accordance with BS EN 13501-1. Class F is assigned when a product fails to attain class E. Untested products cannot be classified in accordance with BS EN 13501-1.
Materials covered by the Classification Without Further Testing (CWFT) process can be found by accessing the European Commission’s website https://eur-lex.europa.eu/.
B7 (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: B7.
The classes of reaction to fire performance of A2, B, C, D and E are accompanied by additional classifications related to the production of smoke (s1, s2, s3), with s1 indicating the lowest production, and/or flaming droplets/particles (d0, d1, d2), with d0 indicating the lowest production.
NOTE: When a classification includes s3, d2 this means that there is no limit set for smoke production and/or flaming droplets/particles.
B8 (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: B8.
To reduce the testing burden on manufacturers, BS EN 13238 defines a number of standard substrates that produce test results representative of different end use applications. The classification for reaction to fire achieved during testing is only valid when the product is used within this direct field of application, i.e. when the product is fixed to a substrate of that class in its end use. The standard substrate selected for testing should take account of the intended end use applications (field of application) of the product and represent end use substrates that have a density of a minimum of 75% of the standard substrate’s nominal density.
B9 (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: B9.
Standard substrates include gypsum plasterboard (BS EN 520) with a density of 700+/-100kg/m3, calcium silicate board (BS EN 14306) 870+/-50kg/m3 and fibre-cement board 1800+/-200kg/m3.
NOTE: Standard calcium silicate board is not representative of gypsum plasterboard end use (due to the paper layer), but would be representative of most gypsum plasters (with densities of more than 650kg/m3).
NOTE: Classifications based on tests using a plasterboard substrate would also be acceptable for products bonded to a gypsum plaster end use substrate.
Thermoplastic materials (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: Thermoplastic materials.
B10 (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: B10.
Thermoplastic material is any synthetic polymeric material that has a softening point below 200°C if tested to BS EN ISO 306 Method A120. Products formed from these materials cannot always be classified in the normal way. In those circumstances the following approach can be followed.
B11 (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: B11.
Thermoplastic materials used for window glazing, rooflights and lighting diffusers within suspended ceilings do not need to meet the criteria within paragraph B18 onwards, if the guidance to requirements B2 and B4 is followed.
B12 (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: B12.
For the purposes of requirements B2 and B4, thermoplastic materials should be classified as TP(a) rigid, TP(a) flexible or TP(b), as follows:
NOTE: If it is not possible to cut or machine a 3mm thick specimen from the product, then a 3mm test specimen can be moulded from the same material as that used to manufacture the product.
B13 (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: B13.
A thermoplastic material alone when used as a lining to a wall or ceiling cannot be assumed to protect a substrate. The surface rating of both thermoplastic material and substrate must therefore meet the required classification.
If, however, the thermoplastic material is fully bonded to a non-thermoplastic substrate, then only the surface rating of the composite needs to meet the required classification.
Roofs (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: Roofs.
B14 (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: B14.
Performance of the resistance of roofs to external fire exposure is measured in terms of penetration through the roof construction and the spread of flame over its surface.
B15 (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: B15.
Roof constructions are classified within the European system as BROOF(t4), CROOF(t4), DROOF(t4), EROOF(t4) or FROOF(t4) in accordance with BS EN 13501-5. BROOF(t4) indicates the highest performance and FROOF(t4) the lowest.
B16 (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: B16.
BS EN 13501-5 refers to four separate roof tests. The suffix (t4) used in paragraph B15 indicates that Test 4 is to be used for the purposes of this approved document.
B17 (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: B17.
This document uses the European classification system for roof covering set out in BS EN 13501-5; however, there may be some products or systems whose performance will need to be assessed based on the recommendations of paragraphs B1 to B5 as being capable of meeting that performance classification.
Fire resistance (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: Fire resistance.
B18 (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: B18.
Common to all of the provisions of Part B of the Building Regulations is the property of fire resistance. Fire resistance is a measure of one or more of the following criteria.
