Appendix C: Fire doorsets C8

C8

Applies until 1 September 2029. From 2 September 2029 the 2029 amendment applies instead: C8 (2029 amendment).

Fire doorsets often do not provide any significant insulation. Unless providing both integrity and insulation in accordance with Appendix B, Table B1, a maximum of 25% of the length of a compartment wall should consist of door openings.

Where it is practicable to maintain a clear space on both sides of the doorway, the above percentage may be greater.