Appendix D: Methods of measurement

Appendix D: Methods of measurement

Occupant number

D1

The number of occupants of a room, storey, building or part of a building is either of the following.

a. The maximum number of people it is designed to hold.
b. In buildings other than dwellings, the number of people calculated by dividing the area of a room or storey(s) (m2) by a floor space factor (m2 per person) such as given in Table D1 for guidance.

D2

Counters and display units should be included when measuring area. All of the following should be excluded.

a. Stair enclosures.
b. Lifts.
c. Sanitary accommodation.
d. Any other fixed part of the building structure.

Table D1 Floor space factors(1)

Type of accommodation(2)(3) Floor space factor (m2/person)
1. Standing spectator areas, bar areas (within 2m of serving point), similar refreshment areas
0.3
2. Amusement arcade, assembly hall (including a general purpose place of assembly), bingo hall, club, crush hall, dance floor or hall, venue for pop concerts and similar events and bar areas without fixed seating
0.5
3. Concourse or queuing area(4)
0.7
4. Committee room, common room, conference room, dining room, licensed betting office (public area), lounge or bar (other than in (1) above), meeting room, reading room, restaurant, staff room or waiting room(5)
1.0
5. Exhibition hall or studio (film, radio, television, recording)
1.5
6. Skating rink
2.0
7. Shop sales area(6)
2.0
8. Art gallery, dormitory, factory production area, museum or workshop
5.0
9. Office
6.0
10. Shop sales area(7)
7.0
11. Kitchen or library
7.0
12. Bedroom or study-bedroom
8.0
13. Bed-sitting room, billiards or snooker room or hall
10.0
14. Storage and warehousing
30.0
15. Car park
Two persons per parking space

NOTES:

1. As an alternative to using the values in the table, the floor space factor may be determined by reference to actual data taken from similar premises. Where appropriate, the data should reflect the average occupant density at a peak trading time of year.
2. Where accommodation is not directly covered by the descriptions given, a reasonable value based on a similar use may be selected.
3. Where any part of the building is to be used for more than one type of accommodation, the most onerous factor(s) should be applied. Where the building contains different types of accommodation, the occupancy of each different area should be calculated using the relevant space factor.
4. For detailed guidance on appropriate floor space factors for concourses in sports grounds refer to Concourses published by the Football Licensing Authority.
5. Alternatively the occupant number may be taken as the number of fixed seats provided, if the occupants will normally be seated.
6. Shops excluding those under item 10, but including: supermarkets and department stores (main sales areas), shops for personal services, such as hairdressing, and shops for the delivery or collection of goods for cleaning, repair or other treatment or for members of the public themselves carrying out such cleaning, repair or other treatment.
7. Shops (excluding those in covered shopping complexes but including department stores) trading predominantly in furniture, floor coverings, cycles, prams, large domestic appliances or other bulky goods, or trading on a wholesale self-selection basis (cash and carry).

Travel distance

D3

Travel distance is measured as the shortest route. Both of the following should be observed.

a. If there is fixed seating or other fixed obstructions, the shortest route is along the centre line of the seatways and gangways.
b. If the route includes a stair, the shortest route is along the pitch line on the centre line of travel.

Width

D4

Width is measured according to the following.

a. For a door (or doorway), the clear width when the door is open (Diagram D1).
b. For an escape route, either of the following.
i. When the route is defined by walls: the width at 1500mm above finished floor level.
ii. Elsewhere: the minimum width of passage available between any fixed obstructions.
c. For a stair, the clear width between the walls or balustrades. On escape routes and stairs, handrails and strings intruding into the width by a maximum of 100mm on each side may be ignored. Rails used for guiding a stair-lift may be ignored, but it should be possible to park the lift’s chair or carriage in a position that does not obstruct the stair or landing.

