Section 13: Resisting fire spread from one building to another Boundaries

Boundaries

13.4

The fire resistance of a wall depends on its distance from the relevant boundary (see Diagram 13.1). Separation distances are measured to boundaries to ensure that the location and design of buildings on adjoining sites have no influence on the building under consideration.

13.5

The boundary that a wall faces is the relevant boundary (Diagram 13.2). It may be one of the following.

a. The site boundary.
b. The centre line of a space where further development is unlikely, such as a road, railway, canal or river.
c. An assumed notional boundary between two buildings on the same site (Diagram 13.3) where either of the following conditions is met.
i. One or both of the buildings are in the ‘residential’ or ‘assembly and recreation’ purpose groups (purpose group 1, 2 or 5).
ii. The buildings will be operated/managed by different organisations.

Diagram 13.1 Principles of space separation

Diagram 13.1 Principles of space separation. Wording on the drawing: See para 13.4; Wall on or very close to the Wall not on, or not very close Wall su°ciently distant from relevant boundary: very limited to, but not su°ciently far from relevant boundary to be a amounts of unprotected area relevant boundary that it can be a 100% unprotected area wholly unprotected area; Fire resisting from inside: reduced insulation criterion; Fire resisting from both sides; No provision for fire resistance; Relevant boundary; Amount of unprotected area dependent on distance from relevant boundary
Diagram 13.1 Principles of space separation

Diagram 13.2 Relevant boundary

Diagram 13.2 Relevant boundary. Wording on the drawing: See para 13.5; NOTES:; This boundary is at less than 80 degrees to side C and is therefore relevant to side C; This diagram sets out the rules that apply in respect of a boundary for it to be considered as a relevant boundary.; < 80°; For a boundary to be relevant it should comply with one of the following:; C; This boundary is parallel to and therefore relevant to side B1; a. Coincide with the side of the building (A). b. Be parallel to the side of the building (B1 or B2). c. Be at an angle of maximum 80 degrees to the side of the building (C).; This boundary coincides with and is therefore relevant to side A; A B1; Building; B2; The boundary is parallel to side B2; But the relevant boundary may be the centre line of a road, railway, canal or river
Diagram 13.2 Relevant boundary

Diagram 13.3 Notional boundary

Diagram 13.3 Notional boundary. Wording on the drawing: See para 13.5; Site boundary; Building A Building B; Notional boundary; Compliance with the provisions for Compliance with the provisions for space separation in respect of building A space separation in respect of building B; NOTES:; The notional boundary should be set in the area between the two buildings using the following rules:; 1. The notional boundary is assumed to exist in the space between the buildings and is positioned so that one of the buildings would comply with the provisions for space separation having regard to the amount of its unprotected area. In practice, if one of the buildings is existing, the position of the boundary will be set by the space separation factors for that building.; 2. The siting of the new building, or the second building if both are new, can then be checked to see that it also complies, using the notional boundary as the relevant boundary for the second building.
Diagram 13.3 Notional boundary