Essential information 19.4

19.4

Information on the location of fire protection measures may be sufficient. An as-built plan of the building should be provided showing all of the following.

a. Escape routes – this should include exit capacity (i.e. the maximum allowable number of people for each storey and for the building).
b. Fire resisting construction and location of fire-separating elements (including cavity barriers in walk-in spaces).
c. Fire doorsets, fire doorsets fitted with a self-closing device and other doors relevant to the fire safety strategy, such as doors equipped with relevant hardware.
d. Locations of fire detector heads (e.g. heat and smoke detectors), manual call points, fire alarm control and indicating equipment, fire alarm sounders, fire safety signage, emergency lighting, fire extinguishers, dry or wet fire mains and other firefighting equipment, and hydrants outside the building.
e. Any sprinkler systems, including isolating valves and control equipment.
f. Any smoke control systems, or ventilation systems with a smoke control function, including mode of operation and control systems.
g. Any high risk areas (e.g. heating machinery).
h. Any power supplies or power generating installations.
i. The location of secure information boxes.