Section 19: Fire safety information Additional information for complex buildings

Additional information for complex buildings

19.6

A detailed record should be provided of both of the following.

a. The fire safety strategy.
b. Procedures for operating and maintaining any fire protection measures. This should include an outline cause and effect matrix/strategy for the building.
Further guidance is available in clause 9 and Annex H of BS 9999.

19.7

The records should include details of the following.

a. The fire safety strategy, including all assumptions in the design of the fire safety systems (such as fire load). Any risk assessments or risk analysis.
b. All assumptions in the design of the fire safety arrangements for the management of the building.
c. All of the following.
i. Escape routes (including occupant load and capacity of escape routes).
ii. Any provision to enable the evacuation of disabled people (including the location and mode of operation of evacuation lifts).
iii. Escape strategy (e.g. simultaneous or phased).
iv. Assembly points and/or muster stations.
d. All passive fire safety measures, including all of the following.
i. Compartmentation.
ii. Fire-separating elements.
iii. Fire resisting construction.
iv. Cavity barriers.
v. Fire doorsets, including fire doorsets fitted with a self-closing device and other doors relevant to the fire safety strategy, such as doors equipped with relevant hardware (e.g. electronic security locks).
vi. Fire dampers, fire and smoke dampers, and smoke control dampers.
vii. Fire shutters.
e. All of the following.
i. Fire detector heads (e.g. heat and smoke detectors).
ii. Manual call points.
iii. Fire alarm control and indicating equipment.
iv. Fire alarm sounders.
v. Emergency communications systems.
vi. CCTV.
vii. Fire safety signage.
viii. Emergency lighting.
ix. Fire extinguishers.
x. Dry or wet fire mains and other firefighting equipment.
xi. Other interior facilities for the fire and rescue service.
xii. Emergency control rooms.
xiii. Location of hydrants outside the building.
xiv. Other exterior facilities for the fire and rescue service.
xv. The location of secure information boxes.
f. All active fire safety measures, including both of the following.
i. Sprinkler system(s) design, including isolating valves and control equipment.
ii. Smoke control system(s) (or heating, ventilation and air conditioning system with a smoke control function) design, including any air inlets, smoke outlets, mode of operation and control systems.
g. Any high risk areas (e.g. heating machinery) and particular hazards.
h. Plans of the building as built, showing the locations of the above.
i. Both of the following.
i. Specifications of any fire safety equipment provided, including all of the following.
• Operational details.
• Operators’ manuals.
• Software.
• System zoning.
• Routine inspection, testing and maintenance schedules.
ii. Records of any acceptance or commissioning tests.
j. Any other details appropriate for the specific building.