B19 (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: B19.
The standards of fire resistance necessary for a particular building are based on assumptions about the severity of fires and the consequences should an element fail. Fire severity is estimated in very broad terms from the use of the building (its purpose group), on the assumption that the building contents (which constitute the fire load) are similar for buildings with the same use.
B20 (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: B20.
Because the use of buildings may change, a precise estimate of fire severity based on the fire load due to a particular use may be misleading. Therefore if a fire engineering approach of this kind is adopted, the likelihood that the fire load may change in the future needs to be considered.
B21 (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: B21.
Performance in terms of the fire resistance to be achieved by elements of structure, doors and other forms of construction is classified in accordance with one of the following.
B22 (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: B22.
Fire resistance is measured in minutes. This relates to time elapsed in a standard test and should not be confused with real time.
B23 (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: B23.
The fire resistance necessary for different circumstances is set out in the following tables.
B24 (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: B24.
This document uses the European classification system (REI) for fire resistance set out in BS EN 13501-2 to 4. Fire resistance is expressed as REI X, where X is the period of fire resistance in minutes in terms of loadbearing capacity (R), integrity (E) and insulation (I). Products or systems cannot typically assume a European class unless they have been tested and classified accordingly.
B25 (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: B25.
Products or systems achieving the European classification (REI) should be specified wherever possible. However, there may be some products or systems that have been assessed as being capable of meeting a fire resistance performance classification. When assessed, products or systems should follow the relevant test standards to indicate their fire resistance performance in terms of loadbearing capacity, integrity and insulation based on the recommendations of paragraphs B1 to B5. In those situations, the performance classifications given in Table B1 and Table B2 may be used.
Table B1 Specific provisions of the test for fire resistance of elements of structure, etc. (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: Table B1 Specific provisions of the test for fire resistance of elements of structure, etc..
| Part of building | Minimum provisions when tested and classified to the relevant European standard (minutes)(1) or assessed following the recommendations of paragraphs B1 to B5 (minutes)(2) | Type of exposure | ||
|---|---|---|---|---|
| Loadbearing capacity(3) | Integrity | Insulation | ||
1. Structural frame, beam or column. | See Table B2 | Not applicable | Not applicable | Exposed faces |
2. Loadbearing wall (for a wall which is also described in any of the following items, the more onerous guidance should be applied). | See Table B2 | Not applicable | Not applicable | Each side separately |
3. Floors(4) | ||||
a. between a shop and flat above | 60 min or see Table B2 (whichever is greater) | 60 min or see Table B2 (whichever is greater) | 60 min or see Table B2 (whichever is greater) | From underside(5) |
b. in upper storey of two storey dwellinghouse (but not over garage or basement) | 30 min | 15 min | 15 min | From underside (5) |
c. any other floor – including compartment floors. | See Table B2 | See Table B2 | See Table B2 | From underside (5) |
4. Roofs | ||||
a. any part forming an escape route | 30 min | 30 min | 30 min | From underside (5) |
b. any roof that performs the function of a floor. | See Table B2 | See Table B2 | See Table B2 | From underside (5) |
5. External walls | ||||
a. any part a maximum of 1000mm from any point on the relevant boundary(6) | See Table B2 | See Table B2 | See Table B2 | Each side separately |
