Ground supported floors (moisture from the ground) Technical solution

Technical solution

4.7

Unless it is subjected to water pressure, which is likely in the case of buildings on very permeable strata such as chalk, limestone or gravel (in which case see Alternative approach, paragraph 4.12), a concrete ground supported floor may be built as follows (Diagram 4):

a. well compacted hardcore bed, no greater than 600mm deep82, of clean, broken brick or similar inert material, free from materials including water-soluble sulphates in quantities which could damage the concrete (BRE Digest 27683; and
b. concrete at least 100mm thick (but thicker if the structural design requires) to mix ST2 in BS 8500 or, if there is embedded reinforcement, to mix ST4 in BS 850084; and
c. damp-proof membrane above or below the concrete, and continuous with the damp-proof courses in walls, piers and the like. If the ground could contain water soluble sulphates, or there is any risk that sulphate or other deleterious matter could contaminate the hardcore, the membrane should be placed at the base of the concrete slab85.

75 BRE Report BR 211 Radon: Guidance on protective measures for new buildings (including supplementary advice for extensions, conversions and refurbishment), 2007.

80 BRE/Environment Agency Report BR 414 Protective measures for housing on gas-contaminated land, 2001.

82 If the hardcore bed is deeper than 600mm, there may be a risk of excessive settlement and cracking of the floor slab. In such cases, a suspended floor slab is advised.

83 BRE Digest 276 Hardcore, 1992.

84 BS 8500-1:2002 Concrete. Complementary British Standard to BS EN 206-1 Method of specifying and guidance for the specifier.

85 BRE Special Digest SD1 Concrete in aggressive ground, 2003.

Diagram 4 Ground supported floor – construction (see paragraph 4.7)

Diagram 4 Ground supported floor – construction (see paragraph 4.7).
Diagram 4 Ground supported floor – construction (see paragraph 4.7)

4.8

A membrane below the concrete could be formed with a sheet of polyethylene, which should be at least 300µm thick (1200 gauge) with sealed joints and laid on a bed of material that will not damage the sheet.

4.9

A membrane laid above the concrete may be either polyethylene sheet as described above (but without the bedding material) or three coats of cold applied bitumen solution or similar moisture and water vapour resisting material. In each case it should be protected by either a screed or a floor finish, unless the membrane is pitchmastic or similar material which will also serve as a floor finish.

4.10

Insulants placed beneath floor slabs should have sufficient strength to resist the weight of the slab and the anticipated floor loading as well as any possible overloading during construction. In order to resist degradation insulation that is placed below the damp proof membrane should have low water absorption. If necessary the insulant should be resistant to contaminants in the ground.

4.11

A timber floor finish laid directly on concrete may be bedded in a material which may also serve as a damp-proof membrane. Timber fillets laid in the concrete as a fixing for a floor finish should be treated with an effective preservative unless they are above the damp-proof membrane. Some preservative treatments are described in BS 1282:199986.