Approved Document O: Overheating
Review requirements to limit unwanted solar gains and provide adequate means of removing excess heat in UK buildings. Ensure Part O compliance.
Title page
The Building Regulations 2010
Overheating
APPROVED DOCUMENT O
2021 edition – for use in England
2021 edition
This approved document supports Part O of Schedule 1 to the Building Regulations 2010.
This approved document takes effect on 15 June 2022 for use in England. It does not apply to work subject to a building notice, full plans application or initial notice submitted before that date, provided the work for each building is started before 15 June 2023. Full detail of the transitional arrangements can be found in Circular Letter 01/2021 published on gov.uk.
Introduction
What is an approved document?
Approved documents are approved by the Secretary of State and give practical guidance on common building situations about how to meet the requirements of the Building Regulations 2010 for England. Different approved documents give guidance on each of the technical parts of the regulations. These are all listed in the back of the approved documents. In addition to guidance, some approved documents include provisions that must be followed exactly, as required by regulations or where methods of test or calculation are approved by the Secretary of State.
Each approved document covers the requirements of the Building Regulations 2010 relating to a different aspect of building work. Building work must also comply with all other applicable requirements of the Building Regulations 2010 and all other applicable legislation.
How is construction regulated in England?
Most building work being carried out in England must comply with the Building Regulations 2010. The Building Regulations are made under powers in the Building Act 1984.
Building Regulations protect the health and safety of people in and around buildings, they also provide for energy and water conservation and access to and use of buildings.
The Manual to the Building Regulations (references to this in the introduction are taken from the first edition) gives an overview of the building regulatory system in England. You can access the most recent version of the manual at: www.gov.uk/guidance/building-regulations-and-approved-documents-index.
How do you comply with the Building Regulations?
Building work must meet all relevant requirements of the Building Regulations. To comply with the Building Regulations, it is necessary both to follow the correct procedures and meet technical performance requirements.
The approved documents set out what, in ordinary circumstances, may be accepted as one way to comply with the Building Regulations. Note, however, that:
Those responsible for building work include agents, designers, builders, installers and the building owner. For further information, see Chapter 7 in Volume 1 and paragraphs A26, B2 and F2 in Volume 2 of the Manual to the Building Regulations.
The Building Regulations can be contravened by not following the correct procedures or not meeting the technical performance requirements. If the building owner or those responsible for the works contravene the Building Regulations, the local authority may prosecute them in the magistrates’ court. For further information on enforcement and sanctions in the existing system, see Chapter B in Volume 2 of the Manual to the Building Regulations.
What do the Building Regulations cover?
‘Building work’ is a legal term for work covered by the Building Regulations. Where a building is not exempt, the Building Regulations apply to all types of building work as defined in regulation 3 of the Building Regulations. For further information, what constitutes building work is covered in Chapter A, Volume 2 of the Manual to the Building Regulations.
The Building Regulations contain sections dealing with definitions, procedures and the expected technical performance of building work. For example, the Building Regulations:
When must a building control body be notified?
It is often necessary to notify a building control body of planned building work. To help ensure that work complies with the Building Regulations, those responsible for building work may need to use one of the two types of building control body listed below:
If building work consists only of installing certain types of services or fittings (e.g. fuel-burning appliances or replacement windows) and the building owner employs an installer that is registered with a relevant competent person scheme designated in the regulations, a building control body does not need to be notified.
For further information about competent person schemes, see Chapter 5 in Volume 1 and Chapter C in Volume 2 of the Manual to the Building Regulations.
How to use this approved document
Each approved document contains:
They may not provide appropriate guidance if the case is unusual in terms of its design, setting, use, scale or technology. Non-standard conditions may include any of the following:
Anyone using the approved documents should have sufficient knowledge and skills to understand the guidance and correctly apply it to the building work. This is important because simply following the guidance does not guarantee that your building work will comply with the legal requirements of the Building Regulations. Each approved document contains legal requirements (which you must follow) and guidance (which you may or may not choose to follow). The text in a box with a green background at the beginning of each section of an approved document is taken from the Building Regulations. This text sets out the legal requirements.
The explanation which follows the legal requirements is guidance (see Diagram i below). The guidance then explains one or more ways to demonstrate how building work can be shown to comply with the legal requirements in common circumstances. The terms in green lettering in an approved document are key terms, listed and explained in the appendix to that approved document. Guidance in the approved documents addresses most, but not all, situations that building owners will face. Situations may arise that are not covered. You or your advisers will need to carefully consider whether following the guidance will mean that the requirements of the Building Regulations will be met.
For further information about the use of technical guidance, see Chapter 7 in Volume 1 and Chapter F in Volume 2 of the Manual to the Building Regulations.
Diagram i The relationship between regulations and guidance in the approved documents

Where to get further help
If you are unsure whether you have the knowledge and skills to apply the guidance correctly, or if you do not understand the technical guidance or other information in this approved document or the additional detailed technical references to which it directs you, you should seek further help. Some sources of help are listed below.
Section 0: Introduction
Summary
0.1
This approved document is Approved Document O: Overheating. It gives guidance on how to comply with Part O of the Building Regulations.
0.2
This approved document contains the following sections.
| Approved document section | Related Building Regulations requirements |
|---|---|
| Section 0: Introduction | n/a |
| Section 1: Simplified method | Requirement O1(1) of Schedule 1 |
| Section 2: Dynamic thermal modelling | |
| Section 3: Ensuring the overheating mitigation strategy is usable | Requirement O1(2)(a) of Schedule 1 |
| Section 4: Providing information | Regulation 40B |
| Appendix A: Key terms | n/a |
| Appendix B: Compliance checklist | n/a |
| Appendix C: Areas with a high risk of its buildings overheating | n/a |
| Appendix D: Calculating equivalent area | n/a |
| Appendix E: Standards referred to | n/a |
| Appendix F: Documents referred to | n/a |
Application
0.3
The guidance in this approved document applies to new residential buildings only. Residential buildings within the scope of Part O and this approved document are detailed in Table 0.1.
