Section 6: Roofs Roofs (resistance to damage from interstitial condensation)
Roofs (resistance to damage from interstitial condensation)
6.10
A roof will meet the requirement if it is designed and constructed in accordance with Clause 8.4 of BS 5250:2002141 and BS EN ISO 13788:2002142. Further guidance is given in the BRE Report BR 262143.
6.11
The requirement will be met by the ventilation of cold deck roofs, i.e. those roofs where the moisture from the building can permeate the insulation. For the purposes of health and safety it may not always be necessary to provide ventilation to small roofs such as those over porches and bay windows. Although a part of a roof which has a pitch of 70° or more is to be insulated as though it were a wall, the provisions in this document apply to roofs of any pitch.
6.12
To avoid excessive moisture transfer to roof voids gaps and penetrations for pipes and electrical wiring should be filled and sealed; this is particularly important in areas of high humidity, e.g. bathrooms and kitchens. An effective draught seal should be provided to loft hatches to reduce inflow of warm air and moisture.
6.13
Because of the high internal temperatures and humidities, there is a particular risk of interstitial condensation in the roofs of swimming pools and other buildings in which high levels of moisture are generated; specialist advice should be sought when these are being designed.