Section 3: Ensuring the overheating mitigation strategy is usable Protection from falling

Protection from falling

3.8

Openings which are intended to be open for long periods to reduce overheating risk might pose a higher risk of falls from height. Only the proportion of openings which can be opened with a very low risk of occupants falling from height should be considered to form part of the overheating mitigation strategy.

3.9

Openings that can be opened wider than 100mm may form part of the overheating mitigation strategy where they meet all of the following conditions.

a. Window handles on windows that open outwards are not more than 650mm from the inside face of the wall when the window is at its maximum openable angle.
b. Guarding meets the minimum standards in Table 3.1.
c. Guarding does not allow children to easily climb it. For example, horizontal bars should generally be avoided.

NOTE: To ensure safe operation it may be necessary to reduce the size of the outward opening windows and provide more windows to meet the required free area.

Table 3.1 Guarding heights

Change in floor level between inside and outsideGuarding height(1)
Less than 600mmSee Approved Document K
More than 600mm1.1mDrawing for Table 3.1: sections through two windows that open outwards. One shows a height of 1.1m from the floor to the top of the guarding; the other shows a gap of less than 100mm between the guarding and the opening.

NOTES:

1. This approved document has increased levels of protection from falling compared to Approved Document K. Where applicable, the higher standard applies.
2. Guarding should be sized to prevent the passage of a 100mm sphere.

3.10

Guarding for large openings could include, but is not limited to, either of the following.

a. Shutters with a child-proof lock.
b. Fixed guarding.