Section 11: Special provisions for car parks

Section 11: Special provisions for car parks

11.1

Car parks call for different measures to restrict fire spread within buildings for the following reasons.

a. The fire load is well defined.
b. The probability of fire spreading from one storey to another in a well ventilated car park is low. Guidance is therefore given for three ventilation scenarios.

Open-sided car parks

Natural ventilation

11.2

For the purposes of assessing fire resistance, a building, compartment or separated part containing a car park may be regarded as open-sided when it complies with all of the following.

a. There are no basement storeys.
b. Each storey is naturally ventilated by permanent openings at each car parking level. The aggregate vent area is a minimum of 1/20 of that level’s floor area, at least half of which is provided equally by two opposite walls (1/80 on each side). The remaining free area can be distributed wherever possible.
c. Where one element of structure supports, carries or stabilises another, the fire resistance of the supporting element at least matches the minimum period of fire resistance for the other element.
d. In mixed use buildings, the fire resistance of any element that supports, carries or stabilises an element in the other part of the building should at least match the minimum period of fire resistance for the other element.
e. All materials used in the construction should be class A1 rated, except for the following.
i. Any surface finish applied to a floor or roof of the car park (or within any building, compartment or separated part adjoining the structure enclosing it), if the finish meets requirements B2 and B4.
ii. Any fire doorset.
iii. Any attendant’s kiosk not exceeding 15m2 in area.
iv. Any shop mobility facility.

Car parks that are not open-sided

11.3

For car parks that do not have the ventilation set out in paragraph 11.2, the required fire resistance is given in Appendix B, Table B2. Ventilation should be either natural or mechanical. See Approved Document F for additional guidance on ventilation of car parks.

Natural ventilation

11.4

Each storey should be ventilated by permanent openings at each car parking level. The openings can be at ceiling level. The aggregate free vent area should be a minimum of 1/40 of that level’s floor area, at least half of which should be provided equally by two opposite walls (1/160 on each side). The remaining free area can be distributed wherever possible.

Mechanical ventilation

11.5

If the minimum standard of natural ventilation is not possible, a system of mechanical ventilation should be provided that complies with all of the following.

a. The system should be both of the following.
i. Independent of any other ventilating system (other than any system that provides day to day ventilation to the car park).
ii. Designed to operate at 10 air changes per hour during a fire.
b. The system should run in two parts, each of which is:
i. capable of extracting 50% of the rates set out in item (a)
ii. able to operate alone or with the other part
iii. provided with an independent power supply capable of operating if the main supply fails.
c. 50% of the outlets should be at high level and 50% at low level.
d. The system should use E, I and S ductwork in accordance with BS EN 1366-8.

For further information on equipment for removing hot smoke, refer to BS EN 12101-3. An alternative method of providing smoke ventilation from enclosed car parks is given in BS 7346-7.