Section 5: General provisions
Section 5: General provisions
Introduction
5.1
This section applies to all buildings and deals with the design, construction and protection of escape routes and service installations.
Protection of escape routes
Fire resistance of enclosures
5.2
Fire resistance test criteria are set out in Appendix B. Standards of performance are summarised in Table B1 and Table B2. Apart from specific situations described in Sections 1 and 2, and requirements B3 and B5, a minimum performance of REI 30 is sufficient to protect means of escape.
Fire resistance of doors
5.3
Fire resistance test criteria are set out in Appendix C. Standards of performance are summarised in Table C1.
Fire resistance of glazed elements
5.4
If glazed elements in fire resisting enclosures and doors can only meet the required integrity performance, their use is limited. These limitations depend on whether the enclosure forms part of a protected shaft (see Section 8) and the provisions set out in Appendix B, Table B3. If both integrity and insulation performance can be met, there is no restriction in this document on the use or amount of glass.
5.5
Glazed elements should also comply with the following, where necessary.
Doors on escape routes
5.6
Doors should be readily openable to avoid undue delay to people escaping. Doors on escape routes (both within and from the building) should comply with paragraphs 5.7 to 5.15. Guidance on door closing and ‘hold open’ devices for fire doorsets is set out in Appendix C.
Door fastenings
5.7
In general, doors on escape routes (whether or not the doors are fire doorsets) should be either of the following.
Doors may be fitted with hardware to allow them to be locked when rooms are empty.
In places such as hotel bedrooms, locks may be fitted that are key operated from the outside and manually opened from the inside.
If a secure door is operated by code or combination keypad, swipe or proximity card, biometric data, etc., a security mechanism override should be possible from the side approached by people escaping.
5.8
Electrically powered locks should return to the unlocked position in all of the following situations.
Security mechanism overrides for electrically powered locks should be a Type A call point as described in BS 7273-4. The call point should be positioned on the side approached by people escaping. If the door provides escape in either direction, a call point should be installed on both sides of the door.
5.9
In places of assembly and shop and commercial buildings (purpose groups 4 and 5), doors on escape routes from rooms with more than 60 people should be either of the following.
In non-residential buildings (purpose groups 3 to 7), some final exit doors feature security locks that are used only when the building is empty. Such locks may be appropriate, but management procedures must emphasise their safe use.
5.10
Guidance on door closing and ‘hold open’ devices for fire doorsets is set out in Appendix C.
Direction of opening
5.11
The door of any doorway or exit should be hung to open in the direction of escape whenever reasonably practicable. It should always be hung to open in the direction of escape if either of the following conditions applies.
Amount of opening and effect on associated escape routes
5.12
All doors on escape routes should be hung to meet both of the following conditions.
5.13
Any door opening towards a corridor or a stair should be recessed to prevent its swing encroaching on the effective width.
Vision panels in doors
5.14
Doors should contain vision panels in both of the following situations.
Approved Document M contains guidance about vision panels in doors across accessible corridors and Approved Document K contains guidance about the safety of glazing.
Revolving and automatic doors
5.15
Where revolving doors, automatic doors and turnstiles are placed across escape routes they should comply with one of the following.
General provisions
Headroom in escape routes
5.16
Escape routes should have a minimum clear headroom of 2m. The only projections allowed below this height are door frames.
Flooring of escape routes
5.17
Escape route floor finishes should minimise their slipperiness when wet. Finishes include the treads of steps and surfaces of ramps and landings.
Ramps and sloping floors
5.18
A ramp forming part of an escape route should meet the provisions in Approved Document M. Any sloping floor or tier should have a pitch of not more than 35 degrees to the horizontal.
5.19
Guidance for where there is fixed seating is given in both of the following.
Final exits
5.20
The width of a final exit should be at least the same as the minimum required width of the escape route it serves.
5.21
People should be able to rapidly leave the area around the building. Direct access to a street, passageway, walkway or open space should be available. The route away from the building should comply with the following.
5.22
Final exits should not present a barrier for disabled people. Where the route to a final exit does not include stairs, a level threshold and, where necessary, a ramp should be provided.
5.23
Final exit locations should be clearly visible and recognisable.
5.24
Final exits should avoid outlets of basement smoke vents and openings to transformer chambers, refuse chambers, boiler rooms and similar risks.