b. any part a minimum of 1000mm from the relevant boundary(6) | See Table B2 | See Table B2 | 15 min | From inside the building |
c. any part beside an external escape route (Section 2, Diagram 2.7 of Approved Document B Volume 1 and Section 3, Diagram 3.4). | 30 min | 30 min | No provision(7) (8) | From inside the building |
6. Compartment walls Separating either: | ||||
a. a flat from any other part of the building (see paragraph 7.1 of Approved Document B Volume 1) | 60 min or see Table B2 (whichever is less) | 60 min or see Table B2 (whichever is less) | 60 min or see Table B2 (whichever is less) | Each side separately |
b. occupancies. | 60 min or see Table B2 (whichever is less) | 60 min or see Table B2 (whichever is less) | 60 min or see Table B2 (whichever is less) | Each side separately |
7. Compartment walls (other than in item 6 or item 10). | See Table B2 | See Table B2 | See Table B2 | Each side separately |
8. Protected shafts Excluding any firefighting shaft: | ||||
a. any glazing described in Section 8, Diagram 8.4 | Not applicable | 30 min | No provision(8) | Each side separately |
b. any other part between the shaft and a protected lobby/corridor described in Section 8, Diagram 8.4 | 30 min | 30 min | 30 min | Each side separately |
c. any part not described in (a) or (b) above. | See Table B2 | See Table B2 | See Table B2 | Each side separately |
9. Enclosure (that does not form part of a compartment wall or a protected shaft) to a: | ||||
a. protected stairway | 30 min | 30 min | 30 min(8) | Each side separately |
b. lift shaft. | 30 min | 30 min | 30 min | Each side separately |
10. Wall or floor separating an attached or integral garage from a dwellinghouse | 30 min | 30 min | 30 min(8) | From garage side |
11. Fire resisting construction in dwellinghouses not described elsewhere | 30 min | 30 min | 30 min(8) | Each side separately |
12. Firefighting shafts | 120 min | 120 min | 120 min | From side remote from shaft |
a. construction that separates firefighting shaft from rest of building | 60 min | 60 min | 60 min | From shaft side |
b. construction that separates firefighting stair, firefighting lift shaft and firefighting lobby. | 60 min | 60 min | 60 min | Each side separately |
13. Enclosure (that is not a compartment wall or described in item 8) to a: | ||||
a. protected lobby | 30 min | 30 min | 30 min(8) | Each side separately |
b. protected corridor. | 30 min | 30 min | 30 min(8) | Each side separately |
14. Sub-division of a corridor | 30 min | 30 min | 30 min(8) | Each side separately |
15. Fire resisting construction | ||||
a. construction that encloses places of special fire hazard | 30 min | 30 min | 30 min | Each side separately |
b. construction between store rooms and sales area in shops | 30 min | 30 min | 30 min | Each side separately |
c. fire resisting sub-division | 30 min | 30 min | 30 min | Each side separately |
d. construction that encloses bedrooms and ancillary accommodation in care homes. | 30 min | 30 min | 30 min | Each side separately |
16. Enclosure in a flat to a protected entrance hall, or to a protected landing. | 30 min | 30 min | 30 min(8) | Each side separately |
17. Cavity barrier | Not applicable | 30 min | 15 min | Each side separately |
18. Ceiling see see paragraph 2.5, Diagram 2.3 of Approved Document B Volume 1 and paragraph 9.5 and Diagram 9.3. | Not applicable | 30 min | 30 min | From underside |
19. Duct described in paragraph 9.17e. | Not applicable | 30 min | No provision | From outside |
20. Casing around a drainage system described in Diagram 9.1 of Approved Document B Volume 1. | Not applicable | 30 min | No provision | From outside |
21. Flue walls described in Diagram 10.4. | Not applicable | Half the period given in Table B2 for the compartment wall/floor | Half the period given in Table B2 for the compartment wall/floor | From outside |
22. Construction described in note (a) to paragraph 12.9 of Approved Document B Volume 1. | Not applicable | 30 min | 30 min | From underside |
23. Fire doorsets | See Table C1 | See Appendix C | ||
NOTES:
Table B2 Minimum periods of fire resistance (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: Table B2 Minimum periods of fire resistance.
