Thermoplastic materials Suspended or stretched-skin ceilings

Suspended or stretched-skin ceilings

6.18

A ceiling constructed from TP(a) flexible panels should meet the following conditions.

a. Have a maximum area of 5m2.
b. Be supported on all sides.

Diagram 6.2 Layout restrictions on class D-s3, d2 plastic rooflights, TP(b) rooflights and TP(b) lighting diffusers

Diagram 6.2 Layout restrictions on class D-s3, d2 plastic rooflights, TP(b) rooflights and TP(b) lighting diffusers. Wording on the drawing: See para 6.17; 5m maximum dimension of group 5m maximum dimension of group; 3m min.; 5m maximum dimension of group 3m min.; 5m max.; 5m² is maximum area of di˜user and rooflight in; any one 5m˜5m group; 5m maximum dimension of group; Rooflight or di˜user; NOTES:; Upper and lower surfaces of suspended ceiling, between plastic panels, to comply with paragraph 6.1.; 1.; Separated groups of rooflights or di˜users; 2.; No restriction on class D-s3, d2 di˜users or rooflights in small rooms.; 3.; See note 4 to Table 6.2.
Diagram 6.2 Layout restrictions on class D-s3, d2 plastic rooflights, TP(b) rooflights and TP(b) lighting diffusers

Table 6.2 Limitations applied to thermoplastic rooflights and lighting diffusers in suspended ceilings and class D-s3, d2 plastic rooflights(1)

Minimum classification of lower surfaceUse of space below the diffusers or rooflightMaximum area of each diffuser or rooflight(2) (m2)Maximum total area of diffusers and rooflights as a percentage of floor area of the space in which the ceiling is located (%)Minimum separation distance between diffusers or rooflights(2) (m)
TP(a)Any except protected stairwayNo limit(3) No limitNo limit
D-s3, d2(4) or TP(b)Rooms150(5)(6) A distance equal to the largest plan dimension of the largest diffuser or rooflight (see Diagram 6.3)
550(5)(6) 3(6)
Circulation spaces except protected stairways515(5) 3

NOTES:

1. This table does not apply to products that meet the provisions in Table 6.1.
2. Smaller rooflights and diffusers can be grouped together provided that both of the following satisfy the dimensions in Diagram 6.2 or 6.3.
a. The overall size of the group.
b. The space between one group and any others.
3. Lighting diffusers of TP(a) flexible rating should be used only in panels of a maximum of 5m2 each. See paragraph 6.18.
4. There are no limits on the use of class D-s3, d2 materials in small rooms. See Table 6.1.
5. The minimum 3m separation given in Diagram 6.2 between each 5m2 group must be maintained. Therefore, in some cases, it may not be possible to use the maximum percentage quoted.
6. Class D-s3, d2 rooflights to rooms in industrial and other non-residential purpose group buildings (purpose groups 3 to 7) may be spaced 1800mm apart provided both of the following conditions are met.
a. The rooflights are evenly distributed.
b. The total area of the rooflights does not exceed 20% of the area of the room.

Diagram 6.3 Layout restrictions on small class D-s3, d2 plastic rooflights, TP(b) rooflights and TP(b) lighting diffusers

Diagram 6.3 Layout restrictions on small class D-s3, d2 plastic rooflights, TP(b) rooflights and TP(b) lighting diffusers. Wording on the drawing: See Table 6.2; dimension x; x min.; y min.; x min. y min.; dimension x; dimension y; Ceiling plan; Materials within this zone – at plane of ceiling – should comply with Table 6.1; Rooflights
Diagram 6.3 Layout restrictions on small class D-s3, d2 plastic rooflights, TP(b) rooflights and TP(b) lighting diffusers