Open-sided car parks 11.2
11.2
For the purposes of assessing fire resistance, a building, compartment or separated part containing a car park may be regarded as open-sided when it complies with all of the following.
a. There are no basement storeys.
b. Each storey is naturally ventilated by permanent openings at each car parking level. The aggregate vent area is a minimum of 1/20 of that level’s floor area, at least half of which is provided equally by two opposite walls (1/80 on each side). The remaining free area can be distributed wherever possible.
c. Where one element of structure supports, carries or stabilises another, the fire resistance of the supporting element at least matches the minimum period of fire resistance for the other element.
d. In mixed use buildings, the fire resistance of any element that supports, carries or stabilises an element in the other part of the building should at least match the minimum period of fire resistance for the other element.
e. All materials used in the construction should be class A1 rated, except for the following.
i. Any surface finish applied to a floor or roof of the car park (or within any building, compartment or separated part adjoining the structure enclosing it), if the finish meets requirements B2 and B4.
ii. Any fire doorset.
iii. Any attendant’s kiosk not exceeding 15m2 in area.
iv. Any shop mobility facility.