Appendix C: Fire doorsets (2029 amendment)

Appendix C: Fire doorsets (2029 amendment)

2029 amendment: takes effect on 2 September 2029. Until then the current text applies: Appendix C: Fire doorsets.

C1 (2029 amendment)

2029 amendment: takes effect on 2 September 2029. Until then the current text applies: C1.

All fire doorsets should have the performance shown in Table C1, based on one of the following.

a. Fire doorsets should be classified in accordance with BS EN 13501-2, as determined with reference to Commission Decision 2000/367/EC regarding the classification of the resistance to fire performance of construction products, construction works and parts thereof, when tested to the relevant European method from the following.
i. BS EN 1634-1.
ii. BS EN 1634-2.
iii. BS EN 1634-3.
b. Fire doorsets may have their performance on fire resistance assessed, following the recommendations of paragraphs B1 to B5, as being capable of meeting a performance classification. In those situations the performance classifications given in Table C1 may be used, presented in terms of integrity, for a period of minutes, when tested to a relevant standard.
c. As determined with reference to European Parliament and Council Directive 95/16/EC (which applies to lifts that permanently serve buildings and constructions and specified safety components) on the approximation of laws of Member States relating to lifts (‘Lifts Directive’) implementing the Lifts Regulations 1997 (SI 1997/831) and calling upon the harmonised standard BS EN 81-58.

C2 (2029 amendment)

2029 amendment: takes effect on 2 September 2029. Until then the current text applies: C2.

The performance requirement is in terms of integrity (E) for a period of minutes. An additional classification of Sa is used for all doors where restricted smoke leakage at ambient temperatures is needed.

C3 (2029 amendment)

2029 amendment: takes effect on 2 September 2029. Until then the current text applies: C3.

The requirement is for test exposure from each side of the doorset separately. The exception is lift doors, which are tested from the landing side only.

C4 (2029 amendment)

2029 amendment: takes effect on 2 September 2029. Until then the current text applies: C4.

Any test evidence used to verify the fire resistance rating of a doorset or shutter should be checked to ensure both of the following.

a. It adequately demonstrates compliance.
b. It is applicable to the complete installed assembly. Small differences in detail might significantly affect the rating and should be tested or assessed in accordance with paragraphs B1 to B5.
Until relevant harmonised product standards are published, for the purposes of meeting the Building Regulations, products or systems tested in accordance with BS EN 1634-1 (with or without pre-fire test mechanical conditioning) or assessed as being capable of meeting a performance classification based on the recommendations of paragraphs B1 to B5 that achieve the minimum performance in Table C1 will be deemed to satisfy the provisions.

C5 (2029 amendment)

2029 amendment: takes effect on 2 September 2029. Until then the current text applies: C5.

All fire doorsets, including to flat entrances and between a dwellinghouse and an integral garage, should be fitted with a self-closing device, except for all of the following.

a. Fire doorsets to cupboards.
b. Fire doorsets to service ducts normally locked shut.
c. Fire doorsets within flats and dwellinghouses.

C6 (2029 amendment)

2029 amendment: takes effect on 2 September 2029. Until then the current text applies: C6.

If a self-closing device would be considered to interfere with the normal approved use of the building, self-closing fire doors may be held open by one of the following.

a. A fusible link, but not if the doorset is in an opening provided as a means of escape unless it complies with paragraph C7.
b. An automatic release mechanism activated by an automatic fire detection and alarm system.
c. A door closer delay device.

C7 (2029 amendment)

2029 amendment: takes effect on 2 September 2029. Until then the current text applies: C7.

Two fire doorsets may be fitted in the same opening if each door is capable of closing the opening, so the total fire resistance is the sum of their individual resistances. If the opening is provided as a means of escape, both fire doorsets should be self-closing.

If one fire doorset is capable of being easily opened by hand and has a minimum of 30 minutes’ fire resistance, the other fire doorset should comply with both of the following.

a. Be fitted with an automatic self-closing device.
b. Be held open by a fusible link.

C8 (2029 amendment)

2029 amendment: takes effect on 2 September 2029. Until then the current text applies: C8.

Fire doorsets often do not provide any significant insulation. Unless providing both integrity and insulation in accordance with Appendix B, Table B1, a maximum of 25% of the length of a compartment wall should consist of door openings.

Where it is practicable to maintain a clear space on both sides of the doorway, the above percentage may be greater.

C9 (2029 amendment)

2029 amendment: takes effect on 2 September 2029. Until then the current text applies: C9.

Rolling shutters should be capable of manual opening and closing for firefighting purposes (see Section 17). Rolling shutters across a means of escape should only be released by a heat sensor, such as a fusible link or electric heat detector, in the immediate vicinity of the door.

Unless a shutter is also intended to partially descend as part of a boundary to a smoke reservoir, shutters across a means of escape should not be closed by smoke detectors or a fire alarm system.

C10 (2029 amendment)

2029 amendment: takes effect on 2 September 2029. Until then the current text applies: C10.

Unless shown to be satisfactory when tested as part of a fire doorset assembly, the essential components of any hinge on which a fire door is hung should be made entirely from materials that have a minimum melting point of 800°C.

C11 (2029 amendment)

2029 amendment: takes effect on 2 September 2029. Until then the current text applies: C11.

