Section 17: Access to buildings for firefighting personnel Design and construction of firefighting shafts

Design and construction of firefighting shafts

17.9

Every firefighting stair and firefighting lift should be approached from the accommodation through a firefighting lobby. Both the stair and lobby of the firefighting shaft should be provided with a means of venting smoke and heat (see clause 27.1 of BS 9999).

Only services associated with the firefighting shaft, such as ventilation systems and lighting for the firefighting shaft, should pass through or be contained within the firefighting shaft.

17.10

All firefighting shafts should have fire mains with outlet connections and valves at every storey.

17.11

A firefighting lift installation includes all of the following.

a. Lift car.
b. Lift well.
c. Lift machinery space.
d. Lift control system.
e. Lift communications system.

The lift shaft should be constructed in accordance with Section 6 of BS 9999.

Firefighting lift installations should conform to BS EN 81-72 and BS EN 81-20.