Appendix C: Fire doorsets C1
C1
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: C1 (2029 amendment).
All fire doorsets should have the performance shown in Table C1, based on one of the following.
a. Fire resistance in terms of integrity, for a period of minutes, when tested to BS 476-22, e.g. FD 30. A suffix (S) is added for doorsets where restricted smoke leakage at ambient temperatures is needed.
b. As determined with reference to Commission Decision 2000/367/EC regarding the classification of the resistance to fire performance of construction products, construction works and parts thereof. All fire doorsets should be classified in accordance with BS EN 13501-2, tested to the relevant European method from the following.
i. BS EN 1634-1.
ii. BS EN 1634-2.
iii. BS EN 1634-3.
c. As determined with reference to European Parliament and Council Directive 95/16/EC (which applies to lifts that permanently serve buildings and constructions and specified safety components) on the approximation of laws of Member States relating to lifts (‘Lifts Directive’) implementing the Lifts Regulations 1997 (SI 1997/831) and calling upon the harmonised standard BS EN 81-58.