Diagram D1 Measurement of door width

Diagram D1 Measurement of door width. Wording on the drawing: E°ective clear E°ective clear width (door stop width (door stop to to projecting door leaf) ironmongery)
Diagram D1 Measurement of door width

Building dimensions

Diagram D2 Cubic capacity

Diagram D2 Cubic capacity. Wording on the drawing: In every case measure the volume contained by all of the following.; a. Under surface of roof. Internal wall Internal wall b. Upper surface of or partition or partition lowest floor. Enclosing wall Enclosing wall Compartment floor c. Inner surface of enclosing walls. Compartment wall When there is not an outer enclosing wall, measure to the; outermost edge of the floor slab. a. Cubic capacity of a building b. Cubic capacity of compartments; or separated part of a building The measured volume should include internal walls and partitions.
Diagram D2 Cubic capacity

Diagram D3 Area

Diagram D3 Area. Wording on the drawing: a. Surface area: roofs and rooflights; In each case measure the visible area; Measure from outermost point of roof at eaves or verge; Lowest point of roof slope; If a hipped roof, asure to outermost t of roof at base area; Roof sheeting; me poin; at eaves; If a lean-to roof, measure from the face of wall to the outermost point of roof; Outermost; Highest point; point of roof; Rooflight; of roof slope; Section Elevation Section; Section; i. Flat or monopitch roof ii. Double pitch roof iii. Rooflight; b. Floor area: c. Floor area: Room, garage, conservatory or outbuilding, Storey, part or compartment, measure to inner surface of enclosing walls measure to inner surface of enclosing walls and include internal walls and partitions; When there is not an outer enclosing wall, measure to the outermost edge of the floor slab
Diagram D3 Area

Diagram D4 Height of building

Diagram D4 Height of building. Wording on the drawing: Highest point; Highest point; Highest point of parapet (including coping); of roof slope; of roof slope; Equal; Mean roof level; Equal; Mean roof level; Lowest point of roof slope; Height of building; a Top level of gutter; b; Highest level; of ground adjacent to outside walls; Mean ground level; Mean ground level; Use height a or b, whichever is greater; Lowest level; a. Double pitch roof; b. Mansard type roof; of ground adjacent to outside walls; Highest point; of roof slope; Mean roof level; Equal; Lowest point of roof slope; Height of building; Highest level; of ground adjacent to outside walls; Mean ground level; Lowest level; c. Flat or monopitch roof; of ground adjacent to outside walls
Diagram D4 Height of building

Diagram D5 Number of storeys

Diagram D5 Number of storeys. Wording on the drawing: Building three storeys; Second; floor; To count the number of storeys in a building, or in a separated part of a building, count only at the position which gives the greatest number and exclude any basement storeys.; First floor; Ground; floor; Basement; Separated part three storeys; Separated part two storeys Second; floor Compartment; NOTES:; wall First floor; 1. In assembly buildings (purpose group 5), a gallery is included as a storey, but not if it is a loading gallery, fly gallery, stage grid, lighting bridge, or any gallery provided for similar purposes, or for maintenance and repair.; Ground; floor; 2. In other purpose group buildings, galleries are not counted as a storey.; Basement; 3. For the definition of basement, see Appendix A.
Diagram D5 Number of storeys

Diagram D6 Height of top storey in building

Diagram D6 Height of top storey in building. Wording on the drawing: Plant; Roof; Height of top storey excludes roof-top plant areas and any top storeys consisting exclusively of plant rooms; Height of top storey measured from upper floor; surface of top floor to ground; level on lowest side of building
Diagram D6 Height of top storey in building

Free area of smoke ventilators

D5

The free area of a smoke ventilator should be measured by either of the following.

a. The declared aerodynamic free area in accordance with BS EN 12101-2.
b. The total unobstructed cross-sectional area (geometric free area), measured in the plane where the area is at a minimum and at right angles to the direction of air flow (Diagram D7).

Diagram D7 Free area of smoke ventilators

Diagram D7 Free area of smoke ventilators. Wording on the drawing: a. b.; Free area measured at right angles to air flow; Free area for louvred; vent = a1+a2+a3+a4+a5; a1 a2 a3 a4 a5; 90°
Diagram D7 Free area of smoke ventilators