Section 17: Access to buildings for firefighting personnel

Section 17: Access to buildings for firefighting personnel

Introduction

17.1

Facilities for fire and rescue, such as firefighting lifts, firefighting stairs and firefighting lobbies, are combined in protected firefighting shafts (Diagram 17.1). Section 8 gives guidance on the design and construction of protected shafts.

Diagram 17.1 Components of a firefighting shaft

Diagram 17.1 Components of a firefighting shaft. Wording on the drawing: See para 17.1; Any building; Fire main outlet; Firefighting stairs; Firefighting; lobby; Firefighting; lift in lift shaft; Minimum fire resistance REI 120 from accommodation side and REI 60 from inside the shaft with E 60 Sa fire doors; Minimum fire resistance REI 60 from both sides with E 30 Sa fire doors; NOTES:; 1. Outlets from a fire main should be located in the firefighting lobby.; 3. This diagram is only to illustrate the basic components and is not meant to represent the only acceptable layout. The firefighting shaft should be constructed generally in accordance with Section 6 of BS 9999.; 2. A firefighting lift is required if the building has a floor more than 18m above, or more than 10m below, fire service vehicle access level.; 4. For the minimum fire resistance of lift doors see Table C1.
Diagram 17.1 Components of a firefighting shaft

Provision of firefighting shafts

17.2

A building with a storey more than 18m above the fire and rescue service vehicle access level should have one or more firefighting shafts containing a firefighting lift. The number and location of firefighting shafts should comply with paragraphs 17.4 to 17.7. Firefighting shafts are not required to serve a basement that is not large or deep enough to need one (see paragraph 17.3 and Diagram 17.2).

17.3

A building with basement storeys should have firefighting shafts in accordance with the following.

a. There is a basement more than 10m below the fire and rescue service vehicle access level. The firefighting shafts should contain firefighting lifts.
b. There are two or more basement storeys, each with a minimum area of 900m2. The firefighting shafts do not need to include firefighting lifts.

The building’s height and size determine whether firefighting shafts also serve upper storeys.

17.4

Firefighting shafts should serve all storeys through which they pass.

17.5

A minimum of two firefighting shafts should be provided to buildings with a storey that has both of the following.

a. A floor area of 900m2 or more.
b. A floor level 18m or more above the fire and rescue service vehicle access level.

17.6

At least two firefighting shafts, which do not need to include firefighting lifts, should be provided if buildings meet all of the following.

a. They are in the ‘shop and commercial’, ‘assembly and recreation’ or ‘industrial’ purpose group (purpose group 4, 5 or 6).
b. They have a storey area of 900m2 or more.
c. They have a storey height of 7.5m or more above fire and rescue service vehicle access level.

Diagram 17.2 Provision of firefighting shafts

Diagram 17.2 Provision of firefighting shafts. Wording on the drawing: See para 17.2; Buildings in which firefighting shafts should be provided,; showing which storeys need to be served; a. Any building b. Any building c. ‘Shop and d. Any building commercial’, The upper storeys The basement The basement ‘assembly and in any building storeys in any storeys in any recreation’ and with a storey more building with a building with two ‘industrial’ than 18m above basement more or more buildings (purpose fire service vehicle than 10m below basements each groups 4, 5 and 6) access level fire service vehicle exceeding 900m² access level; The upper storeys in purpose groups 4, 5 and 6 buildings with a storey of 900m2 or more which is more than 7.5m above fire service vehicle access level; > 18m; Fire service vehicle; > 7.5m; access; level; > 10m; Two or more basement storeys each exceeding 900m²; NOTES:; 1. Height excludes any top storey(s) consisting exclusively of plant rooms.; Extent of firefighting; Extent of firefighting; stair lift 2. Firefighting shafts should serve all floors through which they pass.
Diagram 17.2 Provision of firefighting shafts

Location of firefighting shafts

17.7

Firefighting shafts and protected stairways should be positioned such that every part of each storey more than 18m above the fire and rescue service vehicle access level complies with the maximum distances given in paragraph 17.8. Distances should be measured from the fire main outlet on a route suitable for laying a hose.

NOTE: If the internal layout is not known, the distance should be measured at two-thirds of the direct distance.

17.8

In any building, the hose laying distance should meet all of the following conditions.

a. A maximum of 60m from the fire main outlet in a firefighting shaft (see Diagram 17.3).
b. Additionally, where sprinklers have not been provided in accordance with Appendix E, the hose laying distance should be a maximum of 45m from a fire main outlet in a protected shaft (although this does not imply that the protected shaft needs to be designed as a firefighting shaft (see Diagram 17.3).

Diagram 17.3 Location of firefighting shafts: hose laying distances

Diagram 17.3 Location of firefighting shafts: hose laying distances. Wording on the drawing: See para 17.8; With sprinklers; a.; b.; F; F F; 60m; Without sprinklers; c.; 45m; Floor plan within 60m hose laying distance of fire main outlet; Floor plan within 45m hose laying distance of fire main outlet; F; Hose reach; F H; Firefighting shaft; 60m; Fire main outlet in a protected shaft; Additional hose coverage required; d.; e.; H; F H; F F; 45m; H; NOTES:; 1. Hose laying distance should be measured from the fire main outlet along the route suitable for laying hose. If this route is not known, the distance should be taken at two-thirds of the direct distance.; 2. The fire main outlet should be located according to paragraph 16.4.
Diagram 17.3 Location of firefighting shafts: hose laying distances

Design and construction of firefighting shafts

17.9

Every firefighting stair and firefighting lift should be approached from the accommodation through a firefighting lobby. Both the stair and lobby of the firefighting shaft should be provided with a means of venting smoke and heat (see clause 27.1 of BS 9999).

Only services associated with the firefighting shaft, such as ventilation systems and lighting for the firefighting shaft, should pass through or be contained within the firefighting shaft.

17.10

All firefighting shafts should have fire mains with outlet connections and valves at every storey.

17.11

A firefighting lift installation includes all of the following.

a. Lift car.
b. Lift well.
c. Lift machinery space.
d. Lift control system.
e. Lift communications system.

The lift shaft should be constructed in accordance with Section 6 of BS 9999.

Firefighting lift installations should conform to BS EN 81-72 and BS EN 81-20.

Rolling shutters in compartment walls

17.12

The fire and rescue service should be able to manually open and close rolling shutters without the use of a ladder.