Section 3: Design for vertical escape
Section 3: Design for vertical escape
Introduction
3.1
The limits on horizontal travel escape distances mean most people should be able to independently reach a protected escape route or final exit. The following guidance also includes measures for people who are unable to use stairs without help.
In larger buildings, some escape stairs may need to serve as firefighting stairs, and Section 17 will also apply.
Number of escape stairs
Mixed use buildings
3.2
If a building contains storeys, or parts of storeys, in different purpose groups, it is necessary to consider providing either of the following.
Single escape stairs
3.3
A single escape stair may serve a building (or part of a building) in the following situations.
Provision of refuges
3.4
Refuges form part of the management plan and offer relatively safe areas for people to wait for a short period only. Refuges should meet the following conditions.
3.5
The following are both examples of satisfactory refuges.
3.6
Refuges should be a minimum of 900mm × 1400mm in size and accessible by someone in a wheelchair. Where sited in a protected stairway, protected lobby or protected corridor, they should not reduce the width of the escape route or obstruct the flow of people escaping.
3.7
Refuges should be provided with an emergency voice communication (EVC) system complying with BS 5839-9. It should consist of Type B outstations communicating with a master station in the building control room (if one exists) or next to the fire detection and alarm panel. In some buildings, wireless technology may be more appropriate.
3.8
Refuges and evacuation lifts should be clearly identified. In protected lobbies and protected stairways there should be a blue mandatory sign worded ‘Refuge – keep clear’ in addition to fire safety signs.
3.9
Paragraph 5.32 gives guidance on using lifts, including evacuation lifts, during a fire.
Diagram 3.1 Refuge formed by compartmentation

Diagram 3.2 Refuge formed in a protected stairway

Width of escape stairs
3.10
The width of escape stairs should meet all of the following conditions.
3.11
Approved Document K requires stairs more than 2000mm wide in public buildings to have a central handrail.
3.12
If an exit route from a stair is also the escape route from the ground storey and/or basement storey, the width of the exit route may need to be increased (see paragraph 2.23).
Table 3.1 Minimum widths of escape stairs
| Situation of stair | Maximum number of people served(1) | Minimum stair width (mm) |
|---|---|---|
1a. In a ‘residential (institutional)’ building (unless the stair will only be used by staff) | 150 | 1000(2) |
1b. In an ‘assembly and recreation’ building and serving an area used for assembly purposes (unless the area is less than 100m²) | 220 | 1100 |
1c. In any other building and serving an area with an occupancy of more than 50 | Over 220 | See note 3 |
2. Any stair not described above | 50 | 800(4) |
NOTES:
Calculation of minimum stair width
3.13
The width depends on the number of stairs provided and the escape strategy (simultaneous or phased evacuation). If the maximum number of people needing to use escape stairs is unknown, calculate it using the floor space factors in Appendix D.
Discounting of stairs
3.14
Regardless of escape strategy, where two or more stairs are provided, it should be assumed that one might not be available during a fire. Each stair should be discounted in turn to ensure the capacity of the remaining stairs is adequate. This applies to buildings with or without a sprinkler system.
3.15
Paragraph 3.14 does not apply if either of the following applies.
Despite these exceptions, at least one storey exit still needs to be discounted (paragraph 2.21).
Paragraph 3.34 identifies cases where stairs need lobby protection.
Simultaneous evacuation
3.16
The width of escape stairs should take account of the number of people using them while evacuating all storeys at the same time. The following stairs should be designed to allow simultaneous evacuation.
Annexes B and C of BS 9999 include designs based on simultaneous evacuation.
3.17
The capacity of stairs of widths from 1000mm to 1800mm is given in Table 3.2.
