Appendix C: Fire doorsets

Appendix C: Fire doorsets

Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: Appendix C: Fire doorsets (2029 amendment).

C1

Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: C1 (2029 amendment).

All fire doorsets should have the performance shown in Table C1, based on one of the following.

a. Fire resistance in terms of integrity, for a period of minutes, when tested to BS 476-22, e.g. FD 30. A suffix (S) is added for doorsets where restricted smoke leakage at ambient temperatures is needed.
b. As determined with reference to Commission Decision 2000/367/EC regarding the classification of the resistance to fire performance of construction products, construction works and parts thereof. All fire doorsets should be classified in accordance with BS EN 13501-2, tested to the relevant European method from the following.
i. BS EN 1634-1.
ii. BS EN 1634-2.
iii. BS EN 1634-3.
c. As determined with reference to European Parliament and Council Directive 95/16/EC (which applies to lifts that permanently serve buildings and constructions and specified safety components) on the approximation of laws of Member States relating to lifts (‘Lifts Directive’) implementing the Lifts Regulations 1997 (SI 1997/831) and calling upon the harmonised standard BS EN 81-58.

C2

Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: C2 (2029 amendment).

The performance requirement is in terms of integrity (E) for a period of minutes. An additional classification of Sa is used for all doors where restricted smoke leakage at ambient temperatures is needed.

C3

Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: C3 (2029 amendment).

The requirement is for test exposure from each side of the doorset separately. The exception is lift doors, which are tested from the landing side only.

C4

Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: C4 (2029 amendment).

Any test evidence used to verify the fire resistance rating of a doorset or shutter should be checked to ensure both of the following.

a. It adequately demonstrates compliance.
b. It is applicable to the complete installed assembly. Small differences in detail may significantly affect the rating.

Until relevant harmonised product standards are published, for the purposes of meeting the Building Regulations, products tested in accordance with BS EN 1634-1 (with or without pre-fire test mechanical conditioning) that achieve the minimum performance in Table C1 will be deemed to satisfy the provisions.

C5

Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: C5 (2029 amendment).

All fire doorsets, including to flat entrances and between a dwellinghouse and an integral garage, should be fitted with a self-closing device, except for all of the following.

a. Fire doorsets to cupboards.
b. Fire doorsets to service ducts normally locked shut.
c. Fire doorsets within flats and dwellinghouses.

C6

Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: C6 (2029 amendment).

If a self-closing device would be considered to interfere with the normal approved use of the building, self-closing fire doors may be held open by one of the following.

a. A fusible link, but not if the doorset is in an opening provided as a means of escape unless it complies with paragraph C7.
b. An automatic release mechanism activated by an automatic fire detection and alarm system.
c. A door closer delay device.

C7

Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: C7 (2029 amendment).

Two fire doorsets may be fitted in the same opening if each door is capable of closing the opening, so the total fire resistance is the sum of their individual resistances. If the opening is provided as a means of escape, both fire doorsets should be self-closing.

If one fire doorset is capable of being easily opened by hand and has a minimum of 30 minutes’ fire resistance, the other fire doorset should comply with both of the following.

a. Be fitted with an automatic self-closing device.
b. Be held open by a fusible link.

C8

Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: C8 (2029 amendment).

Fire doorsets often do not provide any significant insulation. Unless providing both integrity and insulation in accordance with Appendix B, Table B1, a maximum of 25% of the length of a compartment wall should consist of door openings.

Where it is practicable to maintain a clear space on both sides of the doorway, the above percentage may be greater.

C9

Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: C9 (2029 amendment).

Rolling shutters should be capable of manual opening and closing for firefighting purposes (see Section 17). Rolling shutters across a means of escape should only be released by a heat sensor, such as a fusible link or electric heat detector, in the immediate vicinity of the door.

Unless a shutter is also intended to partially descend as part of a boundary to a smoke reservoir, shutters across a means of escape should not be closed by smoke detectors or a fire alarm system.

C10

Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: C10 (2029 amendment).

Unless shown to be satisfactory when tested as part of a fire doorset assembly, the essential components of any hinge on which a fire door is hung should be made entirely from materials that have a minimum melting point of 800°C.

C11

Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: C11 (2029 amendment).

Except for doorsets listed in paragraph C12, all fire doorsets should be marked with one of the following fire safety signs, complying with BS 5499-5, as appropriate.

a. To be kept closed when not in use – mark ‘Fire door keep shut’.
b. To be kept locked when not in use – mark ‘Fire door keep locked shut’.
c. Held open by an automatic release mechanism or free swing device – mark ‘Automatic fire door keep clear’.

All fire doorsets should be marked on both sides, except fire doorsets to cupboards and service ducts, which should be marked on the outside.

C12

Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: C12 (2029 amendment).

The following fire doorsets are not required to comply with paragraph C11.

a. Doors to and within flats and dwellinghouses.
b. Bedroom doors in ‘residential (other)’ (purpose group 2(b)) premises.
c. Lift entrance/landing doors.

