Thermoplastic materials Suspended or stretched-skin ceilings
Suspended or stretched-skin ceilings
6.18
A ceiling constructed from TP(a) flexible panels should meet the following conditions.
a. Have a maximum area of 5m2.
b. Be supported on all sides.
Diagram 6.2 Layout restrictions on class D-s3, d2 plastic rooflights, TP(b) rooflights and TP(b) lighting diffusers

Table 6.2 Limitations applied to thermoplastic rooflights and lighting diffusers in suspended ceilings and class D-s3, d2 plastic rooflights(1)
| Minimum classification of lower surface | Use of space below the diffusers or rooflight | Maximum area of each diffuser or rooflight(2) (m2) | Maximum total area of diffusers and rooflights as a percentage of floor area of the space in which the ceiling is located (%) | Minimum separation distance between diffusers or rooflights(2) (m) |
|---|---|---|---|---|
| TP(a) | Any except protected stairway | No limit(3) | No limit | No limit |
| D-s3, d2(4) or TP(b) | Rooms | 1 | 50(5)(6) | A distance equal to the largest plan dimension of the largest diffuser or rooflight (see Diagram 6.3) |
| 5 | 50(5)(6) | 3(6) | ||
| Circulation spaces except protected stairways | 5 | 15(5) | 3 |
NOTES:
1. This table does not apply to products that meet the provisions in Table 6.1.
2. Smaller rooflights and diffusers can be grouped together provided that both of the following satisfy the dimensions in Diagram 6.2 or 6.3.
a. The overall size of the group.
b. The space between one group and any others.
3. Lighting diffusers of TP(a) flexible rating should be used only in panels of a maximum of 5m2 each. See paragraph 6.18.
4. There are no limits on the use of class D-s3, d2 materials in small rooms. See Table 6.1.
5. The minimum 3m separation given in Diagram 6.2 between each 5m2 group must be maintained. Therefore, in some cases, it may not be possible to use the maximum percentage quoted.
6. Class D-s3, d2 rooflights to rooms in industrial and other non-residential purpose group buildings (purpose groups 3 to 7) may be spaced 1800mm apart provided both of the following conditions are met.
a. The rooflights are evenly distributed.
b. The total area of the rooflights does not exceed 20% of the area of the room.
Diagram 6.3 Layout restrictions on small class D-s3, d2 plastic rooflights, TP(b) rooflights and TP(b) lighting diffusers
