Appendix C: Fire doorsets (2029 amendment) C4 (2029 amendment)
C4 (2029 amendment)
2029 amendment: takes effect on 2 September 2029. Until then the current text applies: C4.
Any test evidence used to verify the fire resistance rating of a doorset or shutter should be checked to ensure both of the following.
a. It adequately demonstrates compliance.
b. It is applicable to the complete installed assembly. Small differences in detail might significantly affect the rating and should be tested or assessed in accordance with paragraphs B1 to B5.
Until relevant harmonised product standards are published, for the purposes of meeting the Building Regulations, products or systems tested in accordance with BS EN 1634-1 (with or without pre-fire test mechanical conditioning) or assessed as being capable of meeting a performance classification based on the recommendations of paragraphs B1 to B5 that achieve the minimum performance in Table C1 will be deemed to satisfy the provisions.