Section 6: Wall and ceiling linings Classification of linings
Classification of linings
6.1
The surface linings of walls and ceilings should meet the classifications in Table 6.1.
Table 6.1 Classification of linings
| Location | Classification |
|---|---|
Small rooms of maximum internal floor area: a. 4m2 in residential accommodation b. 30m2 in non-residential accommodation | D-s3, d2 |
| Other rooms (including garages) | C-s3, d2 |
| Other circulation spaces | B-s3, d2(1) |
NOTE:
Walls
6.2
For the purposes of this requirement, a wall includes both of the following.
6.3
For the purposes of this requirement, a wall does not include any of the following.
6.4
Parts of walls in rooms may be of lower performance than stated in Table 6.1, but no worse than class D-s3, d2. In any one room, the total area of lower performance wall lining should be less than an area equivalent to half of the room’s floor area, up to a maximum of:
Ceilings
6.5
For the purposes of this requirement, a ceiling includes all of the following.
6.6
For the purposes of this requirement, a ceiling does not include any of the following.
Fire resisting ceilings
6.7
The need for cavity barriers in concealed floor or roof spaces can be reduced by installing a fire resisting ceiling (minimum EI 30) below the cavity, complying with Diagram 9.3.
Rooflights
6.8
Rooflights should meet the following classifications, according to material. No guidance for European fire test performance is currently available, because there is no generally accepted test and classification procedure.
Special applications
6.9
Any flexible membrane covering a structure, other than an air-supported structure, should comply with Appendix A of BS 7157.
6.10
Guidance on the use of PTFE-based materials for tension-membrane roofs and structures is given in BRE report BR 274.
Fire behaviour of insulating core panels used internally
6.11
Insulating core panels consist of an inner core of insulation sandwiched between, and bonded to, a membrane, such as galvanised steel or aluminium.
Where they are used internally they can present particular problems with regard to fire spread, and should meet all of the following conditions.
Other controls on internal surface properties
6.12
Guidance on the control of flame spread is given in the following sections.