| Purpose group of building | Minimum periods of fire resistance(1) (minutes) in a: | ||||||
|---|---|---|---|---|---|---|---|
| Basement storey* including floor over | Ground or upper storey | ||||||
| Depth (m) of the lowest basement | Height (m) of top floor above ground, in a building or separated part of a building | ||||||
| More than 10 | Up to 10 | Up to 5 | Up to 11 | Up to 18 | Up to 30 | More than 30 | |
1. Residential: a. Block of flats | |||||||
| – without sprinkler system | 90 min | 60 min | 30 min† | 60 min+§ | Not permitted(2) | Not permitted(2) | Not permitted(2) |
| – with sprinkler system(3) | 90 min | 60 min | 30 min† | 60 min+§ | 60 min+§ | 90 min+ | 120 min+ |
b. and c. Dwellinghouse | Not applicable(4) | 30 min*† | 30 min† | 60 min(5) | 60 min(5) | Not applicable(4) | Not applicable(4) |
2. Residential | |||||||
a. Institutional | 90 min | 60 min | 30 min† | 60 min | 60 min | 90 min | 120 min‡ |
b. Other residential | 90 min | 60 min | 30 min† | 60 min | 60 min | 90 min | 120 min‡ |
3. Office: | |||||||
| – without sprinkler system | 90 min | 60 min | 30 min† | 60 min | 60 min | 90 min | Not permitted(6) |
| – with sprinkler system(3) | 60 min | 60 min | 30 min† | 30 min† | 30 min† | 60 min | 120 min‡ |
4. Shop and commercial: | |||||||
| – without sprinkler system | 90 min | 60 min | 60 min | 60 min | 60 min | 90 min | Not permitted(6) |
| – with sprinkler system(3) | 60 min | 60 min | 30 min† | 60 min | 60 min | 60 min | 120 min‡ |
5. Assembly and recreation: | |||||||
| – without sprinkler system | 90 min | 60 min | 60 min | 60 min | 60 min | 90 min | Not permitted(6) |
| – with sprinkler system(3) | 60 min | 60 min | 30 min† | 60 min | 60 min | 60 min | 120 min‡ |
6. Industrial: | |||||||
| – without sprinkler system | 120 min | 90 min | 60 min | 90 min | 90 min | 120 min | Not permitted(6) |
| – with sprinkler system(3) | 90 min | 60 min | 30 min† | 60 min | 60 min | 90 min | 120 min‡ |
7. Storage and other nonresidential: a. any building or part not described elsewhere: | |||||||
| – without sprinkler system | 120 min | 90 min | 60 min | 90 min | 90 min | 120 min | Not permitted(6) |
| – with sprinkler system(3) | 90 min | 60 min | 30 min† | 60 min | 60 min | 90 min | 120 min‡ |
b. car park for light vehicles: | |||||||
i. open sided car park(7) Not applicable | Not applicable | 15 min†# | 15 min†#(8) | 15 min†#(8) | 15 min†#(8) | 60 min | |
ii. any other car park 90 min | 60 min | 30 min† | 60 min | 60 min | 90 min | 120 min‡ | |
NOTES:
For single storey buildings, the periods under the heading ‘Up to 5’ apply. If single storey buildings have basements, for the basement storeys the period appropriate to their depth applies.
† For compartment walls that separate buildings, the period is increased to a minimum of 60 minutes.
+ For any floor that does not contribute to the support of the building within a flat of more than one storey, the period is reduced to 30 minutes.
§ For flat conversions, refer to paragraphs 6.5 to 6.7 of Approved Document B Volume 1 regarding the acceptability of 30 minutes.
‡ For elements that do not form part of the structural frame, the period is reduced to 90 minutes.
# For elements that protect the means of escape, the period is increased to 30 minutes.
Application of the fire resistance standards in Table B2 (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: Application of the fire resistance standards in Table B2.
B26 (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: B26.
The following guidance should be used when applying the fire resistance standards in Table B2.
B27 (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: Appendix B: Performance of materials, products and structures.
For the purposes of this paragraph, the ground storey of a building that has one or more basement storeys and no upper storeys may be considered as a single storey building. The fire resistance of the basement storeys should be that specified for basements.
