Section 12: Resisting fire spread over external walls Combustibility of external walls
Combustibility of external walls
12.3
The external walls of buildings other than those described in regulation 7(4) of the Building Regulations should achieve either of the following.
12.4
In relation to buildings of any height or use, consideration should be given to the choice of materials (including their extent and arrangement) used for the external wall, or attachments to the wall (e.g. balconies, etc.), to reduce the risk of fire spread over the wall.
External surfaces
12.5
The external surfaces (i.e. outermost external material) of external walls should comply with the provisions in Table 12.1. The provisions in Table 12.1 apply to each wall individually in relation to its proximity to the relevant boundary.
Table 12.1 Reaction to fire performance of external surface of walls
| Building type | Building height | Less than 1000mm from the relevant boundary | 1000mm or more from the relevant boundary |
|---|---|---|---|
| ‘Relevant buildings’ as defined in regulation 7(4) (see paragraph 12.15) | Class A2-s1, d0(1) or better | Class A2-s1, d0(1) or better | |
| All ‘residential’ purpose groups (purpose groups 1 and 2) | More than 11m | Class A2-s1, d0(2) or better | Class A2-s1, d0(2) or better |
| 11m or less | Class B-s3, d2(2) or better | No provisions | |
| Assembly and recreation | More than 18m | Class B-s3, d2(2) or better | From ground level to 18m: class C-s3, d2(3) or better From 18m in height and above: class B-s3, d2(2) or better |
| 18m or less | Class B-s3, d2(2) or better | Up to 10m above ground level: class C-s3, d2(3) or better Up to 10m above a roof or any part of the building to which the public have access: class C-s3, d2(3) or better(4) From 10m in height and above: no minimum performance | |
| Any other building | More than 18m | Class B-s3, d2(2) or better | From ground level to 18m: class C-s3, d2(3) or better From 18m in height and above: class B-s3, d2(2) or better |
| 18m or less | Class B-s3, d2(2) or better | No provisions | |
NOTES:
In all cases all the following provisions apply.
In addition to the provisions within this table, buildings with a storey 18m or more above ground level should also meet the provisions of paragraph 12.6.
In addition to the provisions within this table, buildings with a storey 11m or more above ground level should also meet the provisions of paragraph 12.7.
Materials and products
12.6
In a building with a storey 18m or more in height (see Diagram D6 in Appendix D) any insulation product, filler material (such as the core materials of metal composite panels, sandwich panels and window spandrel panels but not including gaskets, sealants and similar) etc. used in the construction of an external wall should be class A2-s3, d2 or better (see Appendix B). This restriction does not apply to masonry cavity wall construction which complies with Diagram 9.2 in Section 9. Where regulation 7(2) applies, that regulation prevails over all the provisions in this paragraph.
12.7
In buildings that include a ‘residential’ purpose (purpose groups 1 and 2) with a storey 11m or more in height (see Diagram D6 in Appendix D) any insulation product, filler material (such as the core materials of metal composite panels, sandwich panels and window spandrel panels but not including gaskets, sealants and similar) etc. used in the construction of an external wall should be class A2-s1, d0 or better (see Appendix B). This restriction does not apply to masonry cavity wall construction which complies with Diagram 9.2 in Section 9. Where regulation 7(2) applies, that regulation prevails over all the provisions in this paragraph.
12.8
Best practice guidance for green walls (also called living walls) can be found in Fire Performance of Green Roofs and Walls, published by the Department for Communities and Local Government. Where regulation 7(2) applies, that regulation prevails over all the provisions in this paragraph.
Cavities and cavity barriers
12.9
Cavity barriers should be provided in accordance with Section 9.
12.10
In the case of an external wall construction of a building which, by virtue of paragraph 9.10d (external cladding system with a masonry or concrete inner leaf), is not subject to the provisions of Table 9.1, the surfaces which face into cavities should also meet the provisions of Table 12.1 and provisions in Section 9, but where regulation 7(2) applies, that regulation prevails over the guidance provided in Table 12.1 and Section 9.