Table 0.1 Residential buildings within the scope of this approved document
| Title | Purpose for which the building is intended to be used |
|---|---|
| Residential (dwellings) | Dwellings, which includes both dwellinghouses and flats. |
| Residential (institutional) | Home, school or other similar establishment, where people sleep on the premises. The building may be living accommodation for the care or maintenance of any of the following. a. Older and disabled people, due to illness or other physical or mental condition. b. People under the age of 5 years. |
| Residential (other) | Residential college, hall of residence and other student accommodation, and living accommodation for children aged 5 years and older. |
Shared communal rooms and common spaces
0.4
Shared communal rooms and common spaces of buildings containing more than one residential unit fall within the scope of this approved document.
Live/work units
0.5
A unit that contains both living accommodation and space for commercial purposes (e.g. as a workshop or office) should be treated as a residential building, as long as the commercial part can revert to residential use.
0.6
The commercial part of a building can revert to residential use if all of the following apply.
NOTE: A large non-residential building that contains a small flat for a manager is not treated as a residential building. A residential building that contains a room used as an office or utility space is still treated as a residential building.
Mixed-use developments
0.7
The guidance in this approved document applies only to the parts of a mixed-use building that are for residential purposes and any corridor that serves residential units.
Alternative approaches
0.8
The guidance in this approved document is the suggested approach to meet the requirements of the Building Regulations. Alternative approaches are possible but they should be discussed and agreed with a building control body before building work starts.
0.9
The legal requirements of the Building Regulations must be met, regardless of whether the guidance in this approved document is followed or alternative measures are taken.
0.10
If alternative ways of mitigating overheating are adopted, the overall level of overheating risk reduction should not be lower than the approved document provides. It is the responsibility of those undertaking the work to demonstrate compliance.
Selected key interactions with other parts of the Building Regulations
0.11
The approved documents set out what, in ordinary circumstances, may be accepted as one way to comply with the Building Regulations. It remains the responsibility of those designing or undertaking building work to assess, on a case-by-case basis, whether specific circumstances require additional or alternative measures to achieve compliance with the regulatory requirements. There are interactions between many of the requirements of the Building Regulations and the following paragraphs provide guidance on some key interactions.
Interaction with Part B
0.12
This approved document, Approved Document O, gives guidance on window openings for removing excess heat from residential buildings. Approved Document B gives guidance on the size of escape windows. Where escape windows are provided to comply with Approved Document B, any extra glazing will impact the risk of overheating.
Interaction with Part F
0.13
This approved document, Approved Document O, includes guidance on providing means of removing excess heat from residential buildings. Where openings are used, the amount of ventilation for removing excess heat is likely to be higher than the purge ventilation required for Part F. The higher amount of ventilation applies – see Section 1 or Section 2 of this approved document, depending on the method of compliance.
Interaction with Part J
0.14
Ventilation fans might cause combustion gases to spill from open-flued appliances and fill the room instead of going up the flue or chimney. This can occur even if the combustion appliance and fan are in separate rooms.
0.15
The guidance in Approved Document J should be followed when installing and testing ventilation appliances and combustion appliances must operate safely whether or not fans are running.
Interaction with Part L
0.16
Solar gains in winter can reduce the amount of space heating required to be delivered by the heating system. Reducing summer overheating by limiting glazing areas will impact winter solar gains and therefore increase the need for space heating.
0.17
Poorly insulated pipework, particularly in community heating schemes, can be a major contributor to overheating. Control of heat losses from pipework is dealt with under Part L of the Building Regulations and the guidance in Approved Document L should be followed.
Interaction with Part K and Part M
0.18
Where manual controls are provided, they should be within reasonable reach of the occupants, to comply with Approved Documents K and M.
Interaction with Part K
0.19
This approved document, Approved Document O, gives guidance on increased levels of protection from falling from openings compared to Part K.
Interaction with Part Q
0.20
This approved document, Approved Document O, gives guidance on security considerations when providing large openings for removing excess heat. The locking systems of windows and doors should also conform to guidance given in Approved Document Q on the security of doors and windows in dwellings.
Requirement O1
This section deals with requirement O1 of Schedule 1 to the Building Regulations 2010.
Requirement
| Requirement | Limits on application |
|---|---|
O1 Overheating mitigation (1) Reasonable provision must be made in respect of a dwelling, institution or any other building containing one or more rooms for residential purposes, other than a room in a hotel (“residences”) to— (a) limit unwanted solar gains in summer; (b) provide an adequate means to remove heat from the indoor environment. (2) In meeting the obligations in paragraph (1)— (a) account must be taken of the safety of any occupant, and their reasonable enjoyment of the residence; and (b) mechanical cooling may only be used where insufficient heat is capable of being removed from the indoor environment without it. |
Intention
The aim of requirement O1 is to protect the health and welfare of occupants of the building by reducing the occurrence of high indoor temperatures.
In the Secretary of State’s view, requirement O1 is met by designing and constructing the building to achieve both of the following.
NOTE: The guidance and regulations are written for the purposes of protecting health and welfare. Following this guidance does not guarantee the comfort of building occupants.
In the Secretary of State’s view, compliance with requirement O1 can be demonstrated by using one of the following methods.
Section 1: Simplified method
1.1
This section details a simplified method for demonstrating compliance with requirement O1. It is suitable for any building within the scope of requirement O1.
NOTE: Appendix B of this approved document includes a compliance checklist. The designer may use this checklist to demonstrate compliance to building control bodies.
Categorising residential buildings (simplified method)
1.2
For the simplified method, the strategy to reduce overheating risk should be selected according to the location of the new residential building and whether it has cross-ventilation, following paragraphs 1.3 to 1.5.
