Appendix A: Key terms
Appendix A: Key terms
NOTE: Except for the items marked * (which are from the Building Regulations 2010), these definitions apply only to Approved Document B.
NOTE: The terms defined below are key terms used in this document only. Refer to BS 4422 for further guidance on the definitions of common terms used in the fire safety industry which are not listed below.
Access room A room that the only escape route from an inner room passes through.
Alternative escape routes Escape routes that are sufficiently separated by direction and space or by fire resisting construction to ensure that one is still available if the other is affected by fire.
NOTE: A second stair, balcony or flat roof which enables a person to reach a place free from danger from fire is considered an alternative escape route for the purposes of a dwellinghouse.
Alternative exit One of two or more exits, each of which is separate from the other.
Appliance ventilation duct A duct to deliver combustion air to a gas appliance.
Atrium (plural atria) A continuous space that passes through one or more structural floors within a building, not necessarily vertically.
NOTE: Enclosed lift wells, enclosed escalator wells, building services ducts and stairs are not classified as atria.
Automatic release mechanism A device that normally holds a door open, but closes it automatically if any one of the following occurs.
Basement storey A storey with a floor that, at some point, is more than 1200mm below the highest level of ground beside the outside walls. (However, see Appendix B, paragraph B26c, for situations where the storey is considered to be a basement only because of a sloping site.)
Boundary The boundary of the land that belongs to a building, or, where the land abuts a road, railway, canal or river, the centre line of that road, railway, canal or river.
*Building Any permanent or temporary building but not any other kind of structure or erection. A reference to a building includes a reference to part of a building.
Building control body A term that includes both local authority building control and approved inspectors.
Cavity A space enclosed by elements of a building (including a suspended ceiling) or contained within an element, but that is not a room, cupboard, circulation space, protected shaft, or space within a flue, chute, duct, pipe or conduit.
Cavity barrier A construction within a cavity, other than a smoke curtain, to perform either of the following functions.
Ceiling Part of a building that encloses a room, protected shaft or circulation space and is exposed overhead.
NOTE: The soffit of a rooflight, but not the frame, is included as part of the surface of the ceiling. An upstand below a rooflight is considered as a wall.
Circulation space A space (including a protected stairway) mainly used as a means of access between a room and an exit from the building or compartment.
Common balcony A walkway, open to the air on one or more sides, that forms part of the escape route from more than one flat.
Common stair An escape stair that serves more than one flat.
Compartment (fire) A building or part of a building, comprising one or more rooms, spaces or storeys, that is constructed to prevent the spread of fire to or from another part of the same building or an adjoining building.
NOTE: A roof space above the top storey of a compartment is included in that compartment. (See also ‘Separated part’.)
Compartment wall or floor A fire resisting wall or floor to separate one fire compartment from another.
NOTE: Provisions relating to construction are given in Section 8.
Corridor access A design of a building containing flats, in which each flat is approached via a common horizontal internal access or circulation space, which may include a common entrance hall.
Curtain Part of a solar shading device which is set in motion by the operating system and fulfils the purpose of a blind, awning or shutter.
Dead end An area from which escape is possible in one direction only.
Direct distance The shortest distance from any point within the floor area to the nearest storey exit, measured within the external enclosures of the building, and ignoring walls, partitions and fittings other than the enclosing walls and partitions to protected stairways.
*Dwelling Includes a dwellinghouse and a flat.
NOTE: A dwelling is a unit where one or more people live (whether or not as a sole or main residence) in either of the following situations.
*Dwellinghouse Does not include a flat or a building containing a flat.
Element of structure Any of the following.
NOTE: However, see the guidance to requirement B3, paragraph 7.3, for a list of structures that are not considered to be elements of structure.
Emergency lighting Lighting for use when the power supply to the normal lighting fails.
Escape lighting The part of the emergency lighting that is provided to ensure that the escape route is illuminated at all material times.
Escape route The route along which people can escape from any point in a building to a final exit.
