Section 10: Protection of openings and fire-stopping
Section 10: Protection of openings and fire-stopping
Introduction
10.1
Every joint, imperfect fit and opening for services through a fire-separating element should be sealed with fire-stopping to ensure the fire resistance of the element is not impaired. Fire-stopping delays the spread of fire and, generally, the spread of smoke as well.
Openings for pipes
10.2
Pipes passing through a fire-separating element, unless in a protected shaft, should comply with one of the alternatives A, B or C below.
Alternative A: Proprietary seals (any pipe diameter)
10.3
Provide a proprietary, tested sealing system that will maintain the fire resistance of the wall, floor or cavity barrier.
Alternative B: Pipes with a restricted diameter
10.4
Where a proprietary sealing system is not used, fire-stop around the pipe, keeping the opening for the pipe as small as possible. The nominal internal diameter of the pipe should not exceed the relevant dimension given in Table 10.1.
Alternative C: Sleeving
10.5
A pipe with a maximum nominal internal diameter of 160mm may be used with a sleeve made out of a high melting point metal, as shown in Diagram 10.1, if the pipe is made of one of the following.
A high melting point metal means any metal (such as cast iron, copper or steel) which, if exposed to a temperature of 800°C, will not soften or fracture to the extent that flame or hot gas will pass through the wall of the pipe.
Diagram 10.1 Pipes penetrating fire-separating elements

Table 10.1 Maximum nominal internal diameter of pipes passing through a fire-separating element
| Situation | Pipe material and maximum nominal internal diameter (mm) | ||
|---|---|---|---|
(a) High melting point metal(1) | (b) Lead, aluminium, aluminium alloy, uPVC(2), fibrecement | (c) Any other material | |
1. Structure (but not a wall separating buildings) enclosing a protected shaft that is not a stairway or a lift shaft | 160 | 110 | 40 |
2. Any other situation | 160 | 40 | 40 |
NOTES:
Mechanical ventilation and air-conditioning systems
General provisions
10.6
Ductwork should not help to transfer fire and smoke through the building. Terminals of exhaust points should be sited away from final exits, cladding or roofing materials achieving class B-s3, d2 or worse and openings into the building.
10.7
Ventilation ducts supplying or extracting air directly to or from a protected stairway should not also serve other areas. A separate ventilation system should be provided for each protected stairway.
10.8
A fire and smoke damper should be provided where ductwork enters or leaves each section of the protected escape route it serves. It should be operated by a smoke detector or suitable fire detection system. Fire and smoke dampers should close when smoke is detected. Alternatively, the methods set out in paragraphs 10.15 and 10.16 and Diagrams 10.2 and 10.3 may be followed.
10.9
In a system that recirculates air, smoke detectors should be fitted in the extract ductwork before both of the following.
When smoke is detected, detectors should do one of the following.
10.10
Non-domestic kitchens, car parks and plant rooms should have separate and independent extraction systems. Extracted air should not be recirculated.
10.11
Under fire conditions, ventilation and air-conditioning systems should be compatible with smoke control systems and need to be considered in their respective design.
Ventilation ducts and flues passing through fire-separating elements
General provisions
10.12
If air handling ducts pass through fire-separating elements, the fire performance of the elements should be maintained using one or more of the following four methods. In most ductwork systems, a combination of the four methods is best.
10.13
Further information on fire resisting ductwork is given in the ASFP Blue Book.
Kitchen extract
10.14
Methods 1 and 4 should not be used for extract ductwork serving kitchens. The likely build-up of grease within the duct can adversely affect dampers.
Ducts passing through protected escape routes
10.15
Method 1 should not be used for extract ductwork passing through the enclosures of protected escape routes (Diagrams 10.2 and 10.3), as large volumes of smoke can pass thermal devices without triggering them.
10.16
An ES classified fire and smoke damper which is activated by a suitable fire detection system (method 4) may also be used for protected escape routes.
Diagram 10.2 Ductwork passing through protected escape routes – method 2 or method 3

Diagram 10.3 Ductwork passing through protected escape routes – method 4

Installation and specification of fire dampers
10.17
Both fire dampers and fire and smoke dampers should be all of the following.
10.18
Access to the fire damper and its actuating mechanism should be provided for inspection, testing and maintenance.
10.19
Fire dampers should meet both of the following conditions.
10.20Fire and smoke dampers should meet both of the following conditions.
10.21
Smoke detectors should be sited so as to prevent the spread of smoke as early as practicable by activating the fire and smoke dampers. Smoke detectors and automatic release mechanisms used to activate fire dampers and/or fire and smoke dampers should conform to BS EN 54-7 and BS 5839-3 respectively.
Further information on fire dampers and/or fire and smoke dampers is given in the ASFP Grey Book.
Sleeping risks
10.22
Where the use of the building involves a sleeping risk, fire dampers or fire and smoke dampers should be actuated by both of the following.
However, in a situation where both of the following are true:
then both of the following exceptions may be made.
Flues, etc.
10.23
The wall of a flue, duct containing flues or appliance ventilation duct(s) should have a fire resistance (REI) that is at least half of any compartment wall or compartment floor it passes through or is built into (Diagram 10.4).
Diagram 10.4 Flues penetrating compartment walls or floors

Fire-stopping
10.24In addition to any other provisions in this section, both of the following conditions should be met.
NOTE: The fire-stopping around fire dampers, fire resisting ducts, fire and smoke dampers and smoke control ducts should be in accordance with the manufacturer or supplier’s installation instructions.
10.25
Materials used for fire-stopping should be reinforced with (or supported by) materials rated class A2-s3, d2 or better to prevent displacement in both of the following cases.
10.26Proprietary, tested fire-stopping and sealing systems are available and may be used. Different materials suit different situations and not all are suitable in every situation.
10.27
Other fire-stopping materials include the following.
These may be used in situations appropriate to the particular material. Not all materials will be suitable in every situation.
10.28Guidance on the design, installation and maintenance of measures to contain fires or slow their spread is given in Ensuring Best Practice for Passive Fire Protection in Buildings produced by the Association for Specialist Fire Protection (ASFP).
10.29Further information on generic systems, their suitability for different applications and guidance on test methods is given in the ASFP Red Book.