Section 10: Protection of openings and fire-stopping Flues, etc.

Flues, etc.

10.23

The wall of a flue, duct containing flues or appliance ventilation duct(s) should have a fire resistance (REI) that is at least half of any compartment wall or compartment floor it passes through or is built into (Diagram 10.4).

Diagram 10.4 Flues penetrating compartment walls or floors

Diagram 10.4 Flues penetrating compartment walls or floors. Wording on the drawing: See para 10.23; a. Flue passing through compartment wall or floor b. Flue built into compartment wall; Compartment wall or floor; Flue Compartment wall; Compartment wall; Flue wall; Flue walls should have a fire resistance of at least In each case flue walls should have a fire resistance of at least one half of that required for the compartment wall one half of that required for the compartment wall and be of or floor and be of class A1 construction. class A1 construction.
Diagram 10.4 Flues penetrating compartment walls or floors