Requirement B4: External fire spread
Requirement B4: External fire spread
These sections deal with the following requirement from Part B of Schedule 1 to the Building Regulations 2010. Section 12 also refers to regulation 7(2) of the Building Regulations 2010. Guidance on regulation 7(1) can be found in Approved Document 7.
Requirement
| Requirement | Limits on application |
|---|---|
External fire spread B4. (1) The external walls of the building shall adequately resist the spread of fire over the walls and from one building to another having regard to the height, use and position of the building. (2) The roof of the building shall adequately resist the spread of fire over the roof and from one building to another, having regard to the use and position of the building. |
Regulation
Regulation 7 – Materials and workmanship
(1) Building work shall be carried out—
(1A) Building work shall be carried out so that relevant metal composite material does not become part of an external wall, or specified attachment, of any building.
(2) Subject to paragraph (3), building work shall be carried out so that materials which become part of an external wall, or specified attachment, of a relevant building are of European Classification A2-s1, d0 or A1 (classified in accordance with the reaction to fire classification).
(3) Paragraph (2) does not apply to—
(4) In this regulation—
Intention
Resisting fire spread over external walls
The external envelope of a building should not contribute to undue fire spread from one part of a building to another part. This intention can be met by constructing external walls so that both of the following are satisfied.
The extent to which this is necessary depends on the height and use of the building.
Resisting fire spread from one building to another
The external envelope of a building should not provide a medium for undue fire spread to adjacent buildings or be readily ignited by fires in adjacent buildings. This intention can be met by constructing external walls so that all of the following are satisfied.
The extent to which this is necessary depends on the use of the building and its position in relation to adjacent buildings and therefore the site boundary.