Section 4: Small premises
Section 4: Small premises
4.1
A ‘small premises’ is generally limited both in its size and in its number of occupants. When undivided, all of its parts are likely to be clearly visible to occupants. Occupants of small premises will be able to reach an exit quickly in an emergency and therefore a reduction in the number of exits and stairs is acceptable.
This guidance is not applicable to small premises where highly flammable materials are sold, stored or used.
4.2
Small premises should meet all of the following general conditions.
4.3
The following paragraphs only apply in place of those provisions elsewhere in this Approved Document which relate to the following.
For provisions other than those listed above, the guidance elsewhere in this Approved Document should be followed.
Construction
4.4
Except in kitchens, ancillary offices and stores, floor areas should be undivided so exits are clearly visible from all parts.
4.5
Store rooms should be enclosed with fire resisting construction (minimum REI 30).
Travel distance and number of escape routes
4.6
Escape routes should be sited so that the travel distance from any point of a storey to the nearest storey exit does not exceed the distance given in Table 4.1 (see Diagrams 4.1, 4.2 and 4.3). The siting of two or more exits or stairs should give effective alternative directions of travel from any point in a storey.
Table 4.1 Maximum travel distances in small premises
| Storey | Maximum travel distance (m) |
|---|---|
| Ground storey with a single exit | 27 |
| Basement or first storey with a single stair | 18 |
| Storey with more than one exit/stair | 45 |
NOTES:
If the internal layout of partitions, fittings, etc. is not known, direct distances, rather than travel distances, should be assessed. The direct distance should be assumed to be two-thirds of the travel distance.
The travel distance in small premises with an open stair is measured as follows.
Diagram 4.1 Maximum travel distances in a small two or three storey premises with a single protected stairway to each storey

Diagram 4.2 Maximum travel distances in a small three storey premises with a single open stair

Diagram 4.3 Maximum travel distances in a small three storey premises with a single stair to each storey

Escape stairs in small premises
4.7
A single escape stair may be used in small premises.
4.8
An open stair may be used as a means of escape if all of the following apply.
4.9
Where the premises contains three storeys and a single open stair serves a top or bottom storey, the stair serving the other storey should be enclosed with fire resisting construction at the ground storey level and discharge to a final exit independent of the ground storey (see Diagram 4.3).