Table 3.2 Capacity of stairs for basements and for simultaneous evacuation of the building
| No. of floors served | Maximum number of people served by a stair of width: | ||||||||
|---|---|---|---|---|---|---|---|---|---|
| 1000mm | 1100mm | 1200mm | 1300mm | 1400mm | 1500mm | 1600mm | 1700mm | 1800mm | |
| 1 | 150 | 220 | 240 | 260 | 280 | 300 | 320 | 340 | 360 |
| 2 | 190 | 260 | 285 | 310 | 335 | 360 | 385 | 410 | 435 |
| 3 | 230 | 300 | 330 | 360 | 390 | 420 | 450 | 480 | 510 |
| 4 | 270 | 340 | 375 | 410 | 445 | 480 | 515 | 550 | 585 |
| 5 | 310 | 380 | 420 | 460 | 500 | 540 | 580 | 620 | 660 |
| 6 | 350 | 420 | 465 | 510 | 555 | 600 | 645 | 690 | 735 |
| 7 | 390 | 460 | 510 | 560 | 610 | 660 | 710 | 760 | 810 |
| 8 | 430 | 500 | 555 | 610 | 665 | 720 | 775 | 830 | 885 |
| 9 | 470 | 540 | 600 | 660 | 720 | 780 | 840 | 900 | 960 |
| 10 | 510 | 580 | 645 | 710 | 775 | 840 | 905 | 970 | 1035 |
NOTES:
3.18
As an alternative to Table 3.2, the capacity of stairs 1100mm wide or wider can be found using either of the following formulas:
where:
P is the number of people that can be served
W is the width of the stair, in metres
N is the number of storeys served.
Separate calculations should be made for stairs serving basement storeys and stairs serving upper storeys.
The population, P, should be divided by the number of available stairs.
The formula is useful to determine the width of stairs where people are not distributed evenly – either within a storey or between storeys.
In the formula, 200W represents the number of people estimated to have left the stair after 2.5 minutes of evacuation, and 50 (W – 0.3)(N – 1) represents the number of people estimated to be on the stair after 2.5 minutes of evacuation.
Worked examples
Phased evacuation
3.19
Phased evacuation cannot be used in every type of building, but can be advantageous for escape stairs in high buildings. It requires supporting facilities, such as fire detection and alarm systems, to be provided and maintained.
In a phased evacuation, the first people to be evacuated are those with reduced mobility and those on the storey most immediately affected by the fire. If needed, subsequent evacuation is done two floors at a time, reducing disruption in large buildings.
Phased evacuation enables stairs to be narrower than with simultaneous evacuation, and may be used for any building provided it is not identified in paragraph 3.16.
3.20
Phased evacuation in buildings with a storey over 30m in height introduces the potential for escaping people to impede firefighters entering and operating within the building. This can be addressed by consulting with the fire and rescue service about special management procedures.
In very tall buildings, typically with a storey over 45m in height, physical measures may need to be incorporated, such as by discounting a stair.
3.21
A building (or part of a building) designed for phased evacuation should satisfy all of the following criteria.
3.22
The minimum width of stairs needed for phased evacuation is given in Table 3.3.
Table 3.3 Minimum width of stairs designed for phased evacuation
| Maximum number of people in any storey | Stair width (mm) |
|---|---|
| 100 | 1000 |
| 120 | 1100 |
| 130 | 1200 |
| 140 | 1300 |
| 150 | 1400 |
| 160 | 1500 |
| 170 | 1600 |
| 180 | 1700 |
| 190 | 1800 |
NOTES:
Worked example using Table 3.3
What is the minimum width needed for the stairs serving a 15 storey office building (ground + 14 office floors), assuming a total population of 2500 people (excluding the ground floor population, which does not use the stairs)? To satisfy the travel distance limitations, three stairs are required.
The building is over 45m in height and designed for phased evacuation. It has been decided to discount one stair to take account of fire and rescue service operations as described in paragraph 3.20. Therefore:
Each remaining stair must be able to accommodate half the population of one storey (i.e. 90 people).
Thus each stair should be 1000mm wide (maximum capacity 100 people).
This width will also be adequate when one storey exit is discounted as described in paragraph 2.21. It also complies with paragraph 3.10a (i.e. the stair widths are not less than the minimum width needed for 90 people in Table 2.3).
Additional worked example using Table 3.3
What is the minimum width needed for the stairs serving a 9 storey office building (ground + 8 office floors), assuming a total population of 1920 people (excluding the ground floor population, which does not use the stairs)? To satisfy the travel distance limitations, two stairs are required.
