Section 18: Venting of heat and smoke from basements Construction of outlet ducts or shafts
Construction of outlet ducts or shafts
18.13
Outlet ducts or shafts, including any bulkheads over them (see Diagram 18.1), should be enclosed in construction of class A1 rating and fire resistance at least equal to that of the element through which they pass.
18.14
Natural smoke outlet shafts should be separated from each other using construction of class A1 rating and fire resistance at least equal to that of the storeys they serve, where the shafts are either of the following.
a. From different compartments of the same basement storey.
b. From different basement storeys.