Except for doorsets listed in paragraph C12, all fire doorsets should be marked with one of the following fire safety signs, complying with BS 5499-5, as appropriate.

a. To be kept closed when not in use – mark ‘Fire door keep shut’.
b. To be kept locked when not in use – mark ‘Fire door keep locked shut’.
c. Held open by an automatic release mechanism or free swing device – mark ‘Automatic fire door keep clear’.

C12 (2029 amendment)

2029 amendment: takes effect on 2 September 2029. Until then the current text applies: C12.

The following fire doorsets are not required to comply with paragraph C11.

a. Doors to and within flats and dwellinghouses.
b. Bedroom doors in ‘residential (other)’ (purpose group 2(b)) premises.
c. Lift entrance/landing doors.

C13 (2029 amendment)

2029 amendment: takes effect on 2 September 2029. Until then the current text applies: C13.

The performance of some doorsets set out in Table C1 is linked to the minimum periods of fire resistance for elements of structure given in Tables B1 and B2. Limitations on the use of uninsulated glazing in fire doorsets are given in Table B3.

C14 (2029 amendment)

2029 amendment: takes effect on 2 September 2029. Until then the current text applies: C14.

Recommendations for the specification, design, construction, installation and maintenance of fire doorsets constructed with non-metallic door leaves are given in BS 8214.

Guidance on timber fire resisting doorsets, in relation to the new European test standard, may be found in Timber Fire Resisting Doorsets: Maintaining Performance Under the New European Test Standard published by the Timber Research and Development Association (TRADA).

Guidance for metal doors is given in Code of Practice for Fire Resisting Metal Doorsets published by the Door and Shutter Manufacturers’ Association (DSMA).

C15 (2029 amendment)

2029 amendment: takes effect on 2 September 2029. Until then the current text applies: C15.

Hardware used on fire doors can significantly affect their performance in a fire. Notwithstanding the guidance in this approved document, guidance is available in Hardware for Fire and Escape Doors published by the Door and Hardware Federation (DHF) and Guild of Architectural Ironmongers (GAI).

Table C1 Provisions for fire doorsets (2029 amendment)

2029 amendment: takes effect on 2 September 2029. Until then the current text applies: Table C1 Provisions for fire doorsets.

Position of doorsetMinimum fire resistance of doorset in terms of integrity (minutes) when tested and classified to the relevant European standard(1) or assessed following the recommendations of paragraph B1 to B5 and C1(2)
1.In a compartment wall separating buildingsSame as for the wall in which the door is fitted, but a minimum of 60 minutes
2.In a compartment wall:
a. if it separates a flat from a space in common use
30 minutes Sa(3)
b. enclosing a protected shaft forming a stairway or an evacuation shaft wholly or partly above the adjoining ground in a building used for flats, other residential, assembly and recreation, or office purposes
30 minutes Sa(3)
c. enclosing a protected shaft forming a stairway or an evacuation shaft not described in (b) above
Half the period of fire resistance of the wall in which it is fitted, but 30 minutes minimum and with suffix Sa(3)
d. enclosing a protected shaft forming a lift or service shaft
Half the period of fire resistance of the wall in which it is fitted, but 30 minutes minimum
e. not described in (a), (b), (c) or (d) above.
Same as for the wall in which it is fitted, but add Sa(3) if the door is used for progressive horizontal evacuation under the guidance to requirement B1
3.In a compartment floor Same as for the floor in which it is fitted
4.Forming part of the enclosures of:
a. a protected stairway or evacuation shaft (except as described in item 9 or 11(b) below)
30 minutes Sa(3)
b. a lift shaft (see paragraph 5.34b) that does not form a protected shaft in 2(b), (c) or (d) above.
30 minutes
5.Forming part of the enclosure of:
a. a protected lobby approach (or protected corridor) to a stairway or an evacuation shaft.
30 minutes Sa(3)
b. any other protected corridor
20 minutes Sa(3)
c. a protected lobby approach to a lift shaft (paragraphs 5.37 to 5.39).
30 minutes Sa(3)
6.Giving access to an external escape route 30 minutes
7.Sub-dividing:
a. corridors connecting alternative exits
20 minutes Sa (3)
b. dead-end portions of corridors from the remainder of the corridor.
20 minutes Sa(3)
8.Any door within a cavity barrier 30 minutes
9.Any door that forms part of the enclosure to a protected entrance hall or protected landing in a flat 20 minutes
10.Any door that forms part of the enclosure:
a. to a place of special fire hazard
30 minutes
b. to ancillary accommodation in care homes (see paragraph 2.44).
30 minutes
11.In a dwellinghouse:
a. between a dwellinghouse and a garage
30 minutes Sa(3)
b. forming part of the enclosures to a protected stairway in a single family dwellinghouse
20 minutes
c. within any fire resisting construction in a dwellinghouse not described elsewhere in this table.
20 minutes

NOTES:

1. Classified in accordance with BS EN 13501-2. In the European classification ‘E’ is the resistance to fire in terms of integrity. Products or systems cannot typically assume a European class unless they have been tested and classified accordingly.
2. When assessed as being capable of meeting a performance classification, products or systems should follow the relevant test standards to indicate their fire resistance performance in terms of integrity for a period of minutes, when following the recommendations of paragraphs B1 to B5.
3. Unless pressurisation techniques that comply with BS EN 12101-6 are used, these doors should also be evidenced to match in performance the additional Sa classification when tested to BS EN 1634-3.