Section 13: Resisting fire spread from one building to another

Section 13: Resisting fire spread from one building to another

Introduction

13.1

The following assumptions enable a reasonable standard of resistance to the spread of fire to be specified.

a. The size of a fire depends on the compartmentation within the building. A fire may involve a complete compartment, but will not spread to other compartments.
b. The intensity of fire is related to the building use, but can be moderated by a sprinkler system.
c. Fires in ‘residential’ and ‘assembly and recreation’ buildings (purposes groups 1, 2 and 5) represent a greater risk to life.
d. A building on the far side of the relevant boundary meets both of the following conditions.
i. Has a similar elevation to the one in question.
ii. Is at the same distance from the common boundary.
e. The radiated heat passing through any part of the fire resisting external wall may be discounted.

13.2

Where regulation 7(2) applies, that regulation prevails over the provisions within this section.

13.3

If a reduced separation distance between buildings, or increased amount of unprotected area, is required, smaller compartments should be considered.

Boundaries

13.4

The fire resistance of a wall depends on its distance from the relevant boundary (see Diagram 13.1). Separation distances are measured to boundaries to ensure that the location and design of buildings on adjoining sites have no influence on the building under consideration.

13.5

The boundary that a wall faces is the relevant boundary (Diagram 13.2). It may be one of the following.

a. The site boundary.
b. The centre line of a space where further development is unlikely, such as a road, railway, canal or river.
c. An assumed notional boundary between two buildings on the same site (Diagram 13.3) where either of the following conditions is met.
i. One or both of the buildings are in the ‘residential’ or ‘assembly and recreation’ purpose groups (purpose group 1, 2 or 5).
ii. The buildings will be operated/managed by different organisations.

Diagram 13.1 Principles of space separation

Diagram 13.1 Principles of space separation. Wording on the drawing: See para 13.4; Wall on or very close to the Wall not on, or not very close Wall su°ciently distant from relevant boundary: very limited to, but not su°ciently far from relevant boundary to be a amounts of unprotected area relevant boundary that it can be a 100% unprotected area wholly unprotected area; Fire resisting from inside: reduced insulation criterion; Fire resisting from both sides; No provision for fire resistance; Relevant boundary; Amount of unprotected area dependent on distance from relevant boundary
Diagram 13.1 Principles of space separation

Diagram 13.2 Relevant boundary

Diagram 13.2 Relevant boundary. Wording on the drawing: See para 13.5; NOTES:; This boundary is at less than 80 degrees to side C and is therefore relevant to side C; This diagram sets out the rules that apply in respect of a boundary for it to be considered as a relevant boundary.; < 80°; For a boundary to be relevant it should comply with one of the following:; C; This boundary is parallel to and therefore relevant to side B1; a. Coincide with the side of the building (A). b. Be parallel to the side of the building (B1 or B2). c. Be at an angle of maximum 80 degrees to the side of the building (C).; This boundary coincides with and is therefore relevant to side A; A B1; Building; B2; The boundary is parallel to side B2; But the relevant boundary may be the centre line of a road, railway, canal or river
Diagram 13.2 Relevant boundary

Diagram 13.3 Notional boundary

Diagram 13.3 Notional boundary. Wording on the drawing: See para 13.5; Site boundary; Building A Building B; Notional boundary; Compliance with the provisions for Compliance with the provisions for space separation in respect of building A space separation in respect of building B; NOTES:; The notional boundary should be set in the area between the two buildings using the following rules:; 1. The notional boundary is assumed to exist in the space between the buildings and is positioned so that one of the buildings would comply with the provisions for space separation having regard to the amount of its unprotected area. In practice, if one of the buildings is existing, the position of the boundary will be set by the space separation factors for that building.; 2. The siting of the new building, or the second building if both are new, can then be checked to see that it also complies, using the notional boundary as the relevant boundary for the second building.
Diagram 13.3 Notional boundary

Unprotected areas and fire resistance

13.6

Parts of an external wall with less fire resistance than the appropriate amount given in Appendix B, Table B2, are called unprotected areas.

13.7

Where a fire resisting external wall has an external surface material that is worse than class B-s3, d2 and is more than 1mm thick, that part of the wall should be classified as an unprotected area equating to half its area (Diagram 13.4).