Table B3 Limitations on the use of uninsulated glazed elements on escape routes. These limitations do not apply to glazed elements that satisfy the relevant insulation criterion, see Table B1 (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: Table B3 Limitations on the use of uninsulated glazed elements on escape routes. These limitations do not apply to glazed elements that satisfy the relevant insulation criterion, see Table B1.
| Position of glazed element | Maximum total glazed area in parts of a building with access to: | |||
|---|---|---|---|---|
| A single stair | More than one stair | |||
| Walls | Door leaf | Walls | Door leaf | |
| Flats | ||||
1. Within the enclosures of a protected entrance hall or protected landing, or within fire resisting separation shown in Section 3, Diagram 3.4 of Approved Document B Volume 1. | Fixed fanlights only | Unlimited above 1100mm from floor | Fixed fanlights only | Unlimited above 1100mm from floor |
| Dwellinghouses | ||||
2. Within either: a. the enclosures of a protected stairway b. fire resisting separation shown in Diagram 2.2 of Approved Document B Volume 1. | Unlimited above 1100mm from floor or pitch of the stair | Unlimited | Unlimited above 1100mm from floor or pitch of the stair | Unlimited |
3. Within fire resisting separation either: a. shown in Diagram 2.4 of Approved Document B Volume 1 b. described in paragraph 2.16b of Approved Document B Volume 1. | Unlimited above 100mm from floor | Unlimited above 100mm from floor | Unlimited above 100mm from floor | Unlimited above 100mm from floor |
4. Existing window between an attached/ integral garage and the dwellinghouse. | Unlimited | Not applicable | Unlimited | Not applicable |
5. Adjacent to an external escape stair (see paragraph 2.17 and Diagram 2.7 of Approved Document B Volume 1) or roof escape route (see paragraph 2.13 of Approved Document B Volume 1). | Unlimited | Unlimited | Unlimited | Unlimited |
| General (except dwellinghouses) | ||||
6. Between residential/sleeping accommodation and a common escape route (corridor, lobby or stair). | Nil | Nil | Nil | Nil |
7. Between a protected stairway(1) and either: a. the accommodation b. a corridor that is not a protected corridor other than in item 6 above. | Nil | 25% of door area | Unlimited above 1100mm(2) | 50% of door area |
8. Between either: a. a protected stairway(1) and a protected lobby or protected corridor b. accommodation and a protected lobby other than in item 6 above. | Unlimited above 1100mm from floor | Unlimited above 100mm from floor | Unlimited above 100mm from floor | Unlimited above 100mm from floor |
9. Between the accommodation and a protected corridor that forms a dead end, other than in item 6 above. | Unlimited above 1100mm from floor | Unlimited above 100mm from floor | Unlimited above 1100mm from floor | Unlimited above 100mm from floor |
10. Between accommodation and any other corridor, or sub-dividing corridors, other than in item 6 above. | Not applicable | Not applicable | Unlimited above 100mm from floor | Unlimited above 100mm from floor |
11. Beside an external escape route. | Unlimited above 1100mm from floor | Unlimited above 1100mm from floor | Unlimited above 1100mm from floor | Unlimited above 1100mm from floor |
12. Beside an external escape stair (see paragraph 3.32 and Diagram 3.4) or roof escape route (see paragraph 2.32). | Unlimited | Unlimited | Unlimited | Unlimited |
NOTES:
Items 1 and 8 apply also to single storey buildings.
Fire resisting glass should be marked with the name of the manufacturer and the name of the product.
Further guidance can be found in A Guide to Best Practice in the Specification and Use of Fire-resistant Glazed Systems published by the Glass and Glazing Federation.
Appendix C: Fire doorsets
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: Appendix C: Fire doorsets (2029 amendment).
C1
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: C1 (2029 amendment).
All fire doorsets should have the performance shown in Table C1, based on one of the following.
C2
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: C2 (2029 amendment).
The performance requirement is in terms of integrity (E) for a period of minutes. An additional classification of Sa is used for all doors where restricted smoke leakage at ambient temperatures is needed.
C3
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: C3 (2029 amendment).
