Section 11: Special provisions for car parks Car parks that are not open-sided

Car parks that are not open-sided

11.3

For car parks that do not have the ventilation set out in paragraph 11.2, the required fire resistance is given in Appendix B, Table B2. Ventilation should be either natural or mechanical. See Approved Document F for additional guidance on ventilation of car parks.

Natural ventilation

11.4

Each storey should be ventilated by permanent openings at each car parking level. The openings can be at ceiling level. The aggregate free vent area should be a minimum of 1/40 of that level’s floor area, at least half of which should be provided equally by two opposite walls (1/160 on each side). The remaining free area can be distributed wherever possible.

Mechanical ventilation

11.5

If the minimum standard of natural ventilation is not possible, a system of mechanical ventilation should be provided that complies with all of the following.

a. The system should be both of the following.
i. Independent of any other ventilating system (other than any system that provides day to day ventilation to the car park).
ii. Designed to operate at 10 air changes per hour during a fire.
b. The system should run in two parts, each of which is:
i. capable of extracting 50% of the rates set out in item (a)
ii. able to operate alone or with the other part
iii. provided with an independent power supply capable of operating if the main supply fails.
c. 50% of the outlets should be at high level and 50% at low level.
d. The system should use E, I and S ductwork in accordance with BS EN 1366-8.

For further information on equipment for removing hot smoke, refer to BS EN 12101-3. An alternative method of providing smoke ventilation from enclosed car parks is given in BS 7346-7.