1.3
For the purposes of following the simplified method, the building’s overheating risk category is determined by its location in one of the following areas.
NOTE: Appendix C also provides guidance for some parts of central Manchester.
1.4
For the purposes of following the simplified method, it should be identified whether the dwellinghouse or each residential unit, shared communal room and common space is able to have cross-ventilation, i.e. it has openings on opposite façades.
NOTE: Having openings on façades that are not opposite does not meet the approved document definition of cross-ventilation, e.g. in a corner flat.
NOTE: A multi-occupancy residential building should not be categorised as having or not having cross-ventilation. Each residential unit, shared communal room and common space should be categorised separately.
1.5
The building’s overheating risk category based on location and whether it is cross-ventilated should be used to select the relevant guidance for both of the following purposes.
Limiting solar gains
1.6
To limit solar gains, all of the following standards should be followed.
1.7
Buildings or parts of buildings with cross-ventilation should not exceed the maximum glazing areas in Table 1.1.
Table 1.1 Limiting solar gains for buildings or parts of buildings with cross-ventilation(1)
| High risk location | Moderate risk location | |||
|---|---|---|---|---|
| Largest glazed façade orientation | Maximum area of glazing (% floor area) | Maximum area of glazing in the most glazed room (% floor area of room) | Maximum area of glazing (% floor area) | Maximum area of glazing in the most glazed room (% floor area of room) |
| North | 15 | 37 | 18 | 37 |
| East | 18 | 37 | 18 | 37 |
| South | 15 | 22 | 15 | 30 |
| West | 18 | 37 | 11 | 22 |
NOTE:
1.8
Buildings or parts of buildings with no cross-ventilation should not exceed the maximum glazing areas in Table 1.2.
Table 1.2 Limiting solar gains for buildings or parts of buildings without cross-ventilation(1)
| High risk location | Moderate risk location | |||
|---|---|---|---|---|
| Largest glazed façade orientation | Maximum area of glazing (% floor area) | Maximum area of glazing in the most glazed room (% floor area of room) | Maximum area of glazing (% floor area) | Maximum area of glazing in the most glazed room (% floor area of room) |
| North | 15 | 26 | 18 | 26 |
| East | 11 | 18 | 18 | 26 |
| South | 11 | 11 | 15 | 15 |
| West | 11 | 18 | 11 | 11 |
NOTE:
1.9
Residential buildings in the high risk location should, in addition to following the maximum glazing areas in Table 1.1 and Table 1.2, provide shading for glazed areas between compass points north-east and north-west via the south. Shading should be provided by one of the following means.
Removing excess heat
1.10
Buildings or parts of buildings with cross-ventilation should equal or exceed the minimum free areas in Table 1.3.
Table 1.3 Minimum free areas for buildings or parts of buildings with cross-ventilation
| High risk location | Moderate risk location | |
|---|---|---|
| Total minimum free area(1) | The greater of the following: a. 6% of the floor area(2) b. 70% of the glazing area(3) | The greater of the following: a. 9% of the floor area(2) b. 55% of the glazing area(3) |
| Bedroom minimum free area | 13% of the floor area of the room(4) | 4% of the floor area of the room(4) |
NOTES:
1.11
Buildings or parts of buildings with no cross-ventilation should equal or exceed the minimum free areas in Table 1.4.
Table 1.4 Minimum free areas for buildings or parts of buildings without cross-ventilation
| High risk location | Moderate risk location | |
|---|---|---|
| Total minimum free area(1) | The greater of the following: a. 10% of the floor area(2) b. 95% of the glazing area(3) | The greater of the following: a. 12% of the floor area(2) b. 80% of the glazing area(3) |
| Bedroom minimum free area | 13% of the floor area of the room(4) | 4% of the floor area of the room(4) |
NOTES:
1.12
Openings should be designed to achieve the free areas in paragraphs 1.10 and 1.11. The equivalent area of the opening should meet or exceed the free area of the opening. The equivalent area of the opening should be assessed by either of the following means.
NOTE: A system for purge ventilation should be provided in each habitable room to demonstrate compliance with Part F of the Building Regulations. The guidance in Section 1 of Approved Document F, Volume 1: Dwellings gives minimum standards for purge ventilation. When following this simplified method, applying the guidance in paragraphs 1.10 to 1.12 will usually result in free areas that exceed the free areas in Approved Document F, Volume 1: Dwellings.
1.13
The simplified method is not suitable for buildings with more than one residential unit which use a communal heating or hot water system with significant amounts of horizontal heating or hot water distribution pipework. Main distribution routes should be through vertical risers to minimise heat gains into common spaces.
Section 2: Dynamic thermal modelling
2.1
This section details a dynamic thermal modelling method for demonstrating compliance with requirement O1. It provides a standardised approach to predicting overheating risk for residential buildings using dynamic thermal modelling as an alternative to the simplified method in Section 1.
2.2
The methodology is suitable for all residential buildings. It may offer the designer additional design flexibility over the solutions in Section 1 in the following situations.
NOTE: Local microclimates may not be well reflected by the geographically closest weather file.
Dynamic thermal modelling method
2.3
To demonstrate compliance using the dynamic thermal modelling method, all of the following guidance should be followed.
2.4
The building control body should be provided with a report that demonstrates that the residential building passes CIBSE’s TM59 assessment of overheating. This report should contain the details in CIBSE’s TM59, section 2.3.
NOTE: Appendix B of this approved document includes a compliance checklist. The designer may use this checklist to demonstrate compliance to the building control body.
Limits on CIBSE’s TM59 modelling
2.5
CIBSE’s TM59 method requires the modeller to make choices. The dynamic thermal modelling method in this section applies limits to these choices, which are detailed in paragraph 2.6. These limits should be applied when following the guidance in CIBSE’s TM59.
2.6
All of the following limits on CIBSE’s TM59, section 3.3, apply.