The requirement is for test exposure from each side of the doorset separately. The exception is lift doors, which are tested from the landing side only.
C4
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: C4 (2029 amendment).
Any test evidence used to verify the fire resistance rating of a doorset or shutter should be checked to ensure both of the following.
Until relevant harmonised product standards are published, for the purposes of meeting the Building Regulations, products tested in accordance with BS EN 1634-1 (with or without pre-fire test mechanical conditioning) that achieve the minimum performance in Table C1 will be deemed to satisfy the provisions.
C5
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: C5 (2029 amendment).
All fire doorsets, including to flat entrances and between a dwellinghouse and an integral garage, should be fitted with a self-closing device, except for all of the following.
C6
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: C6 (2029 amendment).
If a self-closing device would be considered to interfere with the normal approved use of the building, self-closing fire doors may be held open by one of the following.
C7
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: C7 (2029 amendment).
Two fire doorsets may be fitted in the same opening if each door is capable of closing the opening, so the total fire resistance is the sum of their individual resistances. If the opening is provided as a means of escape, both fire doorsets should be self-closing.
If one fire doorset is capable of being easily opened by hand and has a minimum of 30 minutes’ fire resistance, the other fire doorset should comply with both of the following.
C8
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: C8 (2029 amendment).
Fire doorsets often do not provide any significant insulation. Unless providing both integrity and insulation in accordance with Appendix B, Table B1, a maximum of 25% of the length of a compartment wall should consist of door openings.
Where it is practicable to maintain a clear space on both sides of the doorway, the above percentage may be greater.
C9
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: C9 (2029 amendment).
Rolling shutters should be capable of manual opening and closing for firefighting purposes (see Section 17). Rolling shutters across a means of escape should only be released by a heat sensor, such as a fusible link or electric heat detector, in the immediate vicinity of the door.
Unless a shutter is also intended to partially descend as part of a boundary to a smoke reservoir, shutters across a means of escape should not be closed by smoke detectors or a fire alarm system.
C10
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: C10 (2029 amendment).
Unless shown to be satisfactory when tested as part of a fire doorset assembly, the essential components of any hinge on which a fire door is hung should be made entirely from materials that have a minimum melting point of 800°C.
C11
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: C11 (2029 amendment).
Except for doorsets listed in paragraph C12, all fire doorsets should be marked with one of the following fire safety signs, complying with BS 5499-5, as appropriate.
All fire doorsets should be marked on both sides, except fire doorsets to cupboards and service ducts, which should be marked on the outside.
C12
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: C12 (2029 amendment).
The following fire doorsets are not required to comply with paragraph C11.
C13
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: C13 (2029 amendment).
The performance of some doorsets set out in Table C1 is linked to the minimum periods of fire resistance for elements of structure given in Tables B1 and B2. Limitations on the use of uninsulated glazing in fire doorsets are given in Table B3.
C14
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: C14 (2029 amendment).
Recommendations for the specification, design, construction, installation and maintenance of fire doorsets constructed with non-metallic door leaves are given in BS 8214.
Guidance on timber fire resisting doorsets, in relation to the new European test standard, may be found in Timber Fire Resisting Doorsets: Maintaining Performance Under the New European Test Standard published by the Timber Research and Development Association (TRADA).
Guidance for metal doors is given in Code of Practice for Fire Resisting Metal Doorsets published by the Door and Shutter Manufacturers’ Association (DSMA).
C15
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: C15 (2029 amendment).
Hardware used on fire doors can significantly affect their performance in a fire. Notwithstanding the guidance in this approved document, guidance is available in Hardware for Fire and Escape Doors published by the Door and Hardware Federation (DHF) and Guild of Architectural Ironmongers (GAI).
