Section 18: Venting of heat and smoke from basements Provision of smoke outlets
Provision of smoke outlets
18.1
Heat and smoke from basement fires vented via stairs can inhibit access for firefighting personnel. This may be reduced by providing smoke outlets, or smoke vents, which allow heat and smoke to escape from the basement levels to the open air. They can also be used by the fire and rescue service to let cooler air into the basements (Diagram 18.1).
18.2
Each basement space should have one or more smoke outlets.
Where this is not practicable (for example, the plan area is deep and the amount of external wall is restricted by adjoining buildings), the perimeter basement spaces may be vented, with other spaces vented indirectly by opening connecting doors. This does not apply for place of special fire hazard (see paragraph 18.7).
If a basement is compartmented, each compartment should have one or more smoke outlets, rather than indirect venting.
A basement storey or compartment containing rooms with doors or windows does not need smoke outlets.
18.3
Smoke outlets connecting directly to the open air should be provided from every basement storey, except for any basement storey that has both of the following.
18.4
Strong rooms do not need to be provided with smoke outlets.
Natural smoke outlets
18.5
Smoke outlets should be both of the following.
18.6
The combined clear cross-sectional area of all smoke outlets should be a minimum of 1/40 of the area of the floor of the storey they serve.
18.7
Separate outlets should be provided from places of special fire hazard.
18.8
If the smoke outlet terminates at a point that is not readily accessible, it should be kept unobstructed and covered only with a class A1 grille or louvre.
18.9
If the smoke outlet terminates in a readily accessible position, it may be covered by a panel, stallboard or pavement light that can be broken out or opened. The position of covered smoke outlets should be suitably indicated.
18.10
Outlets should not be placed where they prevent the use of escape routes from the building.
Mechanical smoke extract
18.11
If basement storeys are fitted with a sprinkler system in accordance with Appendix E, a mechanical smoke extraction system may be provided as an alternative to natural venting. Sprinklers do not need to be installed on the other storeys unless needed for other reasons.
Car parks are not normally expected to be fitted with sprinklers (see Section 11 for guidance on car parks).
18.12
The air extraction system should comply with all of the following.
Further information on equipment for removing hot smoke is given in BS EN 12101-3.
Diagram 18.1 Fire resisting construction for smoke outlet shafts