C13

Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: C13 (2029 amendment).

The performance of some doorsets set out in Table C1 is linked to the minimum periods of fire resistance for elements of structure given in Tables B1 and B2. Limitations on the use of uninsulated glazing in fire doorsets are given in Table B3.

C14

Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: C14 (2029 amendment).

Recommendations for the specification, design, construction, installation and maintenance of fire doorsets constructed with non-metallic door leaves are given in BS 8214.

Guidance on timber fire resisting doorsets, in relation to the new European test standard, may be found in Timber Fire Resisting Doorsets: Maintaining Performance Under the New European Test Standard published by the Timber Research and Development Association (TRADA).

Guidance for metal doors is given in Code of Practice for Fire Resisting Metal Doorsets published by the Door and Shutter Manufacturers’ Association (DSMA).

C15

Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: C15 (2029 amendment).

Hardware used on fire doors can significantly affect their performance in a fire. Notwithstanding the guidance in this approved document, guidance is available in Hardware for Fire and Escape Doors published by the Door and Hardware Federation (DHF) and Guild of Architectural Ironmongers (GAI).

Table C1 Provisions for fire doorsets

Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: Table C1 Provisions for fire doorsets (2029 amendment).

Position of doorMinimum fire resistance of door in terms of integrity (minutes) when tested to the relevant European standard(1) Minimum fire resistance of door in terms of integrity (minutes) when tested to BS 476-22
1. In a compartment wall separating buildings
Same as for the wall in which the door is fitted, but a minimum of 60 minutesSame as for the wall in which the door is fitted, but a minimum of 60 minutes
2. In a compartment wall:
a. if it separates a flat from a space in common use
E 30 Sa(2) FD 30 S(2)
b. enclosing a protected shaft forming a stairway or an evacuation shaft wholly or partly above the adjoining ground in a building used for flats, other residential, assembly and recreation, or office purposes
E 30 Sa(2) FD 30 S(2)
c. enclosing a protected shaft forming a stairway or an evacuation shaft not described in (b) above
Half the period of fire resistance of the wall in which it is fitted, but 30 minutes minimum and with suffix Sa(2) Half the period of fire resistance of the wall in which it is fitted, but 30 minutes minimum and with suffix S(2)
d. enclosing a protected shaft forming a lift or service shaft
Half the period of fire resistance of the wall in which it is fitted, but 30 minutes minimumHalf the period of fire resistance of the wall in which it is fitted, but 30 minutes minimum
e. not described in (a), (b), (c) or (d) above.
Same as for the wall in which it is fitted, but add Sa(2) if the door is used for progressive horizontal evacuation under the guidance to requirement B1Same as for the wall in which it is fitted, but add S(2) if the door is used for progressive horizontal evacuation under the guidance to requirement B1
3. In a compartment floor
Same as for the floor in which it is fittedSame as for the floor in which it is fitted
4. Forming part of the enclosures of:
a. protected stairway or evacuation shaft (except as described in item 9 or 11(b) below)
E 30 Sa (2) FD 30 S(2)
b. a lift shaft (see paragraph 5.34(b) that does not form a protected shaft in 2(b), (c) or (d) above.
E 30FD 30
5. Forming part of the enclosure of:
a. a protected lobby approach (or protected corridor) to a stairway or an evacuation shaft
E 30 Sa (2) FD 30 S(2)
b. any other protected corridor
E 20 Sa (2) FD 20 S(2)
c. a protected lobby approach to a lift shaft (paragraphs 5.37 to 5.39).
E 30 Sa (2) FD 30 S(2)
6. Giving access to an external escape route
E 30FD 30
7. Sub-dividing:
a. corridors connecting alternative exits
E 20 Sa (2) FD 20 S(2)
b. dead-end portions of corridors from the remainder of the corridor.
E 20 Sa (2) FD 20 S(2)
8. Any door within a cavity barrier
E 30FD 30
9. Any door that forms part of the enclosure to a protected entrance hall or protected landing in a flat
E 20FD 20
10. Any door that forms part of the enclosure:
a. to a place of special fire hazard
E 30FD 30
b. to ancillary accommodation in care homes (see paragraph 2.4).
E 30FD 30
11. In a dwellinghouse:
a. between a dwellinghouse and a garage
E 30 Sa (2) FD 30 S(2)
b. forming part of the enclosures to a protected stairway in a single family dwellinghouse
E 20FD 20
c. within any fire resisting construction in a dwellinghouse not described elsewhere in this table.
E 20FD 20

NOTES:

1. Classified in accordance with BS EN 13501-2. National classifications do not necessarily equate with European classifications, therefore products cannot typically assume a European class unless they have been tested accordingly.
2. Unless pressurisation techniques that comply with BS EN 12101-6 are used, these doors should also comply with one of the following conditions.
a. Have a leakage rate not exceeding 3m3/m/hour (from head and jambs only) when tested at 25Pa under BS 476-31.1.
b. Meet the additional Sa classification when tested to BS EN 1634-3.