Fire detection and alarm systems 1.9

1.9

BS 5839-1 specifies three categories of system.

a. Category L – for the protection of life.
b. Category M – manual fire detection and alarm systems.
c. Category P – for property protection.

Category L systems are divided into the following.

L1 – systems installed throughout the protected building.

L2 – systems installed only in defined parts of the protected building (a category L2 system will normally include the coverage required of a category L3 system).

L3 – systems designed to warn of fire at an early enough stage to enable all occupants, other than possibly those in the room where the fire started, to escape safely before the escape routes become impassable because of fire, smoke or toxic gases.

L4 – systems installed within those parts of the escape routes that comprise circulation areas and circulation spaces, such as corridors and stairs.

L5 – systems in which the protected area(s) and/or the location of detectors are designed to satisfy a specific fire safety objective (other than that of a category L1, L2, L3 or L4 system).

Type P systems are divided into the following.

P1 – systems installed throughout the protected building.

P2 – systems installed only in defined parts of the protected building.

View this page on RegsUK