Acceptable strategies for reducing overheating risk
Limiting solar gains
2.7
Solar gains in summer should be limited by any of the following means.
2.8
Although internal blinds and curtains provide some reduction in solar gains, they should not be taken into account when considering whether requirement O1 has been met.
2.9
Foliage, such as tree cover, can provide some reduction in solar gains. However, it should not be taken into account when considering whether requirement O1 has been met.
NOTE: Examples of solar shading and their effectiveness are provided in the Building Research Establishment’s BR 364 Solar Shading of Buildings.
Removing excess heat
2.10
Excess heat should be removed from the residential building by any of the following means.
2.11
The building should be constructed to meet requirement O1 using passive means as far as reasonably practicable. It should be demonstrated to the building control body that all practicable passive means of limiting unwanted solar gains and removing excess heat have been used first before adopting mechanical cooling. Any mechanical cooling (air-conditioning) is expected to be used only where requirement O1 cannot be met using openings.
NOTE: Any method to reduce overheating risk in residential buildings must comply with all other parts of the Building Regulations. Particular attention should be paid to the requirements of Part F and the guidance in Approved Document F, Volume 1: Dwellings on noise and maintenance.
NOTE: A system for purge ventilation should be provided in each habitable room to demonstrate compliance with Part F of the Building Regulations. The guidance in Section 1 of Approved Document F, Volume 1: Dwellings should be followed for the minimum standards for purge ventilation. A larger amount of purge ventilation may be required than that in Approved Document F, Volume 1: Dwellings in order to satisfy requirement O1 on providing an adequate means to remove excess heat from the indoor environment.
Requirement O1(2)(a)
This section deals with requirement O1(2)(a) of Schedule 1 to the Building Regulations 2010.
Requirement
| Requirement | Limits on application |
|---|---|
O1 Overheating mitigation (1) Reasonable provision must be made in respect of a dwelling, institution or any other building containing one or more rooms for residential purposes, other than a room in a hotel (“residences”) to— (a) limit unwanted solar gains in summer; (b) provide an adequate means to remove heat from the indoor environment. (2) In meeting the obligations in paragraph (1)— (a) account must be taken of the safety of any occupant, and their reasonable enjoyment of the residence; and (b) mechanical cooling may only be used where insufficient heat is capable of being removed from the indoor environment without it. |
Intention
In the Secretary of State’s view, requirement O1(2)(a) is met in a new residential building if the building’s overheating mitigation strategy for use by occupants takes account of all of the following.
Section 3: Ensuring the overheating mitigation strategy is usable
3.1
The standards in this section may mean that the standards of the simplified method cannot be met. For example, if external noise is an issue, it is unlikely that windows would be opened by an occupant and therefore the minimum free areas of the simplified method cannot be met. In such cases, dynamic thermal modelling should be used.
Noise
3.2
In locations where external noise may be an issue (for example, where the local planning authority considered external noise to be an issue at the planning stage), the overheating mitigation strategy should take account of the likelihood that windows will be closed during sleeping hours (11pm to 7am).
3.3
Windows are likely to be closed during sleeping hours if noise within bedrooms exceeds the following limits.
3.4
Where in-situ noise measurements are used as evidence that these limits are not exceeded, measurements should be taken in accordance with the Association of Noise Consultants’ Measurement of Sound Levels in Buildings with the overheating mitigation strategy in use.
NOTE: Guidance on reducing the passage of external noise into buildings can be found in the National Model Design Code: Part 2 – Guidance Notes (MHCLG, 2021) and the Association of Noise Consultants’ Acoustics, Ventilation and Overheating: Residential Design Guide (2020).
Pollution
3.5
Buildings located near to significant local pollution sources should be designed to minimise the intake of external air pollutants. Guidance is given in Section 2 of Approved Document F, Volume 1: Dwellings.
Security
3.6
When determining the free area available for ventilation during sleeping hours, only the proportion of openings that can be opened securely should be considered to provide useful ventilation. This particularly applies in the following locations, where openings may be vulnerable to intrusion by a casual or opportunistic burglar.
3.7
Open windows or doors can be made secure by using any of the following.
Protection from falling
3.8
Openings which are intended to be open for long periods to reduce overheating risk might pose a higher risk of falls from height. Only the proportion of openings which can be opened with a very low risk of occupants falling from height should be considered to form part of the overheating mitigation strategy.
3.9
Openings that can be opened wider than 100mm may form part of the overheating mitigation strategy where they meet all of the following conditions.
NOTE: To ensure safe operation it may be necessary to reduce the size of the outward opening windows and provide more windows to meet the required free area.
Table 3.1 Guarding heights
| Change in floor level between inside and outside | Guarding height(1) |
|---|---|
| Less than 600mm | See Approved Document K |
| More than 600mm | 1.1m![]() |
NOTES:
3.10
Guarding for large openings could include, but is not limited to, either of the following.
Protection from entrapment
3.11
Louvered shutters, window railings and ventilation grilles should not allow body parts to become trapped. They should comply with all of the following.
Regulation 40B: Providing information
This section deals with the requirements of regulation 40B of the Building Regulations 2010.
Regulation
Information about overheating
40B. (1) This regulation applies to building work in respect of a building where Part O of Schedule 1 applies.
Intention
When a new residential building is erected, information about the building must be given to the owner of the building to allow them to use the overheating mitigation strategy effectively.
In the Secretary of State’s view, regulation 40B is met by providing information in accordance with Section 4.
Section 4: Providing information
4.1
Sufficient information about the overheating mitigation strategy and its maintenance requirements must be given to owners so that it can be used effectively. The information should be provided in a clear manner, for a non-technical audience.
4.2
The following information should be provided, where relevant.
Home User Guide
4.3
A Home User Guide should be provided for new dwellings as described in Section 9 of Approved Document L, Volume 1: Dwellings. The Home User Guide should contain a section on ‘Staying cool in hot weather’, which provides non-technical advice on how to keep the dwelling cool in hot weather. The information in paragraph 4.2 should be provided in this section of the Home User Guide.
