Combustibility of external walls External surfaces

External surfaces

12.5

The external surfaces (i.e. outermost external material) of external walls should comply with the provisions in Table 12.1. The provisions in Table 12.1 apply to each wall individually in relation to its proximity to the relevant boundary.

Table 12.1 Reaction to fire performance of external surface of walls

Building typeBuilding heightLess than 1000mm from the relevant boundary1000mm or more from the relevant boundary
‘Relevant buildings’ as defined in regulation 7(4) (see paragraph 12.15)Class A2-s1, d0(1) or betterClass A2-s1, d0(1) or better
All ‘residential’ purpose groups (purpose groups 1 and 2)More than 11mClass A2-s1, d0(2) or betterClass A2-s1, d0(2) or better
11m or lessClass B-s3, d2(2) or betterNo provisions
Assembly and recreationMore than 18mClass B-s3, d2(2) or better

From ground level to 18m: class C-s3, d2(3) or better

From 18m in height and above: class B-s3, d2(2) or better

18m or lessClass B-s3, d2(2) or better

Up to 10m above ground level: class C-s3, d2(3) or better

Up to 10m above a roof or any part of the building to which the public have access: class C-s3, d2(3) or better(4)

From 10m in height and above: no minimum performance

Any other buildingMore than 18mClass B-s3, d2(2) or better

From ground level to 18m: class C-s3, d2(3) or better

From 18m in height and above: class B-s3, d2(2) or better

18m or lessClass B-s3, d2(2) or betterNo provisions

NOTES:

In all cases all the following provisions apply.

• Regulation 7(1A) prohibits the use of relevant metal composite materials in the external walls, and specified attachments, of all buildings of any height (see paragraphs 12.12 and 12.13).
• The advice in paragraph 12.4 should always be followed.

In addition to the provisions within this table, buildings with a storey 18m or more above ground level should also meet the provisions of paragraph 12.6.

In addition to the provisions within this table, buildings with a storey 11m or more above ground level should also meet the provisions of paragraph 12.7.

1. The restrictions for these buildings apply to all the materials used in the external wall and specified attachments (see paragraphs 12.14 to 12.17 for further guidance).
2. Profiled or flat steel sheet at least 0.5 mm thick with an organic coating of no more than 0.2mm thickness is also acceptable.
3. Timber cladding at least 9mm thick is also acceptable.
4. 10m is measured from the top surface of the roof.