External walls on, and within 1000mm of, the relevant boundary

13.8

Unprotected areas should meet the conditions in Diagram 13.5 and the rest of the wall should be fire resisting from both sides.

External surface materials facing the boundary should be class B-s3, d2 or better.

External walls 1000mm or more from the relevant boundary

13.9

Unprotected area should not exceed the result given by one of the methods in paragraph 13.17, and the rest of the wall (if any) should be fire resisting but only from the inside of the building.

External walls of protected stairways

13.10

Exclude external walls of stairways in a protected shaft when assessing unprotected areas (see Diagram 3.3)

Diagram 13.4 Status of materials achieving class B-s3, d2 or worse as unprotected area

Diagram 13.4 Status of materials achieving class B-s3, d2 or worse as unprotected area. Wording on the drawing: See para 13.7; b; Area of fire resisting wall with materials more than 1mm thick and with a reaction to fire performance worse than class B-s3, d2 = a˜b; Area of wall counted as unprotected area = 0.5a˜b; Area of fire resisting wall with materials having a reaction to fire performance better than class B-s3, d2; a
Diagram 13.4 Status of materials achieving class B-s3, d2 or worse as unprotected area

Small unprotected areas

13.11

In an otherwise protected wall, small unprotected areas may be ignored where they meet the conditions in Diagram 13.5.

Diagram 13.5 Small unprotected areas that may be disregarded in assessing the separation distance from the boundary

Diagram 13.5 Small unprotected areas that may be disregarded in assessing the separation distance from the boundary. Wording on the drawing: See para 13.11; Roof; Roofs pitched at an angle of less than 70 degrees may be disregarded for a a separation distance purposes; b; b; a; b b; The unprotected area of the external wall of a stairway forming a protected shaft may be disregarded for separation distance purposes; b b; b a; Compartment; Compartment wall; floor; Dimensional restrictions; Represents an unprotected area of not more than 1m2 which may consist of two or more smaller areas within an area of 1000mm˜1000mm; a; 4000mm minimum distance; b; 1500mm minimum distance; Represents an area of not more than 0.1m2
Diagram 13.5 Small unprotected areas that may be disregarded in assessing the separation distance from the boundary

Large uncompartmented buildings

13.12

For the purposes of assessing unprotected area, parts of walls of uncompartmented buildings that are more than 30m above mean ground level may be ignored.

Canopies

13.13

Where both of the following apply, separation distances may be determined from the wall rather than from the edge of the canopy (Diagram 13.6).

a. The canopy is attached to the side of a building.
b. The edges of the canopy are a minimum of 2m from the relevant boundary.

Canopies that fall within class 6 or class 7 of Schedule 2 to the regulations (Exempt Buildings and Work) are exempt from the Building Regulations.

13.14

Space separation may be disregarded if a canopy is all of the following.

a. Free-standing.
b. Above a limited risk or controlled hazard, for example over petrol pumps.
c. A minimum of 1000mm from the relevant boundary.

Diagram 13.6 The effect of a canopy on separation distance

Diagram 13.6 The effect of a canopy on separation distance. Wording on the drawing: See para 13.13; Canopy arrangement; Loading bay arrangement; 2m min. Canopy; 2m min.; Relevant boundary; Relevant Loading platform boundary; Building line Distance to; Building line; Distance to; relevant boundary; relevant boundary; measured from; measured from; building line; building line; NOTE: Projections from the building line, such as a canopy or a loading platform, can be ignored when assessing separation distance. This does not apply where the canopy is enclosed by side walls.
Diagram 13.6 The effect of a canopy on separation distance

Roofs

13.15

Roofs with a pitch of more than 70 degrees to the horizontal should be assessed in accordance with this section. Vertical parts of a pitched roof, such as dormer windows, should be included, only if the slope of the roof exceeds 70 degrees.

It is a matter of judgement whether a continuous run of dormer windows that occupies most of a steeply pitched roof should be treated as a wall rather than a roof.

