Section 4: Floors
Section 4: Floors
4.1
This section gives guidance for five situations:
4.2
Floors next to the ground should:
4.3
Consideration should be given to whether 4.2(a) need apply to a building used wholly for:
4.4
Floors next to the ground and floors exposed from below should be designed and constructed so that their structural and thermal performance are not adversely affected by interstitial condensation.
4.5
All floors should not promote surface condensation or mould growth, given reasonable occupancy conditions.
Ground supported floors (moisture from the ground)
4.6
Any ground supported floor will meet the requirement if the ground is covered with dense concrete laid on a hardcore bed and a damp-proof membrane is provided. Suitable insulation may be incorporated.
Technical solution
4.7
Unless it is subjected to water pressure, which is likely in the case of buildings on very permeable strata such as chalk, limestone or gravel (in which case see Alternative approach, paragraph 4.12), a concrete ground supported floor may be built as follows (Diagram 4):
75 BRE Report BR 211 Radon: Guidance on protective measures for new buildings (including supplementary advice for extensions, conversions and refurbishment), 2007.
80 BRE/Environment Agency Report BR 414 Protective measures for housing on gas-contaminated land, 2001.
82 If the hardcore bed is deeper than 600mm, there may be a risk of excessive settlement and cracking of the floor slab. In such cases, a suspended floor slab is advised.
83 BRE Digest 276 Hardcore, 1992.
84 BS 8500-1:2002 Concrete. Complementary British Standard to BS EN 206-1 Method of specifying and guidance for the specifier.
85 BRE Special Digest SD1 Concrete in aggressive ground, 2003.
Diagram 4 Ground supported floor – construction (see paragraph 4.7)

4.8
A membrane below the concrete could be formed with a sheet of polyethylene, which should be at least 300µm thick (1200 gauge) with sealed joints and laid on a bed of material that will not damage the sheet.
4.9
A membrane laid above the concrete may be either polyethylene sheet as described above (but without the bedding material) or three coats of cold applied bitumen solution or similar moisture and water vapour resisting material. In each case it should be protected by either a screed or a floor finish, unless the membrane is pitchmastic or similar material which will also serve as a floor finish.
4.10
Insulants placed beneath floor slabs should have sufficient strength to resist the weight of the slab and the anticipated floor loading as well as any possible overloading during construction. In order to resist degradation insulation that is placed below the damp proof membrane should have low water absorption. If necessary the insulant should be resistant to contaminants in the ground.
4.11
A timber floor finish laid directly on concrete may be bedded in a material which may also serve as a damp-proof membrane. Timber fillets laid in the concrete as a fixing for a floor finish should be treated with an effective preservative unless they are above the damp-proof membrane. Some preservative treatments are described in BS 1282:199986.
Alternative approach
4.12
The requirement can also be achieved by following the relevant recommendations of Clause 11 of BS CP 102:197387. BS 8102:199088 includes recommendations for floors subject to water pressure.
Suspended timber ground floors (moisture from the ground)
4.13
Any suspended timber floor next to the ground will meet the requirement if:
86 BS 1282:1999 Wood preservatives. Guidance on choice, use and application.
87 BS CP 102:1973 Protection of buildings against water from the ground.
88 BS 8102:1990 Code of practice for protection of structures against water from the ground.
Technical solution
4.14
Unless it is covered with a floor finish which is highly vapour resistant (in which case see the Alternative approach in paragraph 4.16), a suspended timber floor next to the ground may be built as follows (Diagram 5):
To prevent water collecting on the ground covering, either the top should be entirely above the highest level of the adjoining ground or, on sloping sites, consideration should be given to installing drainage on the outside of the up-slope side of the building (see Diagram 6).
89 BS 8500-1:2002 Concrete. Complementary British Standard to BS EN 206-1 Method of specifying and guidance for the specifier.
Diagram 5 Suspended timber floor – construction (see paragraph 4.14(a) (i))

Diagram 6 Suspended floor – preventing water collection (see paragraph 4.14(a))

4.15
In areas such as kitchens, utility rooms and bathrooms where water may be spilled, any board used as a flooring, irrespective of the storey, should be moisture resistant. In the case of chipboard it should be of one of the grades with improved moisture resistance specified in BS 7331:199091 or BS EN 312 Part 5:199792. It should be laid, fixed and jointed in the manner recommended by the manufacturer. To demonstrate compliance the identification marks should be facing upwards. Any softwood boarding should be at least 20mm thick and from a durable species93 or treated with a suitable preservative.
Alternative approach
4.16
The requirement can also be met (see paragraph 4.14 above) by following the relevant recommendations of Clause 11 of BS CP 102:197394.
Suspended concrete ground floors (moisture from the ground)
4.17
Any suspended floor of in situ or precast concrete, including beam and block floors, next to the ground will meet the requirement if it will adequately prevent the passage of moisture to the upper surface and if the reinforcement is protected against moisture.
Technical solution
4.18
One solution for a suspended concrete floor could be:
4.19
A suspended concrete floor will meet the requirements if it incorporates:
4.20
In localities where flooding is likely, consideration may be given to including means of inspecting and clearing out the sub-floor voids beneath suspended floors. For guidance, see Improving the flood performance of new buildings – Flood resilient construction8.
8 Improving the flood performance of new buildings – Flood resilient construction, Communities and Local Government, Defra and the Environment Agency, 2007.
90 BS 5628-3:2001 Code of practice for use of masonry. Materials and components, design and workmanship.
91 BS 7331:1990 Specification for direct surfaced wood chipboard based on thermosetting resins.
92 BS EN 312-5:1997 Particleboards. Specifications. Requirements for load-bearing boards for use in humid conditions.
93 BRE Digest 429 Timbers: their natural durability and resistance to preservative treatment, 1998.
94 BS CP 102:1973 Protection of buildings against water from the ground.
Diagram 7 Typical floors exposed from below

Ground floors and floors exposed from below (resistance to damage from interstitial condensation)
4.21
A ground floor or floor exposed from below, i.e. above an open parking space or passageway, as shown in Diagram 7, will meet the requirement if it is designed and constructed in accordance with Clause 8.5 and Appendix D of BS 5250:200296, BS EN ISO 13788:200297 and BR 26298.
Floors (resistance to surface condensation and mould growth)
4.22
A floor will meet the requirement if:
96 BS 5250:2002 Code of practice for the control of condensation in buildings.
97 BS EN ISO 13788:2002 Hygrothermal performance of building components and building elements. Internal surface temperature to avoid critical surface humidity and interstitial condensation. Calculation methods.
98 BRE Report BR 262 Thermal insulation: avoiding risks, 2002.
99 Accredited Construction Details which can be downloaded from www.planningportal.gov.uk/buildingregulations/approveddocuments/partl/bcassociateddocuments9/acd.
100 BRE Information Paper IP17/01 Assessing the effects of thermal bridging at junctions and around openings, 2001.