Section 4: Small premises Escape stairs in small premises
Escape stairs in small premises
4.7
A single escape stair may be used in small premises.
4.8
An open stair may be used as a means of escape if all of the following apply.
a. The stair connects a maximum of two storeys.
b. The stair enters the ground storey a maximum of 3m from the final exit (see Diagrams 4.2 and 4.3).
c. The premises is not a bar or restaurant.
d. Either of the following applies.
i. The storey is also served by a protected stairway.
ii. The stair is a single stair and the floor area of any single storey is a maximum of 90m2.
4.9
Where the premises contains three storeys and a single open stair serves a top or bottom storey, the stair serving the other storey should be enclosed with fire resisting construction at the ground storey level and discharge to a final exit independent of the ground storey (see Diagram 4.3).