Section 6: Wall and ceiling linings Classification of linings

Classification of linings

6.1

The surface linings of walls and ceilings should meet the classifications in Table 6.1.

Table 6.1 Classification of linings

LocationClassification

Small rooms of maximum internal floor area:

a. 4m2 in residential accommodation
b. 30m2 in non-residential accommodation
D-s3, d2
Other rooms (including garages)C-s3, d2
Other circulation spacesB-s3, d2(1)

NOTE:

1. Wallcoverings which conform to BS EN 15102, achieving at least class C-s3, d2 and bonded to a class A2-s3, d2 substrate, will also be acceptable.

Walls

6.2

For the purposes of this requirement, a wall includes both of the following.

a. The internal surface of internal and external glazing (except glazing in doors).
b. Any part of a ceiling which slopes at an angle greater than 70 degrees to the horizontal.

6.3

For the purposes of this requirement, a wall does not include any of the following.

a. Doors and door frames.
b. Window frames and frames in which glazing is fitted.
c. Architraves, cover moulds, picture rails, skirtings and similar narrow members.
d. Fireplace surrounds, mantle shelves and fitted furniture.

6.4

Parts of walls in rooms may be of lower performance than stated in Table 6.1, but no worse than class D-s3, d2. In any one room, the total area of lower performance wall lining should be less than an area equivalent to half of the room’s floor area, up to a maximum of:

a. 20m2 in residential accommodation.
b. 60m2 in non-residential accommodation.

Ceilings

6.5

For the purposes of this requirement, a ceiling includes all of the following.

a. Glazed surfaces.
b. Any part of a wall at 70 degrees or less to the horizontal.
c. The underside of a gallery.
d. The underside of a roof exposed to the room below.

6.6

For the purposes of this requirement, a ceiling does not include any of the following.

a. Trap doors and their frames.
b. The frames of windows or rooflights and frames in which glazing is fitted.
c. Architraves, cover moulds, picture rails, exposed beams and similar narrow members.

Fire resisting ceilings

6.7

The need for cavity barriers in concealed floor or roof spaces can be reduced by installing a fire resisting ceiling (minimum EI 30) below the cavity, complying with Diagram 9.3.

Rooflights

6.8

Rooflights should meet the following classifications, according to material. No guidance for European fire test performance is currently available, because there is no generally accepted test and classification procedure.

a. Non-plastic rooflights should meet the relevant classification in Table 6.1.
b. Plastic rooflights, if the limitations in Table 6.2 and Table 14.2 are observed, should be a minimum class D-s3, d2 rating. Otherwise they should meet the relevant classification in Table 6.1.

Special applications

6.9

Any flexible membrane covering a structure, other than an air-supported structure, should comply with Appendix A of BS 7157.

6.10

Guidance on the use of PTFE-based materials for tension-membrane roofs and structures is given in BRE report BR 274.

Fire behaviour of insulating core panels used internally

6.11

Insulating core panels consist of an inner core of insulation sandwiched between, and bonded to, a membrane, such as galvanised steel or aluminium.

Where they are used internally they can present particular problems with regard to fire spread, and should meet all of the following conditions.

a. Panels should be sealed to prevent exposure of the core to a fire. This includes at joints and where services penetrate the panel.
b. In high fire risk areas, such as kitchens, places of special fire hazard, or in proximity to where hot works occur, only class A1 cored panels should be used.
c. Fixing systems for all panels should be designed to take account of the potential for the panel to delaminate. For instance, where panels are used to form a suspended ceiling, the fixing should pass through the panel and support it from the lower face.

Other controls on internal surface properties

6.12

Guidance on the control of flame spread is given in the following sections.

a. Stairs and landings: Section 3 (escape stairs) and Section 17 (firefighting shafts).
b. Section 9: exposed surfaces above fire-protecting suspended ceilings.