Section 19: Fire safety information

Section 19: Fire safety information

19.1

For building work involving the erection or extension or a change of use of a relevant building (i.e. a building to which the Regulatory Reform (Fire Safety) Order 2005 or the Building Safety Act 2022 applies, or will apply), fire safety information should be given to the relevant dutyholder (responsible person or accountable person) at one of the following times, whichever is the earlier.

a. When the project is complete.
b. When the building or extension is first occupied.

19.2

This section is a guide to the information that should be provided and is not exhaustive. Guidance is in terms of essential information and additional information for complex buildings; however, the level of detail required should be considered on a case-by-case basis.

Essential information

19.3

The essential information provided should be sufficient to enable the relevant dutyholder to understand, operate and maintain the building (including the fire safety systems in it). It should make it clear how the fire safety arrangements of the building are intended to operate together. In cases where a fire safety strategy has been prepared (e.g. as part of the design and construction process for a building or building work), then this should be made available to the relevant dutyholder.

19.4

Information on the location of fire protection measures may be sufficient. An as-built plan of the building should be provided showing all of the following.

a. Escape routes – this should include exit capacity (i.e. the maximum allowable number of people for each storey and for the building).
b. Fire resisting construction and location of fire-separating elements (including cavity barriers in walk-in spaces).
c. Fire doorsets, fire doorsets fitted with a self-closing device and other doors relevant to the fire safety strategy, such as doors equipped with relevant hardware.
d. Locations of fire detector heads (e.g. heat and smoke detectors), manual call points, fire alarm control and indicating equipment, fire alarm sounders, fire safety signage, emergency lighting, fire extinguishers, dry or wet fire mains and other firefighting equipment, and hydrants outside the building.
e. Any sprinkler systems, including isolating valves and control equipment.
f. Any smoke control systems, or ventilation systems with a smoke control function, including mode of operation and control systems.
g. Any high risk areas (e.g. heating machinery).
h. Any power supplies or power generating installations.
i. The location of secure information boxes.

19.5

Details should be provided of all of the following.

a. Specifications of fire safety equipment provided, including routine maintenance schedules.
b. Any assumptions regarding the management of the building in the design of the fire safety arrangements.
c. Any provision enabling the evacuation of disabled people, which can be used when designing personal emergency evacuation plans.
d. Information for care homes should include the assessment for the number of beds in a compartment, as this should set out the expected number of staff and level of assistance of residents (see paragraph 2.39).

Additional information for complex buildings

19.6

A detailed record should be provided of both of the following.

a. The fire safety strategy.
b. Procedures for operating and maintaining any fire protection measures. This should include an outline cause and effect matrix/strategy for the building.
Further guidance is available in clause 9 and Annex H of BS 9999.

19.7

The records should include details of the following.

a. The fire safety strategy, including all assumptions in the design of the fire safety systems (such as fire load). Any risk assessments or risk analysis.
b. All assumptions in the design of the fire safety arrangements for the management of the building.
c. All of the following.
i. Escape routes (including occupant load and capacity of escape routes).
ii. Any provision to enable the evacuation of disabled people (including the location and mode of operation of evacuation lifts).
iii. Escape strategy (e.g. simultaneous or phased).
iv. Assembly points and/or muster stations.
d. All passive fire safety measures, including all of the following.
i. Compartmentation.
ii. Fire-separating elements.
iii. Fire resisting construction.
iv. Cavity barriers.
v. Fire doorsets, including fire doorsets fitted with a self-closing device and other doors relevant to the fire safety strategy, such as doors equipped with relevant hardware (e.g. electronic security locks).
vi. Fire dampers, fire and smoke dampers, and smoke control dampers.
vii. Fire shutters.
e. All of the following.
i. Fire detector heads (e.g. heat and smoke detectors).
ii. Manual call points.
iii. Fire alarm control and indicating equipment.
iv. Fire alarm sounders.
v. Emergency communications systems.
vi. CCTV.
vii. Fire safety signage.
viii. Emergency lighting.
ix. Fire extinguishers.
x. Dry or wet fire mains and other firefighting equipment.
xi. Other interior facilities for the fire and rescue service.
xii. Emergency control rooms.
xiii. Location of hydrants outside the building.
xiv. Other exterior facilities for the fire and rescue service.
xv. The location of secure information boxes.
f. All active fire safety measures, including both of the following.
i. Sprinkler system(s) design, including isolating valves and control equipment.
ii. Smoke control system(s) (or heating, ventilation and air conditioning system with a smoke control function) design, including any air inlets, smoke outlets, mode of operation and control systems.
g. Any high risk areas (e.g. heating machinery) and particular hazards.
h. Plans of the building as built, showing the locations of the above.
i. Both of the following.
i. Specifications of any fire safety equipment provided, including all of the following.
• Operational details.
• Operators’ manuals.
• Software.
• System zoning.
• Routine inspection, testing and maintenance schedules.
ii. Records of any acceptance or commissioning tests.
j. Any other details appropriate for the specific building.

View this page on RegsUK