Appendix D: Methods of measurement Occupant number

Occupant number

D1

The number of occupants of a room, storey, building or part of a building is either of the following.

a. The maximum number of people it is designed to hold.
b. In buildings other than dwellings, the number of people calculated by dividing the area of a room or storey(s) (m2) by a floor space factor (m2 per person) such as given in Table D1 for guidance.

D2

Counters and display units should be included when measuring area. All of the following should be excluded.

a. Stair enclosures.
b. Lifts.
c. Sanitary accommodation.
d. Any other fixed part of the building structure.

Table D1 Floor space factors(1)

Type of accommodation(2)(3) Floor space factor (m2/person)
1. Standing spectator areas, bar areas (within 2m of serving point), similar refreshment areas
0.3
2. Amusement arcade, assembly hall (including a general purpose place of assembly), bingo hall, club, crush hall, dance floor or hall, venue for pop concerts and similar events and bar areas without fixed seating
0.5
3. Concourse or queuing area(4)
0.7
4. Committee room, common room, conference room, dining room, licensed betting office (public area), lounge or bar (other than in (1) above), meeting room, reading room, restaurant, staff room or waiting room(5)
1.0
5. Exhibition hall or studio (film, radio, television, recording)
1.5
6. Skating rink
2.0
7. Shop sales area(6)
2.0
8. Art gallery, dormitory, factory production area, museum or workshop
5.0
9. Office
6.0
10. Shop sales area(7)
7.0
11. Kitchen or library
7.0
12. Bedroom or study-bedroom
8.0
13. Bed-sitting room, billiards or snooker room or hall
10.0
14. Storage and warehousing
30.0
15. Car park
Two persons per parking space

NOTES:

1. As an alternative to using the values in the table, the floor space factor may be determined by reference to actual data taken from similar premises. Where appropriate, the data should reflect the average occupant density at a peak trading time of year.
2. Where accommodation is not directly covered by the descriptions given, a reasonable value based on a similar use may be selected.
3. Where any part of the building is to be used for more than one type of accommodation, the most onerous factor(s) should be applied. Where the building contains different types of accommodation, the occupancy of each different area should be calculated using the relevant space factor.
4. For detailed guidance on appropriate floor space factors for concourses in sports grounds refer to Concourses published by the Football Licensing Authority.
5. Alternatively the occupant number may be taken as the number of fixed seats provided, if the occupants will normally be seated.
6. Shops excluding those under item 10, but including: supermarkets and department stores (main sales areas), shops for personal services, such as hairdressing, and shops for the delivery or collection of goods for cleaning, repair or other treatment or for members of the public themselves carrying out such cleaning, repair or other treatment.
7. Shops (excluding those in covered shopping complexes but including department stores) trading predominantly in furniture, floor coverings, cycles, prams, large domestic appliances or other bulky goods, or trading on a wholesale self-selection basis (cash and carry).