Appendix E: Sprinklers

Appendix E: Sprinklers

Sprinkler systems

E1

Sprinkler systems installed in buildings can reduce the risk to life and significantly reduce the degree of damage caused by fire within a building.

E2

Further recommendations for the provision of sprinklers are provided in the following sections:

Volume 1 – Dwellings

Functional requirementParagraphTitle
B12.6Dwellinghouses with two or more storeys more than 4.5m above ground level
B12.23Loft conversions
B13.21Internal planning of multi-storey flats
B3Table B2Minimum periods of fire resistance
B37.4Sprinklers
B411.15Unprotected areas and fire resistance – portal frames
B411.21Methods for calculating acceptable unprotected area – sprinkler systems
B515.7Provision of firefighting shafts

Volume 2 – Buildings other than dwellings

Functional requirementParagraphTitle
B12.46Residential care homes – sprinkler systems
B13.21Width of escape stairs – phased evacuation
B15.46Shop store rooms
B37.7Raised storage areas
B3Table 8.1Maximum dimensions of building or compartment
B3Table B2Minimum periods of fire resistance
B38.14Sprinklers
B413.16Unprotected areas and fire resistance – portal frames
B413.22Methods for calculating acceptable unprotected area – sprinkler systems
B517.8Location of firefighting shafts
B518.11Provision of smoke outlets – mechanical smoke extract

Design of sprinkler systems

E3

Where required, sprinkler systems should be provided throughout the building or separated part, unless acting as a compensatory feature to address a specific risk. They should be designed and installed in accordance with the following.

a. For residential buildings, the requirements of BS 9251.
b. For non-residential buildings, or residential buildings outside the scope of BS 9251, the requirements of BS EN 12845, including the relevant hazard classification together with additional measures to improve system reliability and availability as described in Annex F of the standard.

NOTE: Any sprinkler system installed to satisfy the requirements of Part B of the Building Regulations should be provided with additional measures to improve system reliability and availability and is therefore to be regarded as a life safety system. However, there may be some circumstances in which additional measures to improve system reliability and availability specified in Annex F of BS EN 12845 are inappropriate or unnecessary.

E4

If the provisions in a building vary from those in this document, sprinkler protection can also sometimes be used as a compensatory feature.

BS 9251 makes additional recommendations when sprinklers are proposed as compensatory features.

Water supplies and pumps

E5

For non-residential sprinkler systems designed and installed to BS EN 12845, water supplies should consist of either of the following.

a. Two single water supplies complying with clause 9.6.1, independent of each other.
b. Two stored water supplies meeting all of the following conditions.
i. Gravity or suction tanks should satisfy all the requirements of clause 9.6.2(b), other than capacity.
ii. Any pump arrangements should comply with clause 10.2.
iii. In addition to meeting the requirements for inflow, either of the following should apply.
• The capacity of each tank should be at least half the specified minimum water volume of a single full capacity tank, appropriate to the hazard.
• One tank should be at least equivalent to half the specified water volume of a single full capacity tank, and the other shall not be less than the minimum volume of a reduced capacity tank (see clause 9.3.4) appropriate to the hazard.
The total capacity of the water supply in (iii), including any inflow for a reduced capacity tank, should be at least that of a single full holding capacity tank that complies with Table 9, Table 10 or clause 9.3.2.3, as appropriate to the hazard and pipework design.

E6

For the systems described in paragraph E5, both of the following apply if pumps are used to draw water from two tanks.

a. Each pump should be able to draw water from either tank.
b. Any one pump, or either tank, should be able to be isolated.

The sprinkler water supplies should not be used as connections for other services or other fixed firefighting systems.

View this page on RegsUK