Appendix C: Fire doorsets C11
C11
Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: C11 (2029 amendment).
Except for doorsets listed in paragraph C12, all fire doorsets should be marked with one of the following fire safety signs, complying with BS 5499-5, as appropriate.
a. To be kept closed when not in use – mark ‘Fire door keep shut’.
b. To be kept locked when not in use – mark ‘Fire door keep locked shut’.
c. Held open by an automatic release mechanism or free swing device – mark ‘Automatic fire door keep clear’.
All fire doorsets should be marked on both sides, except fire doorsets to cupboards and service ducts, which should be marked on the outside.