As both stairs need to be entered at each level through a protected lobby (see paragraph 3.21), both stairs can be assumed to be available (see paragraph 3.15). Therefore:
Design and protection of escape stairs
Enclosure of escape stairs
3.23
Every internal escape stair should be a protected stairway (within a fire resisting enclosure). If it is also a protected shaft (i.e. it passes from one compartment to another) or firefighting shaft, additional guidance in Sections 8 and 17 applies.
There is one exception: an unprotected stair (e.g. an accommodation stair) may form part of an internal route to a storey exit or final exit, provided that the distance of travel and the number of people involved are very limited. For example, small premises (Section 4) and raised storage areas (see paragraphs 7.6 and 7.7).
Construction of escape stairs
3.24
The flights and landings of escape stairs should be constructed of materials achieving class A2-s3, d2 or better in all of the following situations.
Materials achieving class B-s3, d2 or worse may be added to the top horizontal surface, except on firefighting stairs.
3.25
Further guidance on firefighting stairs is given in Section 17. Dimensional constraints on the design of stairs are given in Approved Document K.
Single steps
3.26
Single steps on escape routes should be prominently marked. A single step on the line of a doorway is acceptable, subject to paragraph 5.22.
Helical stairs and spiral stairs
3.27
Helical stairs and spiral stairs may form part of an escape route provided they are designed in accordance with BS 5395-2. If they are intended to serve members of the public, stairs should be type E (public) stairs.
Fixed ladders
3.28
Fixed ladders should not be provided as a means of escape for members of the public. They should only be provided where a conventional stair is impractical, such as for access to plant rooms which are not normally occupied.
External walls adjacent to protected stairways
3.29
With some configurations of external wall, a fire in one part of a building could subject the external wall of a protected stairway to heat (for example, where the two are adjacent at an internal angle in the façade, as shown in Diagram 3.3).
3.30
If a protected stairway projects beyond, is recessed from or is in an internal angle of the adjoining external wall of the building, then the minimum distance between an unprotected area of the building enclosure and an unprotected area of the stair enclosure should be 1800mm.
Diagram 3.3 External protection to protected stairways

External escape stairs
3.31
Where a storey or part of the building has more than one escape route available, some of the escape routes may be via an external escape stair, provided the following conditions are met.
3.32
Any external escape stair should meet all of the following conditions (Diagram 3.4).
3.33
Access to an external escape stair may be via a flat roof, provided the flat roof meets the requirements of paragraphs 2.31 and 2.32.
Diagram 3.4 Fire resistance of areas near to external stairs

Access lobbies and corridors
3.34
In the following situations, protected lobbies or protected corridors should be provided at all storeys above ground, except the top storey.
As an alternative to (a) to (c), a smoke control system as described in paragraph 3.15a may be used.
3.35
A protected lobby should be provided between an escape stair and a place of special fire hazard to protect from the ingress of smoke. The lobby should have a minimum 0.4m2 of permanent ventilation, or be protected by a mechanical smoke control system.
Exits from protected stairways
3.36
Every protected stairway should lead to a final exit, either directly or via an exit passageway. Any protected exit corridor or stair should have the same standard of fire resistance and lobby protection as the stair it serves. The exit from a protected stairway should comply with paragraphs 5.20 to 5.24.
Separation of adjoining protected stairways
3.37
The construction separating two adjacent protected stairways (or exit passageways) leading to different final exits should be imperforate.
Use of space within protected stairways
3.38
A protected stairway may only include any of the following.
Gas service and installation pipes in protected stairways
3.39
Gas service and installation pipes and meters should not be within a protected stairway, unless installed in accordance with the Pipelines Safety Regulations 1996 and the Gas Safety (Installation and Use) Regulations 1998.
Basement stairs
3.40
An escape stair forming part of the only escape route from an upper storey should not continue down to serve a basement storey. The basement storey should be served by a separate escape stair.
3.41
Where multiple escape stairs serve the upper storeys, only one needs to end at ground level. Other stairs may connect with the basement storeys if there is a protected lobby or a protected corridor between the stairs and accommodation at each basement level.