Section 0: Introduction

Section 0: Introduction

Summary

0.1

This approved document is Approved Document O: Overheating. It gives guidance on how to comply with Part O of the Building Regulations.

0.2

This approved document contains the following sections.

Approved document sectionRelated Building Regulations requirements
Section 0: Introductionn/a
Section 1: Simplified methodRequirement O1(1) of Schedule 1
Section 2: Dynamic thermal modelling
Section 3: Ensuring the overheating mitigation strategy is usableRequirement O1(2)(a) of Schedule 1
Section 4: Providing informationRegulation 40B
Appendix A: Key termsn/a
Appendix B: Compliance checklistn/a
Appendix C: Areas with a high risk of its buildings overheatingn/a
Appendix D: Calculating equivalent arean/a
Appendix E: Standards referred ton/a
Appendix F: Documents referred ton/a

Application

0.3

The guidance in this approved document applies to new residential buildings only. Residential buildings within the scope of Part O and this approved document are detailed in Table 0.1.

Table 0.1 Residential buildings within the scope of this approved document

TitlePurpose for which the building is intended to be used
Residential (dwellings)Dwellings, which includes both dwellinghouses and flats.
Residential (institutional)

Home, school or other similar establishment, where people sleep on the premises. The building may be living accommodation for the care or maintenance of any of the following.

a. Older and disabled people, due to illness or other physical or mental condition.
b. People under the age of 5 years.
Residential (other)Residential college, hall of residence and other student accommodation, and living accommodation for children aged 5 years and older.

Shared communal rooms and common spaces

0.4

Shared communal rooms and common spaces of buildings containing more than one residential unit fall within the scope of this approved document.

Live/work units

0.5

A unit that contains both living accommodation and space for commercial purposes (e.g. as a workshop or office) should be treated as a residential building, as long as the commercial part can revert to residential use.

0.6

The commercial part of a building can revert to residential use if all of the following apply.

a. There is direct access between the commercial space and the residential accommodation.
b. The commercial space and the residential accommodation are within the same thermal envelope.
c. The residential accommodation comprises a substantial proportion of the total area of the unit. What constitutes a ‘substantial proportion’ should be assessed on a case-by-case basis by the building control body.

NOTE: A large non-residential building that contains a small flat for a manager is not treated as a residential building. A residential building that contains a room used as an office or utility space is still treated as a residential building.

Mixed-use developments

0.7

The guidance in this approved document applies only to the parts of a mixed-use building that are for residential purposes and any corridor that serves residential units.

Alternative approaches

0.8

The guidance in this approved document is the suggested approach to meet the requirements of the Building Regulations. Alternative approaches are possible but they should be discussed and agreed with a building control body before building work starts.

0.9

The legal requirements of the Building Regulations must be met, regardless of whether the guidance in this approved document is followed or alternative measures are taken.

0.10

If alternative ways of mitigating overheating are adopted, the overall level of overheating risk reduction should not be lower than the approved document provides. It is the responsibility of those undertaking the work to demonstrate compliance.

Selected key interactions with other parts of the Building Regulations

0.11

The approved documents set out what, in ordinary circumstances, may be accepted as one way to comply with the Building Regulations. It remains the responsibility of those designing or undertaking building work to assess, on a case-by-case basis, whether specific circumstances require additional or alternative measures to achieve compliance with the regulatory requirements. There are interactions between many of the requirements of the Building Regulations and the following paragraphs provide guidance on some key interactions.

Interaction with Part B

0.12

This approved document, Approved Document O, gives guidance on window openings for removing excess heat from residential buildings. Approved Document B gives guidance on the size of escape windows. Where escape windows are provided to comply with Approved Document B, any extra glazing will impact the risk of overheating.

Interaction with Part F

0.13

This approved document, Approved Document O, includes guidance on providing means of removing excess heat from residential buildings. Where openings are used, the amount of ventilation for removing excess heat is likely to be higher than the purge ventilation required for Part F. The higher amount of ventilation applies – see Section 1 or Section 2 of this approved document, depending on the method of compliance.

Interaction with Part J

0.14

Ventilation fans might cause combustion gases to spill from open-flued appliances and fill the room instead of going up the flue or chimney. This can occur even if the combustion appliance and fan are in separate rooms.

0.15

The guidance in Approved Document J should be followed when installing and testing ventilation appliances and combustion appliances must operate safely whether or not fans are running.

Interaction with Part L

0.16

Solar gains in winter can reduce the amount of space heating required to be delivered by the heating system. Reducing summer overheating by limiting glazing areas will impact winter solar gains and therefore increase the need for space heating.

0.17

Poorly insulated pipework, particularly in community heating schemes, can be a major contributor to overheating. Control of heat losses from pipework is dealt with under Part L of the Building Regulations and the guidance in Approved Document L should be followed.

Interaction with Part K and Part M

0.18

Where manual controls are provided, they should be within reasonable reach of the occupants, to comply with Approved Documents K and M.

Interaction with Part K

0.19

This approved document, Approved Document O, gives guidance on increased levels of protection from falling from openings compared to Part K.

Interaction with Part Q

0.20

This approved document, Approved Document O, gives guidance on security considerations when providing large openings for removing excess heat. The locking systems of windows and doors should also conform to guidance given in Approved Document Q on the security of doors and windows in dwellings.