Section 16: Fire mains and hydrants Design and construction of fire mains

Design and construction of fire mains

16.4

If a firefighting shaft is provided, outlets from fire mains should be within the protected stairway or protected lobby (see Diagram 17.1).

16.5

Guidance on the design and construction of fire mains is given in BS 9990.

16.6

Buildings with a storey more than 50m above fire service vehicle access level should be provided with wet fire mains. In all other buildings where fire mains are provided, either wet or dry fire mains are suitable.

16.7

Fire service vehicle access to fire mains should be provided as described in paragraphs 15.4 and 15.5.