Evacuation lift A lift that may be used to evacuate people in a fire.
Evacuation lift lobby An area protected from fire and smoke ingress by fire resisting construction and smoke control measures, providing direct access to an evacuation lift, where a person can wait for a lift service in relative safety while an evacuation is underway.
Evacuation shaft A protected shaft containing a protected stairway, an evacuation lift (together with its machine room) and evacuation lift lobbies.
Exit passageway A protected passageway that connects a protected stairway to a final exit.
NOTE: Exit passageways should be protected to the same standard as the stairway they serve.
*External wall The external wall of a building includes all of the following.
Final exit The end of an escape route from a building that gives direct access to a street, passageway, walkway or open space, and is sited to ensure that people rapidly disperse away from the building so that they are no longer in danger from fire and/or smoke.
NOTE: Windows are not acceptable as final exits.
Fire alarm system Combination of components for giving an audible and/or other perceptible warning of fire.
Fire damper A mechanical or intumescent device within a duct or ventilation opening that operates automatically and is designed to resist the spread of fire.
Fire and smoke damper A fire damper which, in addition to the performance of the fire damper, resists the spread of smoke.
Fire doorset A door or shutter which, together with its frame and furniture as installed in a building, is intended (when closed) to resist the spread of fire and/or gaseous products of combustion and meets specified performance criteria to those ends.
NOTE: A fire doorset may have one or more leaves. The term includes a cover or other form of protection to an opening in a fire resisting wall or floor, or in a structure that surrounds a protected shaft. A fire doorset is a complete door assembly, assembled on site or delivered as a completed assembly, consisting of the door frame, leaf or
leaves, essential hardware, edge seals and glazing, and any integral side panels or fanlight panels in an associated door screen.
Firefighting lift A lift with additional protection and with controls that enable it to be used by the fire and rescue service when fighting a fire. (See Section 17.)
Firefighting lobby A protected lobby that provides access from a firefighting stair to the accommodation area and to any associated firefighting lift.
Firefighting shaft A protected enclosure that contains a firefighting stair, firefighting lobbies and, if provided, a firefighting lift together with its machine room.
Firefighting stair A protected stairway that connects to the accommodation area through only a firefighting lobby.
Fire resisting (Fire resistance) The ability of a component or a building to satisfy, for a stated period of time, some or all of the appropriate criteria given in the relevant standard.
Fire-separating element A compartment wall, compartment floor, cavity barrier and construction that encloses a protected escape route and/or a place of special fire hazard.
Fire-stop (Fire-stopping) A seal provided to close an imperfection of fit or design tolerance between elements or components, to restrict the spread of fire and smoke.
*Flat A flat is a separate and self-contained premises constructed or adapted for use for residential purposes and forming part of a building from some other part of which it is divided horizontally.
Gallery A floor or balcony that does not extend across the full extent of a building’s footprint and is open to the floor below.
Habitable room A room used, or intended to be used, for people to live in (including, for the purposes of Approved Document B Volumes 1 and 2, a kitchen, but not a bathroom).
Height (of a building or storey for the purposes of Approved Document B Volumes 1 and 2)
Inner room Room from which escape is possible only by passing through another room (the access room).
Interlocked stair Two interlocking protected stairways providing two separate paths of egress within one protected shaft or separated protected shafts. These are also sometimes referred to as scissor stairs or stacked stairs.
Live/work unit A flat that is a workplace for people who live there, its occupants, and for people who do not live on the premises.
Means of escape Structural means that provide one or more safe routes for people to go, during a fire, from any point in the building to a place of safety.
Measurement
Notional boundary A boundary presumed to exist between two buildings on the same site.
Open spatial planning The internal arrangement of a building in which more than one storey or level is contained in one undivided volume, e.g. split-level floors. For the purposes of this document there is a distinction between open spatial planning and an atrium space.
Perimeter (of a building) The maximum aggregate plan perimeter, found by vertical projection onto a horizontal plane. (See Section 15.)
