Provision of smoke outlets Natural smoke outlets
Natural smoke outlets
18.5
Smoke outlets should be both of the following.
a. Sited at high level in either the ceiling or wall of the space they serve.
b. Evenly distributed around the perimeter, to discharge to the open air.
18.6
The combined clear cross-sectional area of all smoke outlets should be a minimum of 1/40 of the area of the floor of the storey they serve.
18.7
Separate outlets should be provided from places of special fire hazard.
18.8
If the smoke outlet terminates at a point that is not readily accessible, it should be kept unobstructed and covered only with a class A1 grille or louvre.
18.9
If the smoke outlet terminates in a readily accessible position, it may be covered by a panel, stallboard or pavement light that can be broken out or opened. The position of covered smoke outlets should be suitably indicated.
18.10
Outlets should not be placed where they prevent the use of escape routes from the building.