Section 16: Fire mains and hydrants Provision of private hydrants
Provision of private hydrants
16.8
A building requires additional fire hydrants if both of the following apply.
a. It has a compartment with an area more than 280m2.
b. It is being erected more than 100m from an existing fire hydrant.
16.9
If additional hydrants are required, these should be provided in accordance with the following.
a. For buildings provided with fire mains – within 90m of dry fire main inlets.
b. For buildings not provided with fire mains – hydrants should be both of the following.
i. Within 90m of an entrance to the building.
ii. A maximum of 90m apart.
16.10
Each fire hydrant should be clearly indicated by a plate, fixed nearby in a conspicuous position, in accordance with BS 3251.
16.11
Guidance on aspects of provision and siting of private fire hydrants is given in BS 9990.
Alternative supply of water
16.12
An alternative source of water supply should be provided where any of the following apply.
a. No piped water supply is available.
b. Pressure and flow in the water main are insufficient.
c. An alternative source of supply is proposed.
16.13
The alternative source of water supply should be one of the following, subject to consultation with the local fire and rescue service.
a. A charged static water tank with a minimum capacity of 45,000 litres.
b. A spring, river, canal or pond that is capable of fulfilling both of the following conditions.
i. Providing or storing a minimum of 45,000 litres of water at all times.
ii. Providing access, space and a hardstanding for a pumping appliance.
c. Any other water supply that the local fire and rescue service considers appropriate.