Section 5: General provisions Lifts

Lifts

Evacuation lifts

5.32

Generally, lifts should not be used when there is a fire in the building, unless their use forms part of a management plan for evacuating people and the following conditions are met.

a. Lifts are appropriately sited and protected.
b. Lifts contain safety features to ensure they remain usable during a fire.

Guidance on the design and use of evacuation lifts is given in Annex G to BS 9999.

5.33

Where a firefighting lift is provided, it can be used to evacuate disabled people. Management plans should describe how this would be managed, and what will happen when the fire and rescue service arrives.

Fire protection of lift installations

5.34

Lift wells should comply with one of the following conditions.

a. Be sited within the enclosures of a protected stairway.
b. Be enclosed with fire resisting construction (minimum REI 30) when in a position that might prejudice the means of escape.

5.35

A lift well connecting different compartments should form a protected shaft (see Section 8).

5.36

Lifts that rise within a large volume such as a mall or atrium and do not have a conventional well, such as wall-climber or feature lifts, may be at risk if they run through a smoke reservoir. Care should be taken to maintain the integrity of the smoke reservoir and protect people in the lift.

5.37

In buildings designed for phased evacuation or progressive horizontal evacuation, if the lift well is not within the enclosures of a protected stairway, its entrance should be separated at every storey by a protected lobby (minimum REI 30).

5.38

In basements and enclosed car parks, the lift should be within the enclosure of a protected stairway. Otherwise, the lift should be approached only via a protected lobby or protected corridor (minimum REI 30).

5.39

If a lift delivers into a protected corridor or protected lobby serving sleeping accommodation and also serves a storey containing a high fire risk (such as a kitchen, communal areas, stores, etc.) then the lift should be separated from the high fire risk area(s) by a protected lobby or protected corridor (minimum REI 30).

5.40

A lift shaft serving storeys above ground level should not serve any basement if either of the following applies.

a. There is only one escape stair serving storeys above ground level and smoke from a basement fire would adversely affect escape routes in the upper storeys.
b. The lift shaft is within the enclosure to an escape stair that terminates at ground level.

5.41

Lift machine rooms should be sited over the lift well where possible. Where buildings or part of a building with only one stairway make this arrangement impractical, the lift machine room should be sited outside the protected stairway.