NOTE: Information about ventilation and the conservation of fuel and power is required under different regulations and guidance is given in Approved Document F (Ventilation) and Approved Document L (Conservation of fuel and power). Where the system provides more than one function, the owner should be informed of each separate function.
Appendix A: Key terms
The definitions below apply to this document only and are not intended to be applied in other circumstances.
Building control body A local authority or an approved inspector.
Common spaces Spaces which are used mainly for circulation, e.g. a corridor or lift lobby.
Cross-ventilation The ability to ventilate using openings on opposite façades of a dwelling. Having openings on façades that are not opposite is not allowing cross-ventilation, e.g. in a corner flat.
Dynamic thermal modelling A method of building modelling that predicts the internal conditions and energy demands of a building at short time intervals using weather data and building characteristics.
Easily accessible Defined as one of the following.
Effective area The area through which air flows after the resistance of airflow has been taken into account.
Equivalent area A measure of the aerodynamic performance of an opening. It is the area of a sharp-edged circular orifice through which air would pass at the same volume flow rate, under an identical applied pressure difference, as through the opening under consideration.
Floor area The area of the residential unit, measured to the internal face of the perimeter walls at each floor level.
NOTE: This area is the gross internal area as measured in accordance with the Code of Measuring Practice by the Royal Institution of Chartered Surveyors (RICS).
Floor area of the room The area of the room, measured to the internal face of the perimeter walls. Where a room serves more than one activity, e.g. open-plan kitchen and living room, the area with the largest glazing area should be assessed and the room area calculated based on a room depth no greater than 4.5m from the glazed façade.
Free area The geometric open area of a ventilation opening. This area assumes a clear sharp-edged orifice that would have a coefficient of discharge (Cd) of 0.62.
Glazing area The area of transparent material, not including the window frame.
Guarding A barrier that denies people access to another area, for example the floor below.
Louvre A set of angled slats that allow air or light to pass through.
Passive means Any means of cooling a building which is not mechanical cooling (e.g. air conditioning). Openable windows or mechanical ventilation fans are considered to be passive means of cooling.
Purge ventilation Ventilation of rooms or spaces at a relatively high rate to rapidly dilute pollutants and/or disperse water vapour.
Residential units Habitable rooms or a suite of habitable rooms. Examples of a residential unit include, but are not limited to, a flat or rooms that are similar to a flat in care homes or student halls of residence.
Shared communal rooms Rooms in buildings containing dwellings or residential units, which provide facilities for the residents, e.g. a shared living room, kitchen or laundry room.
Appendix B: Compliance checklist
B1
This compliance checklist is divided into three parts, as follows.
B2
All three parts of the compliance checklist should be completed. The relevant parts of Part 2 and 3 should be signed by a person who is competent to design the residential building.
B3
A copy of this checklist, or a similar checklist, may be submitted to the building control body as evidence that the building has been constructed as designed to reduce the risk of overheating.
Part 1 – Building details and declarations
The designer should complete this section.
| 1.1 | Building and site details | |
|---|---|---|
| Residential building name/number | ||
| Street | ||
| Town | ||
| County | ||
| Postcode | ||
| Proposed building use/type of building | ||
| Are there any security, noise or pollution issues? | ||
| 1.2 | Designer’s details | |
| Designer’s name | ||
| Company | ||
| Address line 1 | ||
| Address line 2 | ||
| Postcode | ||
| Telephone number | ||
| Email address | ||
Part 2 – Design details
The designer should complete either Part 2a or 2b, depending on the method used.
Part 2a – Simplified method (as detailed in Section 1)
| 2a.1 | Site details | |
|---|---|---|
| Site location, assigned using paragraph 1.3(1) | ||
| Building category, assigned using paragraph 1.4 | ||
| 2a.2 | Designed overheating mitigation strategy | |
| Details of standards selected: | ||
| a. Maximum area of glazing | ||
b. Maximum area of glazing in the most glazed room | ||
| c. Shading strategy | ||
| d. Total minimum free area | ||
| e. Bedroom minimum free area | ||
| 2a.3 | Designer’s declaration | |
| Designer’s name | ||
| Designer’s organisation | ||
| Designer’s signature | ||
| Registration number (if applicable) | ||
| Date of design | ||
NOTE:
Part 2b – Dynamic thermal modelling method (as detailed in Section 2)
| 2b.1 | Modelling details | |||
|---|---|---|---|---|
| Dynamic software name and version | ||||
| Weather file location used, including any additional, more extreme weather files | ||||
| Number of sample units modelled, including an explanation of why the size/selection has been chosen | ||||
| 2b.2 | Modelled occupancy | |||
| Has the project passed the assessment described in CIBSE’s TM59, taking into account the limits detailed in paragraphs 2.5 and 2.6?(1) | Yes | No | ||
| Details of the occupancy profiles used | ||||
| Details of the equipment profiles used | ||||
| Details of the opening profiles used | ||||
| 2b.3 | Modelled overheating mitigation strategy | |||
| Free areas | ||||
| Infiltration and mechanical flow rates | ||||
| Window g-value | ||||
| Shading strategy | ||||
| Mechanical cooling | ||||
| 2b.4 | Modelling results | |||
| Has the project passed the assessment described in CIBSE’s TM59, taking into account the limits detailed in paragraphs 2.5 and 2.6? | Yes | No | ||
| What is the overall overheating strategy (i.e. what design features are key to the project passing)? | ||||
| 2b.5 | Designer’s declaration | |||
| Has the building construction proposal been modelled accurately? | Yes | No | ||
| Designer’s name | ||||
| Designer’s organisation | ||||
| Designer’s signature | ||||
| Registration number (if applicable) | ||||
| Date of design | ||||
NOTE:
Part 3 – Completion details
Both the builder and the building control body inspector should complete this section.
| 3.1 | Builder’s declaration | |||
|---|---|---|---|---|
| Has the residential building been constructed and completed according to the specifications set out in Parts 1 and 2 of this checklist? | Yes | No | ||
| Builder’s name | ||||
| Builder’s organisation | ||||
| Builder’s signature | ||||
| Date of signature | ||||
| 3.2 | Building control body inspector’s declaration | |||
| Is the residential building’s construction consistent with the details provided in Parts 1 and 2 of this checklist? | Yes | No | ||
| Inspector’s name | ||||
| Inspector’s signature | ||||
| Registration number (if applicable) | ||||
| Date of inspection | ||||
Appendix C: Areas with a high risk of its buildings overheating
C1
This appendix provides a list of the areas deemed to have a high risk of the buildings within them overheating.