Table 5.1 Provisions for escape lighting
| Use of the building or part of the building | Areas requiring escape lighting |
|---|---|
| Residential | All common escape routes(1), except in two storey blocks of flats |
| Office, industrial, storage and other nonresidential | a. Underground or windowless accommodation b. Stairs either: • in a central core • that serve storey(s) more than 18m above ground level c. Internal corridors more than 30m long d. Open-plan areas of more than 60m2 |
| Shop and commercial, and car parks | a. Underground or windowless accommodation b. Stairs either: • in a central core • that serve storey(s) more than 18m above ground level c. Internal corridors more than 30m long d. Open-plan areas of more than 60m2 e. All escape routes (other than the following exception) to which the public are admitted.(1) The exception is shops that meet all of the following: • have a maximum of three storeys • have no sales floor of more than 280m2 • are not a restaurant or bar |
| Assembly and recreation | a. All escape routes(1) b. Accommodation except for that which is open on one side to view sport or entertainment during normal daylight hours |
| Any purpose group | a. All toilet accommodation with a minimum floor area of 8m2 b. Electricity and generator rooms c. Switch room/battery room for emergency lighting system d. Emergency control rooms |
NOTE:
Lighting of escape routes
5.25
All escape routes should have adequate artificial lighting. If the mains electricity power supply fails, escape lighting should illuminate the routes listed in Table 5.1.
5.26
Escape stair lighting should be on a separate circuit from the electricity supply to any other part of the escape route.
5.27
Escape lighting should conform to BS 5266-1.
Exit signs
5.28
Every doorway or other exit providing access to a means of escape, other than exits in ordinary use (e.g. main entrances), should be distinctively and conspicuously marked by an exit sign in accordance with BS ISO 3864-1 and BS 5499-4.
Advice on fire safety signs, including emergency escape signs, is given in the HSE publication Safety Signs and Signals: Guidance on Regulations.
Some buildings may require additional signs to comply with other legislation.
Protected power circuits
5.29
To limit potential damage to cables in protected circuits, all of the following should apply.
5.30
A protected circuit to operate equipment during a fire should achieve all of the following.
5.31
Guidance on cables for large and complex buildings is given in BS 5839-1, BS 5266-1 and BS 8519.
Lifts
Evacuation lifts
5.32
Generally, lifts should not be used when there is a fire in the building, unless their use forms part of a management plan for evacuating people and the following conditions are met.
Guidance on the design and use of evacuation lifts is given in Annex G to BS 9999.
5.33
Where a firefighting lift is provided, it can be used to evacuate disabled people. Management plans should describe how this would be managed, and what will happen when the fire and rescue service arrives.
Fire protection of lift installations
5.34
Lift wells should comply with one of the following conditions.
5.35
A lift well connecting different compartments should form a protected shaft (see Section 8).
5.36
Lifts that rise within a large volume such as a mall or atrium and do not have a conventional well, such as wall-climber or feature lifts, may be at risk if they run through a smoke reservoir. Care should be taken to maintain the integrity of the smoke reservoir and protect people in the lift.
5.37
In buildings designed for phased evacuation or progressive horizontal evacuation, if the lift well is not within the enclosures of a protected stairway, its entrance should be separated at every storey by a protected lobby (minimum REI 30).
5.38
In basements and enclosed car parks, the lift should be within the enclosure of a protected stairway. Otherwise, the lift should be approached only via a protected lobby or protected corridor (minimum REI 30).
5.39
If a lift delivers into a protected corridor or protected lobby serving sleeping accommodation and also serves a storey containing a high fire risk (such as a kitchen, communal areas, stores, etc.) then the lift should be separated from the high fire risk area(s) by a protected lobby or protected corridor (minimum REI 30).
5.40
A lift shaft serving storeys above ground level should not serve any basement if either of the following applies.
5.41
Lift machine rooms should be sited over the lift well where possible. Where buildings or part of a building with only one stairway make this arrangement impractical, the lift machine room should be sited outside the protected stairway.
Refuse chutes and storage
5.42
Refuse storage chambers, refuse chutes and refuse hoppers should be sited and constructed in accordance with BS 5906.
5.43
Refuse chutes and rooms for storing refuse should meet both of the following conditions.
5.44
The approach to rooms containing refuse chutes or for storing refuse should comply with one of the following conditions.
5.45
Access openings to refuse storage chambers should not be sited next to escape routes or final exits.
Shop store rooms
5.46
Fully enclosed walk-in store rooms should be separated from retail areas with fire resisting construction (minimum REI 30) if they negatively affect the means of escape. The fire resisting construction is not necessary if the walk-in store room complies with either of the following.