Section 3: Design for vertical escape Number of escape stairs

Number of escape stairs

Mixed use buildings

3.2

If a building contains storeys, or parts of storeys, in different purpose groups, it is necessary to consider providing either of the following.

a. Separate escape routes from the areas of different use.
b. Other effective means to protect common escape routes.

Single escape stairs

3.3

A single escape stair may serve a building (or part of a building) in the following situations.

a. When independent escape routes from areas in different purpose groups are not necessary (see paragraph 3.2).
b. From a basement that is allowed to have a single escape route in accordance with paragraph 2.6b and Table 2.1.
c. In small premises, provided it meets the conditions in paragraph 4.2.
d. From a building that meets both of the following conditions.
i. It has no storey with a floor level more than 11m above ground level.
ii. It is allowed to have only a single escape route in every storey in accordance with paragraph 2.6b and Table 2.1.
e. An office building with a maximum of five storeys above the ground storey where both of the following apply.
i. The travel distance from every point in each storey does not exceed the distances given in Table 2.1 for escape in one direction only.
ii. Every storey with a floor level more than 11m above ground level has an alternative means of escape.
f. A factory comprising no more than either of the following.
i. For low risk buildings, two storeys above the ground storey.
ii. For normal risk buildings, one storey above the ground storey, provided the travel distance from every point on each storey does not exceed the distances given in Table 2.1 for escape in one direction only.
g. Process plant buildings with a maximum of 10 people.