C2
This appendix should be used with the simplified method to categorise residential buildings, following paragraph 1.3.
C3
The postcodes in Table C1 are in the high risk part of London. Diagram C1 also shows the high risk part of London, where a higher standard of risk mitigation is needed.
NOTE: Central Manchester (postcodes M1, M2, M3, M5, M15, M16 and M50) may also have elevated night time temperatures. Consider following the guidance for higher risk locations for buildings in these postcodes.
Table C1 Overheating risk at postcode area level in the high risk part of London
- CR4
- CR7
- E1
- E1W
- E2
- E3
- E4
- E5
- E6
- E7
- E8
- E9
- E10
- E11
- E12
- E13
- E14
- E15
- E16
- E17
- E18
- E20
- EC1A
- EC1M
- EC1N
- EC1R
- EC1V
- EC1Y
- EC2A
- EC2M
- EC2N
- EC2P
- EC2R
- EC2V
- EC2Y
- EC3A
- EC3M
- EC3N
- EC3R
- EC3V
- EC4A
- EC4M
- EC4N
- EC4R
- EC4V
- EC4Y
- HA0
- HA9
- IG1
- IG2
- IG3
- IG4
- KT1
- KT2
- KT3
- KT4
- KT5
- KT6
- KT7
- KT8
- IG11
- N1
- N1C
- N2
- N4
- N5
- N6
- N7
- N8
- N9
- N13
- N15
- N16
- N17
- N18
- N19
- N22
- NW1
- NW2
- NW3
- NW5
- NW6
- NW8
- NW10
- NW11
- RM8
- RM9
- RM10
- SE1
- SE2
- SE3
- SE4
- SE5
- SE6
- SE7
- SE8
- SE9
- SE10
- SE11
- SE12
- SE13
- SE14
- SE15
- SE16
- SE17
- SE18
- SE19
- SE20
- SE21
- SE22
- SE23
- SE24
- SE25
- SE26
- SE27
- SE28
- SW1A
- SW1E
- SW1H
- SW1P
- SW1V
- SW1W
- SW1X
- SW1Y
- SW2
- SW3
- SW4
- SW5
- SW6
- SW7
- SW8
- SW9
- SW10
- SW11
- SW12
- SW13
- SW14
- SW15
- SW16
- SW17
- SW18
- SW19
- SW20
- TW1
- TW2
- TW3
- TW4
- TW5
- TW6
- TW7
- TW8
- TW9
- TW10
- TW11
- TW12
- TW13
- TW14
- TW15
- TW19
- UB1
- UB2
- UB3
- UB4
- UB5
- UB6
- UB7
- UB8
- UB11
- W1B
- W1C
- W1D
- W1F
- W1G
- W1H
- W1J
- W1K
- W1S
- W1T
- W1U
- W1W
- W2
- W3
- W4
- W5
- W6
- W7
- W8
- W9
- W10
- W11
- W12
- W13
- W14
- WC1A
- WC1B
- WC1E
- WC1H
- WC1N
- WC1R
- WC1V
- WC1X
- WC2A
- WC2B
- WC2E
- WC2H
- WC2N
- WC2R
Diagram C1 Overheating risk at postcode area level in the high risk part of London

Appendix D: Calculating equivalent area
D1
The free areas in Section 1 of this approved document are geometric open areas that assume a clear sharp-edged orifice with a 0.62 coefficient of discharge (Cd). Different opening types will reduce the amount of air flow by both affecting the way air flows and reducing the physical area. Accounting for these factors gives the equivalent area.
D2
The equivalent area of a window can be calculated using one of the following.
NOTE: As stated in paragraph 1.12, measurement of equivalent area to BS EN 13141-1 is also appropriate. Measurement of equivalent area is more accurate than calculation and is therefore preferable.
D3
Using Tables D1 to D9 to calculate equivalent area is appropriate for the following types of window.
