Section 3: Ensuring the overheating mitigation strategy is usable Protection from falling
Protection from falling
3.8
Openings which are intended to be open for long periods to reduce overheating risk might pose a higher risk of falls from height. Only the proportion of openings which can be opened with a very low risk of occupants falling from height should be considered to form part of the overheating mitigation strategy.
3.9
Openings that can be opened wider than 100mm may form part of the overheating mitigation strategy where they meet all of the following conditions.
a. Window handles on windows that open outwards are not more than 650mm from the inside face of the wall when the window is at its maximum openable angle.
b. Guarding meets the minimum standards in Table 3.1.
c. Guarding does not allow children to easily climb it. For example, horizontal bars should generally be avoided.
NOTE: To ensure safe operation it may be necessary to reduce the size of the outward opening windows and provide more windows to meet the required free area.
Table 3.1 Guarding heights
| Change in floor level between inside and outside | Guarding height(1) |
|---|---|
| Less than 600mm | See Approved Document K |
| More than 600mm | 1.1m![]() |
NOTES:
1. This approved document has increased levels of protection from falling compared to Approved Document K. Where applicable, the higher standard applies.
2. Guarding should be sized to prevent the passage of a 100mm sphere.
3.10
Guarding for large openings could include, but is not limited to, either of the following.
a. Shutters with a child-proof lock.
b. Fixed guarding.