Section 5: Walls Cavity external walls

Cavity external walls

5.12

Any external cavity wall will meet the requirement if the outer leaf is separated from the inner leaf by a drained air space, or in any other way which will prevent precipitation from being carried to the inner leaf.

Technical solution

5.13

The construction of a cavity external wall could include:

a. outer leaf masonry (bricks, blocks, stone or manufactured stone); and
b. cavity at least 50mm wide. The cavity is to be bridged only by wall ties, cavity trays provided to prevent moisture being carried to the inner leaf (see paragraph 5.15 for cavity insulation), and cavity barriers, firestops and cavity closures, where appropriate; and
c. inner leaf masonry or frame with lining.

Masonry units should be laid on a full bed of mortar with the cross joints substantially and continuously filled to ensure structural robustness and weather resistance.

Where a cavity is to be partially filled, the residual cavity should not be less than 50mm wide (see Diagram 11).

Alternative approach

5.14

The requirement can also be met by following the relevant recommendations of BS 5628-3:2001108. The code describes factors affecting rain penetration of cavity walls.