Diagram D1 Side hung window illustration with table references

Table D1 Equivalent area of a window with an opening angle of α = 10°
| Opening width, w (m) | ||||||
|---|---|---|---|---|---|---|
| 0.5 | 0.75 | 1 | 1.25 | 1.5 | ||
| Opening height, h (m) | 0.5 | 0.08 | 0.14 | 0.18 | 0.28 | 0.34 |
| 0.75 | 0.11 | 0.17 | 0.27 | 0.34 | 0.41 | |
| 1 | 0.14 | 0.23 | 0.30 | 0.45 | 0.54 | |
| 1.25 | 0.18 | 0.28 | 0.38 | 0.47 | 0.68 | |
| 1.5 | 0.21 | 0.32 | 0.45 | 0.57 | 0.68 | |
| 1.75 | 0.25 | 0.37 | 0.53 | 0.66 | 0.79 | |
| 2 | 0.28 | 0.42 | 0.56 | 0.75 | 0.91 | |
| 2.25 | 0.32 | 0.47 | 0.63 | 0.85 | 1.02 | |
| 2.5 | 0.35 | 0.53 | 0.70 | 0.88 | 1.13 | |
| 2.75 | 0.39 | 0.58 | 0.77 | 0.96 | 1.25 | |
| 3 | 0.42 | 0.63 | 0.84 | 1.05 | 1.26 | |
Table D2 Equivalent area of a window with an opening angle of α = 20°
| Opening width, w (m) | ||||||
|---|---|---|---|---|---|---|
| 0.5 | 0.75 | 1 | 1.25 | 1.5 | ||
| Opening height, h (m) | 0.5 | 0.13 | 0.22 | 0.29 | 0.43 | 0.52 |
| 0.75 | 0.19 | 0.28 | 0.44 | 0.55 | 0.66 | |
| 1 | 0.24 | 0.38 | 0.50 | 0.73 | 0.88 | |
| 1.25 | 0.29 | 0.47 | 0.63 | 0.79 | 1.10 | |
| 1.5 | 0.35 | 0.53 | 0.76 | 0.94 | 1.13 | |
| 1.75 | 0.41 | 0.62 | 0.88 | 1.10 | 1.32 | |
| 2 | 0.47 | 0.71 | 0.94 | 1.26 | 1.51 | |
| 2.25 | 0.53 | 0.80 | 1.06 | 1.42 | 1.70 | |
| 2.5 | 0.59 | 0.88 | 1.18 | 1.47 | 1.89 | |
| 2.75 | 0.65 | 0.97 | 1.30 | 1.62 | 2.08 | |
| 3 | 0.71 | 1.06 | 1.42 | 1.77 | 2.12 | |
Table D3 Equivalent area of a window with an opening angle of α = 30°
| Opening width, w (m) | ||||||
|---|---|---|---|---|---|---|
| 0.5 | 0.75 | 1 | 1.25 | 1.5 | ||
| Opening height, h (m) | 0.5 | 0.16 | 0.27 | 0.36 | 0.52 | 0.62 |
| 0.75 | 0.24 | 0.36 | 0.54 | 0.68 | 0.81 | |
| 1 | 0.30 | 0.48 | 0.64 | 0.90 | 1.08 | |
| 1.25 | 0.38 | 0.60 | 0.80 | 1.00 | 1.36 | |
| 1.5 | 0.45 | 0.68 | 0.96 | 1.20 | 1.43 | |
| 1.75 | 0.53 | 0.79 | 1.12 | 1.40 | 1.67 | |
| 2 | 0.60 | 0.90 | 1.21 | 1.59 | 1.91 | |
| 2.25 | 0.68 | 1.02 | 1.36 | 1.79 | 2.15 | |
| 2.5 | 0.75 | 1.13 | 1.51 | 1.88 | 2.39 | |
| 2.75 | 0.83 | 1.24 | 1.66 | 2.07 | 2.63 | |
| 3 | 0.90 | 1.36 | 1.81 | 2.26 | 2.71 | |
Table D4 Equivalent area of a window with an opening angle of α = 40°
| Opening width, w (m) | ||||||
|---|---|---|---|---|---|---|
| 0.5 | 0.75 | 1 | 1.25 | 1.5 | ||
| Opening height, h (m) | 0.5 | 0.18 | 0.30 | 0.40 | 0.56 | 0.67 |
| 0.75 | 0.27 | 0.41 | 0.61 | 0.76 | 0.91 | |
| 1 | 0.35 | 0.55 | 0.73 | 1.01 | 1.21 | |
| 1.25 | 0.43 | 0.68 | 0.91 | 1.14 | 1.52 | |
| 1.5 | 0.52 | 0.78 | 1.09 | 1.36 | 1.64 | |
| 1.75 | 0.61 | 0.91 | 1.27 | 1.59 | 1.91 | |
| 2 | 0.69 | 1.04 | 1.38 | 1.82 | 2.18 | |
| 2.25 | 0.78 | 1.17 | 1.56 | 2.05 | 2.46 | |
| 2.5 | 0.86 | 1.30 | 1.73 | 2.16 | 2.73 | |
| 2.75 | 0.95 | 1.43 | 1.90 | 2.38 | 3.00 | |
| 3 | 1.04 | 1.56 | 2.08 | 2.59 | 3.11 | |
Table D5 Equivalent area of a window with an opening angle of α = 50°
| Opening width, w (m) | ||||||
|---|---|---|---|---|---|---|
| 0.5 | 0.75 | 1 | 1.25 | 1.5 | ||
| Opening height, h (m) | 0.5 | 0.20 | 0.32 | 0.43 | 0.59 | 0.70 |
| 0.75 | 0.30 | 0.44 | 0.65 | 0.81 | 0.97 | |
| 1 | 0.38 | 0.59 | 0.79 | 1.08 | 1.29 | |
| 1.25 | 0.47 | 0.74 | 0.98 | 1.23 | 1.62 | |
| 1.5 | 0.56 | 0.85 | 1.18 | 1.48 | 1.77 | |
| 1.75 | 0.66 | 0.99 | 1.38 | 1.72 | 2.07 | |
| 2 | 0.75 | 1.13 | 1.51 | 1.97 | 2.36 | |
| 2.25 | 0.85 | 1.27 | 1.69 | 2.21 | 2.66 | |
| 2.5 | 0.94 | 1.41 | 1.88 | 2.35 | 2.95 | |
| 2.75 | 1.04 | 1.55 | 2.07 | 2.59 | 3.25 | |
| 3 | 1.13 | 1.69 | 2.26 | 2.82 | 3.39 | |
Table D6 Equivalent area of a window with an opening angle of α = 60°
| Opening width, w (m) | ||||||
|---|---|---|---|---|---|---|
