Section 13: Resisting fire spread from one building to another Boundaries
Boundaries
13.4
The fire resistance of a wall depends on its distance from the relevant boundary (see Diagram 13.1). Separation distances are measured to boundaries to ensure that the location and design of buildings on adjoining sites have no influence on the building under consideration.
13.5
The boundary that a wall faces is the relevant boundary (Diagram 13.2). It may be one of the following.
a. The site boundary.
b. The centre line of a space where further development is unlikely, such as a road, railway, canal or river.
c. An assumed notional boundary between two buildings on the same site (Diagram 13.3) where either of the following conditions is met.
i. One or both of the buildings are in the ‘residential’ or ‘assembly and recreation’ purpose groups (purpose group 1, 2 or 5).
ii. The buildings will be operated/managed by different organisations.
Diagram 13.1 Principles of space separation

Diagram 13.2 Relevant boundary

Diagram 13.3 Notional boundary