Water supplies and pumps E6

E6

For the systems described in paragraph E5, both of the following apply if pumps are used to draw water from two tanks.

a. Each pump should be able to draw water from either tank.
b. Any one pump, or either tank, should be able to be isolated.

The sprinkler water supplies should not be used as connections for other services or other fixed firefighting systems.