Portal frames

13.16

Portal frames are often used in single storey industrial and commercial buildings where there may be no need for fire resistance of the structure (requirement B3). However, where a portal framed building is near a relevant boundary, the external wall near the boundary may need fire resistance to restrict the spread of fire between buildings. It is generally accepted that a portal frame acts as a single structural element because of the moment-resisting connections used, especially at the column/rafter joints. Thus, in cases where the external wall of the building cannot be wholly unprotected, the rafter members of the frame, as well as the column members, may need to be fire protected. The design method for this is set out in SCI Publication P313.

NOTE: The recommendations in the SCI publication for designing the foundation to resist overturning do not need to be followed if the building is fitted with a sprinkler system in accordance with Appendix E.

NOTE: Normally, portal frames of reinforced concrete can support external walls requiring a similar degree of fire resistance without specific provision at the base to resist overturning.

NOTE: Existing buildings may have been designed to comply with all of the following guidance, which is also acceptable.

a. The column members are fixed rigidly to a base of sufficient size and depth to resist overturning.
b. There is brick, block or concrete protection to the columns up to a protected ring beam providing lateral support.
c. There is some form of roof venting to give early heat release. (The roof venting could be, for example, PVC rooflights covering some 10% of the floor area and evenly spaced over the floor area.)

Methods for calculating acceptable unprotected area

13.17

Two simple methods are given for calculating the acceptable amount of unprotected area in an external wall that is a minimum of 1000mm from any point on the relevant boundary. More precise methods are described in BRE report BR 187 and may be used instead. When using BR 187 the following radiation intensity at each unprotected area should be assumed.

a. 84kW/m2 if the purpose group of the building is ‘residential’ (purpose groups 1 or 2), ‘office’ (purpose group 3) or ‘assembly and recreation’ (purpose group 5) or if the building is an opensided multi-storey car park (purpose group 7(b)).
b. 168kW/m2 if the purpose group of the building is ‘shop and commercial’ (purpose group 4), ‘industrial’ (purpose group 6) or ‘storage and other non-residential’ (purpose group 7(a)).

Method 1

13.18

This method applies to small buildings intended to be used for ‘residential (other)’ purposes.

13.19

The building should not exceed three storeys in height (excluding basements) or 24m in length. Each side of the building should meet the limits stated in Diagram 13.7. Any small unprotected areas falling within the limits shown in Diagram 13.5 can be ignored.

Diagram 13.7 Permitted unprotected areas in small residential buildings

Diagram 13.7 Permitted unprotected areas in small residential buildings. Wording on the drawing: See para 13.19; 24m max.; Minimum distance (a) Maximum total area of between side of building unprotected areas (m2) and relevant boundary (m); 1 5.6 2 12 3 18 4 24 5 30 6 No limit; a; Relevant boundary
Diagram 13.7 Permitted unprotected areas in small residential buildings

Method 2

13.20

This method may be used for buildings or compartments intended for any use and for which method 1 is not appropriate.

13.21

Except for an open-sided car park in purpose group 7(b) (see paragraph 11.2), the building should not exceed 10m in height. Each side of the building should meet the limits in Table 13.1. Areas falling within the limits in Diagram 13.5 can be ignored.

Table 13.1 Permitted unprotected areas in small buildings or compartments

Minimum distance between side of building and relevant boundary (m)

Maximum total percentage of unprotected area (%)

(3)

Purpose groups

Residential, office, assembly and recreation

(1)

Shop and commercial, industrial, storage and other non-residential

(2)

Not applicable14
128
2.5520
51040
7.51560
102080
12.525100

NOTES:

1. Intermediate values may be obtained by interpolation.
2. For buildings fitted with an automatic sprinkler system, see paragraph 13.22.
3. For open-sided car parks in purpose group 7(b), the distances set out in column (1) may be used instead of those in column (2).
4. The total percentage of unprotected area is found by dividing the total unprotected area by the area of a rectangle that encloses all the unprotected areas, and multiplying the result by 100.

Sprinkler systems

13.22

If a building is fitted throughout with a sprinkler system in accordance with Appendix E, either of the following is permitted.

a. The boundary distance can be halved, to a minimum distance of 1m.
b. The amount of unprotected area can be doubled.

Atrium buildings

13.23

If a building contains one or more atria, the recommendations in clause B8 of BS 9999 should be followed.