Provision of private hydrants 16.9
16.9
If additional hydrants are required, these should be provided in accordance with the following.
a. For buildings provided with fire mains – within 90m of dry fire main inlets.
b. For buildings not provided with fire mains – hydrants should be both of the following.
i. Within 90m of an entrance to the building.
ii. A maximum of 90m apart.