| 0.5 | 0.75 | 1 | 1.25 | 1.5 | ||
| Opening height, h (m) | 0.5 | 0.21 | 0.34 | 0.45 | 0.60 | 0.72 |
| 0.75 | 0.31 | 0.47 | 0.67 | 0.84 | 1.01 | |
| 1 | 0.40 | 0.62 | 0.83 | 1.12 | 1.34 | |
| 1.25 | 0.50 | 0.78 | 1.03 | 1.29 | 1.68 | |
| 1.5 | 0.60 | 0.89 | 1.24 | 1.55 | 1.86 | |
| 1.75 | 0.70 | 1.04 | 1.45 | 1.81 | 2.17 | |
| 2 | 0.79 | 1.19 | 1.59 | 2.07 | 2.48 | |
| 2.25 | 0.89 | 1.34 | 1.79 | 2.33 | 2.79 | |
| 2.5 | 0.99 | 1.49 | 1.99 | 2.48 | 3.10 | |
| 2.75 | 1.09 | 1.64 | 2.19 | 2.73 | 3.41 | |
| 3 | 1.19 | 1.79 | 2.38 | 2.98 | 3.58 | |
Table D7 Equivalent area of a window with an opening angle of α = 70°
| Opening width, w (m) | ||||||
|---|---|---|---|---|---|---|
| 0.5 | 0.75 | 1 | 1.25 | 1.5 | ||
| Opening height, h (m) | 0.5 | 0.21 | 0.34 | 0.46 | 0.61 | 0.73 |
| 0.75 | 0.32 | 0.48 | 0.69 | 0.86 | 1.03 | |
| 1 | 0.41 | 0.64 | 0.85 | 1.15 | 1.37 | |
| 1.25 | 0.51 | 0.80 | 1.07 | 1.33 | 1.72 | |
| 1.5 | 0.62 | 0.93 | 1.28 | 1.60 | 1.92 | |
| 1.75 | 0.72 | 1.08 | 1.49 | 1.87 | 2.24 | |
| 2 | 0.82 | 1.23 | 1.65 | 2.13 | 2.56 | |
| 2.25 | 0.93 | 1.39 | 1.85 | 2.40 | 2.88 | |
| 2.5 | 1.03 | 1.54 | 2.06 | 2.57 | 3.20 | |
| 2.75 | 1.13 | 1.70 | 2.26 | 2.83 | 3.52 | |
| 3 | 1.23 | 1.85 | 2.47 | 3.09 | 3.70 | |
Table D8 Equivalent area of a window with an opening angle of α = 80°
| Opening width, w (m) | ||||||
|---|---|---|---|---|---|---|
| 0.5 | 0.75 | 1 | 1.25 | 1.5 | ||
| Opening height, h (m) | 0.5 | 0.22 | 0.35 | 0.46 | 0.61 | 0.73 |
| 0.75 | 0.33 | 0.49 | 0.70 | 0.87 | 1.04 | |
| 1 | 0.42 | 0.65 | 0.87 | 1.16 | 1.39 | |
| 1.25 | 0.53 | 0.82 | 1.09 | 1.36 | 1.74 | |
| 1.5 | 0.63 | 0.95 | 1.31 | 1.63 | 1.96 | |
| 1.75 | 0.74 | 1.11 | 1.53 | 1.91 | 2.29 | |
| 2 | 0.84 | 1.26 | 1.68 | 2.18 | 2.61 | |
| 2.25 | 0.95 | 1.42 | 1.90 | 2.45 | 2.94 | |
| 2.5 | 1.05 | 1.58 | 2.11 | 2.63 | 3.27 | |
| 2.75 | 1.16 | 1.74 | 2.32 | 2.90 | 3.60 | |
| 3 | 1.26 | 1.90 | 2.53 | 3.16 | 3.79 | |
Table D9 Equivalent area of a window with an opening angle of α = 90°
| Opening width, w (m) | ||||||
|---|---|---|---|---|---|---|
| 0.5 | 0.75 | 1 | 1.25 | 1.5 | ||
| Opening height, h (m) | 0.5 | 0.22 | 0.35 | 0.47 | 0.61 | 0.74 |
| 0.75 | 0.33 | 0.50 | 0.70 | 0.88 | 1.05 | |
| 1 | 0.43 | 0.66 | 0.88 | 1.17 | 1.40 | |
| 1.25 | 0.53 | 0.83 | 1.10 | 1.38 | 1.76 | |
| 1.5 | 0.64 | 0.96 | 1.33 | 1.66 | 1.99 | |
| 1.75 | 0.75 | 1.12 | 1.55 | 1.93 | 2.32 | |
| 2 | 0.86 | 1.28 | 1.71 | 2.21 | 2.65 | |
| 2.25 | 0.96 | 1.44 | 1.93 | 2.48 | 2.98 | |
| 2.5 | 1.07 | 1.60 | 2.14 | 2.67 | 3.31 | |
| 2.75 | 1.18 | 1.76 | 2.35 | 2.94 | 3.64 | |
| 3 | 1.28 | 1.93 | 2.57 | 3.21 | 3.85 | |
Appendix E: Standards referred to
BS EN 13141-1 Ventilation for buildings. Performance testing of components/products for residential ventilation – Externally and internally mounted air transfer devices [2019]
Appendix F: Documents referred to
Legislation
(available via www.legislation.gov.uk)
Building Act 1984, c. 55
Building (Approved Inspectors etc.) Regulations 2010, SI 2010/2215
Building Regulations 2010, SI 2010/2214
Other documents
Association of Noise Consultants
(www.association-of-noise-consultants.co.uk)
Acoustics, Ventilation and Overheating: Residential Design Guide [2020]
Measurement of Sound Levels in Buildings [2020]
Building Research Establishment (BRE)
(www.bre.co.uk)
BR 364 Solar Shading of Buildings, Second Edition [2018]
Chartered Institution of Building Services Engineers (CIBSE)
(www.cibse.org)
TM59 Design Methodology for the Assessment of Overheating Risk in Homes [2017]
Ministry of Housing, Communities and Local Government (MHCLG)
National Model Design Code: Part 2 – Guidance Notes [2021]