Table C1 Provisions for fire doorsets
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: Table C1 Provisions for fire doorsets (2029 amendment).
| Position of door | Minimum fire resistance of door in terms of integrity (minutes) when tested to the relevant European standard(1) | Minimum fire resistance of door in terms of integrity (minutes) when tested to BS 476-22 |
|---|---|---|
1. In a compartment wall separating buildings | Same as for the wall in which the door is fitted, but a minimum of 60 minutes | Same as for the wall in which the door is fitted, but a minimum of 60 minutes |
2. In a compartment wall: | ||
a. if it separates a flat from a space in common use | E 30 Sa(2) | FD 30 S(2) |
b. enclosing a protected shaft forming a stairway or an evacuation shaft wholly or partly above the adjoining ground in a building used for flats, other residential, assembly and recreation, or office purposes | E 30 Sa(2) | FD 30 S(2) |
c. enclosing a protected shaft forming a stairway or an evacuation shaft not described in (b) above | Half the period of fire resistance of the wall in which it is fitted, but 30 minutes minimum and with suffix Sa(2) | Half the period of fire resistance of the wall in which it is fitted, but 30 minutes minimum and with suffix S(2) |
d. enclosing a protected shaft forming a lift or service shaft | Half the period of fire resistance of the wall in which it is fitted, but 30 minutes minimum | Half the period of fire resistance of the wall in which it is fitted, but 30 minutes minimum |
e. not described in (a), (b), (c) or (d) above. | Same as for the wall in which it is fitted, but add Sa(2) if the door is used for progressive horizontal evacuation under the guidance to requirement B1 | Same as for the wall in which it is fitted, but add S(2) if the door is used for progressive horizontal evacuation under the guidance to requirement B1 |
3. In a compartment floor | Same as for the floor in which it is fitted | Same as for the floor in which it is fitted |
4. Forming part of the enclosures of: | ||
a. protected stairway or evacuation shaft (except as described in item 9 or 11(b) below) | E 30 Sa (2) | FD 30 S(2) |
b. a lift shaft (see paragraph 5.34(b) that does not form a protected shaft in 2(b), (c) or (d) above. | E 30 | FD 30 |
5. Forming part of the enclosure of: | ||
a. a protected lobby approach (or protected corridor) to a stairway or an evacuation shaft | E 30 Sa (2) | FD 30 S(2) |
b. any other protected corridor | E 20 Sa (2) | FD 20 S(2) |
c. a protected lobby approach to a lift shaft (paragraphs 5.37 to 5.39). | E 30 Sa (2) | FD 30 S(2) |
6. Giving access to an external escape route | E 30 | FD 30 |
7. Sub-dividing: | ||
a. corridors connecting alternative exits | E 20 Sa (2) | FD 20 S(2) |
b. dead-end portions of corridors from the remainder of the corridor. | E 20 Sa (2) | FD 20 S(2) |
8. Any door within a cavity barrier | E 30 | FD 30 |
9. Any door that forms part of the enclosure to a protected entrance hall or protected landing in a flat | E 20 | FD 20 |
10. Any door that forms part of the enclosure: | ||
a. to a place of special fire hazard | E 30 | FD 30 |
b. to ancillary accommodation in care homes (see paragraph 2.4). | E 30 | FD 30 |
11. In a dwellinghouse: | ||
a. between a dwellinghouse and a garage | E 30 Sa (2) | FD 30 S(2) |
b. forming part of the enclosures to a protected stairway in a single family dwellinghouse | E 20 | FD 20 |
c. within any fire resisting construction in a dwellinghouse not described elsewhere in this table. | E 20 | FD 20 |
NOTES:
Appendix C: Fire doorsets (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: Appendix C: Fire doorsets.
C1 (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: C1.
All fire doorsets should have the performance shown in Table C1, based on one of the following.
C2 (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: C2.
The performance requirement is in terms of integrity (E) for a period of minutes. An additional classification of Sa is used for all doors where restricted smoke leakage at ambient temperatures is needed.
C3 (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: C3.
The requirement is for test exposure from each side of the doorset separately. The exception is lift doors, which are tested from the landing side only.
C4 (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: C4.
Any test evidence used to verify the fire resistance rating of a doorset or shutter should be checked to ensure both of the following.