Pipe Includes pipe fittings and accessories. The definition of ‘pipe’ excludes a flue pipe and a pipe used for ventilating purposes, other than a ventilating pipe for an above-ground drainage system.
Place of special fire hazard A room such as any of the following.
Platform floor (also called an access or raised floor) A floor that is supported by a structural floor, but with an intervening cavity to house services.
Protected circuit An electrical circuit that is protected against fire.
Protected corridor/lobby A corridor or lobby that is adequately protected from fire in adjoining areas by fire resisting construction.
Protected entrance hall/landing A circulation area, consisting of a hall or space in a flat, that is enclosed with fire resisting construction other than an external wall of a building.
Protected shaft A shaft that enables people, air or objects to pass from one compartment to another, and which is enclosed with fire resisting construction.
Protected stairway A stair that leads to a final exit to a place of safety and that is adequately enclosed with fire resisting construction. Included in the definition is any exit passageway between the foot of the stair and the final exit.
Purpose group A classification of a building according to the purpose to which it is intended to be put. (See Table 0.1.)
Relevant boundary The boundary or notional boundary that one side of the building faces and/ or coincides with, and that is parallel or at an angle of a maximum of 80 degrees to that side of the building.
Rooflight A dome light, lantern light, skylight, ridge light, glazed barrel vault or other element to admit daylight through a roof.
Room An enclosed space within a building that is not used solely as a circulation space. The term includes not only conventional rooms, but also cupboards that are not fittings and large spaces such as warehouses and auditoria. The term does not include cavities such as ducts, ceiling cavities and roof spaces.
School A place of education for children between 2 and 19 years old. The term includes nursery schools, primary schools and secondary schools as defined in the Education Act 1996.
Self-closing device A device that closes a door, when open at any angle, against a door frame.
NOTE: If the door is in a cavity barrier, rising butt hinges (which are different from the self-closing device mentioned above) are acceptable.
Separated part (of a building) Part of a building that is separated from another part of the same building by a compartment wall. The wall runs the full height of the part and is in one vertical plane. (See Appendix D, Diagram D5.)
Sheltered housing Includes two or more dwellings in the same building or on adjacent sites, designed and constructed as residential accommodation for vulnerable or elderly people who receive, or will receive, a support service.
Single storey building A building that consists of a ground storey only. Basements are not counted as storeys in a building (see Appendix D). A separated part that consists of a ground storey only, with a roof to which access is only provided for repair or maintenance, may be treated as a single storey building.
Site (of a building) The land occupied by the building, up to the boundaries with land in other ownership.
*Solar shading device A device attached to the external surface of an external wall for reducing heat gain within a building by shading or deflecting sunlight.
*Specified attachment Includes any of the following.
Storey Includes any of the following.
NOTE: The building is regarded as a multi-storey building if both of the following apply.
Storey exit A final exit, or a doorway that gives direct access into a protected stairway, evacuation lift lobby within an evacuation shaft, firefighting lobby or external escape route.
NOTE: If an institutional building is planned to enable progressive horizontal evacuation, a door in a compartment wall is considered a storey exit for the purposes of requirement B1.
Suspended ceiling (fire-protecting) A ceiling suspended below a floor that adds to the fire resistance of the floor.
Thermoplastic material Any synthetic polymeric material that has a softening point below 200°C if tested to BS EN ISO 306 Method A120. Specimens for this test may be fabricated from the original polymer where the thickness of material of the end product is less than 2.5mm.
Travel distance (unless otherwise specified, e.g. as in the case of flats) The distance that a person would travel from any point within the floor area to the nearest storey exit, determined by the layout of walls, partitions and fittings.
Unprotected area (in relation to a side or external wall of a building) All of the following are classed as unprotected areas.
NOTE: Recessed car parking areas as shown in Diagram A1 should not be regarded as unprotected areas.
Diagram A1 Recessed car parking areas